Plan Review Details - Permit 20080881
Plan Review Stops For Permit 20080881
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-09-21 Cont ID  
Sent By rmcphers Date 2020-09-21 Time 14:14 Rev Time 0.00
Received By rmcphers Date 2020-09-21 Time 14:14 Sent To  
Notes
2020-09-21 14:15:43PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-21 Cont ID  
Sent By rmcphers Date 2020-09-21 Time 14:14 Rev Time 0.00
Received By rmcphers Date 2020-09-21 Time 13:41 Sent To  
Notes
2020-09-21 14:14:34WINDOW WALL SHOP DRAWINGS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE)
 2) PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 3) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ENGINEER OR ARCHITECT.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-03 Cont ID  
Sent By jleahy Date 2020-09-03 Time 16:03 Rev Time 0.00
Received By jleahy Date 2020-09-03 Time 16:03 Sent To  
Notes
2020-09-03 16:12:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
  
 1) PANEL SCHEDULE STATES PANEL IS 60A? WITH OVER 100A
 LOAD
  
 2) AIC CALCULATION REQUIRED FOR THE SERVICE AND PANEL.
 110.9, 110.10, LABELS REQUIRED PER 110.24
  
 3) SEVERAL LOADS IN PANEL SHOW NO LO0ADS FOR
 CALCULATION.
  
 4) RISER DOES NOT SHOW ANY WIRE SIZES. 120 AMP? SHOW
 WIRE SIZES FOR SUBFEEDER TO PANEL. 215.5
  
 5) 40% IS FOR A RESIDENTIAL CALCULATION AS STATED IN
 YOUR LOAD SUMMARY. 215.5
  
 6) ALL 120VOLT OUTLETS IN KITCHEN AREA TO BE GFCI
 PROTECTED 210.8
  
 7) PLAN SHOWS TWO WATER HEATERS??

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-08-24 Cont ID  
Sent By pleduc Date 2020-08-24 Time   Rev Time 0.00
Received By pleduc Date 2020-08-24 Time 15:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-21 Cont ID  
Sent By rmcphers Date 2020-09-21 Time 14:19 Rev Time 0.00
Received By rmcphers Date 2020-08-20 Time 08:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-27 Cont ID  
Sent By ccole Date 2020-08-27 Time 16:05 Rev Time 0.00
Received By ccole Date 2020-08-27 Time 12:47 Sent To  
Notes
2020-08-27 16:05:521ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20080881
 8/27/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS CVR, A1, & E1: REFER TO TABLE 403.3 AND
 PROVIDE PLUMBING FIXTURES CALCULATIONS FOR THE BUSINESS
 OCCUPANCY. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED FIXTURES. CONCERNING THE REQUIRED
 DRINKING FOUNTAIN FOR BUSINESS OCCUPANCIES, PLEASE
 CORRECT THE NOTE UNDER CODE ANALYSIS ON SHEET CVR. IN
 RESTAURANTS ONLY WHERE DRINKING WATER IS PROVIDED TO
 CUSTOMERS IN A CONTAINER FREE OF CHARGE, DRINKING
 FOUNTAINS SHALL NOT BE REQUIRED- SECTION 410.4. PLEASE
 NOTE DRINKING FOUNTAINS SHALL NOT BE REQUIRED FOR AN
 OCCUPANT LOAD OF 15 OR FEWER- SECTION 410.2.
  
 2) SHEETS CVR, A1, & E1: VERIFY COMPLIANCE WITH SECTION
 403.3 EXCEPTION 2: SEPARATE PLUMBING FIXTURES ARE NOT
 REQUIRED FOR AN OCCUPANT LOAD INCLUDING BOTH EMPLOYEES
 AND CUSTOMERS OF 15 OR FEWER.
  
 3) SHEETS CVR, A1, & E1: SECTION 403.3 REQUIRES THAT
 PUBLIC TOILET FACILITIES SHALL BE PROVIDED FOR
 CUSTOMERS, PATRONS AND VISITORS TO THE NEW TENANT SPACE
 UNLESS EXCEPTION 2 UNDER 403.3 IS APPLICABLE. PLEASE
 VERIFY COMPLIANCE WITH EXCEPTION 2 UNDER 403.3, OR
 PROVIDE A PUBLIC TOILET ROOM. PLEASE NOTE THAT PUBLIC
 ACCESS THROUGH THE KITCHEN AREA TO THE TOILET ROOM AT
 BOH IS NOT ALLOWED PER SECTION 403.3.1.
 SECTION 403.3 EXCEPTION 2: PUBLIC TOILET FACILITIES
 SHALL NOT BE REQUIRED IN STRUCTURES AND TENANT SPACES
 INTENDED FOR QUICK TRANSACTIONS, INCLUDING TAKEOUT,
 PICKUP AND DROP-OFF, HAVING A PUBLIC ACCESS AREA LESS
 THAN OR EQUAL TO 300 SQUARE FEET.
  
 4) A1 & E1: THE NEW TOILET ROOM SHALL BE DESIGNED IN
 ACCORDANCE WITH THE FLORIDA ACCESSIBILITY CODE- 2017
 SIXTH EDITION. REFER TO SECTION 213 AND PROVIDE
 ENLARGED, DIMENSIONED TOILET ROOM DRAWINGS SHOWING:
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAMETER- SECTION 304.3.
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SECTION 604.4.
 F) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3
 G) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 306.
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5 & 609.4
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 J) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE
 TOILET PAPER DISPENSER- SECTION 604.7.
 L) HEIGHT OF THE MIRROR FROM THE FINISHED FLOORS TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3.
  
 5) A1: PROVIDE AN INTERIOR FINISH MATERIAL SCHEDULE FOR
 THE NEW TOILET ROOM- SECTION 310.3 FBC P.
  
 6) E1: IT APPEARS THAT THE SANITARY RISER DOES NOT
 REPRESENT THE NEW TOILET ROOM DRAIN AND VENT SYSTEM AND
 IS SHOWING THE GREASE WASTE SYSTEM. PLEASE CORRECT PER
 SECTION 107.2.1 AND 107.3.5.1 WPB.
  
 7) E1: CORRECT THE 3-COMPARTMENT SINK/GREASE TRAP
 DETAIL AND THE GREASE TRAP RISER IN ACCORDANCE WITH
 SECTIONS 802.1.8 & 802.2 FBC P. EACH WELL OF A
 MULTIPLE-COMPARTMENT SINK SHALL DISCHARGE INDEPENDENTLY
 TO A WASTE RECEPTOR,
 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS.
 SINKS, IN OTHER THAN DWELLING UNITS, USED FOR THE
 WASHING, RINSING OR SANITIZING OF UTENSILS, DISHES,
 POTS, PANS OR SERVICE WARE USED IN THE PREPARATION,
 SERVING OR EATING OF FOOD SHALL DISCHARGE INDIRECTLY
 THROUGH AN AIR GAP OR AN AIR BREAK TO THE DRAINAGE
 SYSTEM.
 802.2 INSTALLATION.
 INDIRECT WASTE PIPING SHALL DISCHARGE THROUGH AN AIR
 GAP OR AIR BREAK INTO A WASTE RECEPTOR. WASTE RECEPTORS
 SHALL BE TRAPPED AND VENTED AND SHALL CONNECT TO THE
 BUILDING DRAINAGE SYSTEM. INDIRECT WASTE PIPING THAT
 EXCEEDS 30 INCHES (762 MM) IN DEVELOPED LENGTH MEASURED
 HORIZONTALLY, OR 54 INCHES (1372 MM) IN TOTAL DEVELOPED
 LENGTH, SHALL BE TRAPPED.
  
 8) E-1: IT APPEARS THAT THE FLOOR SINK FOR THE
 3-COMPARTMENT SINK IS MISLABELED AS A FLOOR DRAIN, AND
 THE ROOM FLOOR DRAIN IS MISSING FROM THE RISER- SEE
 SECTION 802.3.1.
  
 9) E-1: TRAP SEAL PROTECTION IS REQUIRED FOR THE FLOOR
 DRAIN- SECTION 1002.4.1 & 1002.4.1.1. PLEASE NOTE THAT
 TRAP SEAL PRIMER VALVES SHALL CONFORM TO ASSE 1018.
  
 10) E-1 GREASE TRAP RISER: THE MOP SINK AND
 3-COMPARTMENT SINK TRAPS REQUIRE VENTING PER SECTIONS
 901.2.1 AND 802.2.
  
 11) E-1 GREASE TRAP RISER: WITHIN EACH PLUMBING SYSTEM,
 NOT LESS THAN ONE STACK VENT OR VENT STACK SHALL EXTEND
 OUTDOORS TO THE OPEN AIR- SECTION 918.7.
  
 12) E-1 GREASE INTERCEPTOR: A) PROVIDE AN EQUIPMENT
 SCHEDULE FOR THE NEW INTERCEPTOR INDICATING THE MAKE,
 MODEL AND GALLON SIZE- SECTION 1003.3.4 B) PROVIDE
 GREASE WASTE CALCULATIONS IN ACCORDANCE WITH SECTION
 AND TABLE 1003.3.4.1. C) PROVIDE A PLUMBING PIPING
 DETAIL IN THE PLAN CONSISTENT WITH THE MANUFACTURER'S
 GUIDELINES FOR INSTALLATION- SECTION 1003.3.4.1.
  
 13) E-1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW
 TANKLESS WATER HEATER. PLEASE CLARIFY WHY THERE ARE TWO
 WATER HEATERS SHOWN ON THE PLANS- SECTION 107.2.1 WPB.
  
 14) E-1: PROVIDE A WATER DISTRIBUTION RISER SHOWING THE
 SUPPLY PIPING RUNS TO THE PLUMBING FIXTURES, AND
 LOCATIONS OF SHUT OFF VALVES, AND OTHER DEVICES SUCH AS
 WATER HAMMER ARRESTORS, BACKFLOW PREVENTERS, AND MIXING
 VALVES- SECTION 107.3.5.1 WPB.
  
 15) E-1: INDICATE HOW REQUIRED TEMPERED WATER WILL BE
 PROVIDE TO THE LAVATORY SINK- SECTION 416.5 FBC P.
 PLEASE NOTE THAT TEMPERATURE LIMITING DEVICES SUCH AS
 MIXING VALVES SHALL CONFORM TO ASSE 1070 OR CSA B125.3.
  
 16) E-1: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE
 ON THE PLAN- SECTION 401.1 FBC P 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-21 Cont ID  
Sent By rmcphers Date 2020-09-21 Time 14:17 Rev Time 0.00
Received By rmcphers Date 2020-09-21 Time 14:17 Sent To  
Notes
2020-09-21 14:18:42SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.
2020-09-03 16:13:34ELECTRICAL PAGE NOT SIGNED JLEAHY