Plan Review Details - Permit 20080790
Plan Review Stops For Permit 20080790
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-09-23 Cont ID  
Sent By fgiaquin Date 2020-09-23 Time 23:34 Rev Time 0.00
Received By fgiaquin Date 2020-09-23 Time 22:41 Sent To  
Notes
2020-09-23 23:34:36ARC-FAULT, TAMPERPROOF RECEPTACLES AND SMOKE DETECTORS
 REQUIRED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-09-13 Cont ID  
Sent By fgiaquin Date 2020-09-13 Time 14:00 Rev Time 0.00
Received By fgiaquin Date 2020-09-13 Time 12:56 Sent To  
Notes
2020-09-13 13:32:10ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ANY NEW METERS THAT ARE BEING REQUESTED MUST BE
 APPROVED BY THE ZONING DEPARTMENT.
  
 2. REPLACEMENT OF ELECTRICAL RECEPTACLES SHALL COMPLY
 WITH THE APPLICABLE REQUIREMENTS OF SECTION 406.4(D) OF
 NFPA 70 (AFCI & TAMPERPROOF). PER FBC-EB 607.1.1
  
 3. PROVIDE ONE-LINE DIAGRAM OF EXISTING SERVICE SHOWING
 ALL SERVICE DISCONNECTING MEANS, ALONG WITH LOCATION TO
 INCLUDE 2 NEW METER MAINS PROPOSED. NEC 215.5; WPB FBC
 107.2.1
  
 4. ARE 2 NEW METERS TO BE NEW SERVICES? FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-25 Cont ID  
Sent By ppetty Date 2020-08-25 Time 11:36 Rev Time 0.00
Received By ppetty Date 2020-08-25 Time 11:36 Sent To  
Notes
2020-08-25 11:38:28SCOPE,NOTES AND APPLICATION CONFLICT PLEASE REVISE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-13 Cont ID  
Sent By fgiaquin Date 2020-09-13 Time 14:00 Rev Time 0.00
Received By fgiaquin Date 2020-09-03 Time 17:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-25 Cont ID  
Sent By ppetty Date 2020-08-25 Time 11:38 Rev Time 0.00
Received By ppetty Date 2020-08-18 Time 14:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-13 Cont ID  
Sent By fgiaquin Date 2020-09-13 Time 13:36 Rev Time 0.00
Received By fgiaquin Date 2020-09-13 Time 13:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-25 Cont ID  
Sent By medwards Date 2020-08-25 Time 13:06 Rev Time 0.00
Received By medwards Date 2020-08-25 Time 13:06 Sent To  
Notes
***NONE***