Plan Review Details - Permit 20080765
Plan Review Stops For Permit 20080765
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-10-20 Cont ID  
Sent By rmcphers Date 2020-10-20 Time 08:38 Rev Time 0.00
Received By rmcphers Date 2020-10-20 Time 08:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-07 Cont ID  
Sent By cthroop Date 2020-10-07 Time 16:26 Rev Time 0.00
Received By cthroop Date 2020-10-07 Time 15:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-21 Cont ID  
Sent By rmcphers Date 2020-09-21 Time 12:42 Rev Time 0.00
Received By rmcphers Date 2020-09-21 Time 11:30 Sent To  
Notes
2020-09-21 12:42:00ROOFED PATIO AND REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE ATTIC VENTILATION FOR THE OUTDOOR
 PATIO TO COMPLY WITH FBC R806.1
 2) PLEASE SHOW THE ATTIC ACCESS SIZE AND LOCATION FOR
 THE OUTDOOR PATIO TO COMPLY WITH FBC R807.1
 3) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE ROOFING SHINGLES.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-10-19 Cont ID  
Sent By jleahy Date 2020-10-19 Time 17:35 Rev Time 0.00
Received By jleahy Date 2020-10-19 Time 17:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-07 Cont ID  
Sent By cthroop Date 2020-10-07 Time 16:24 Rev Time 0.00
Received By cthroop Date 2020-10-07 Time 15:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-31 Cont ID  
Sent By cthroop Date 2020-08-31 Time 10:11 Rev Time 0.00
Received By cthroop Date 2020-08-31 Time 09:15 Sent To  
Notes
2020-08-31 10:26:28PLAN REVIEW - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE NEW LOAD CALC'S FOR 200 AMP MAIN PANEL THAT
 INCLUDES THE NEW SUMMER KITCHEN LOADS.
 PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL LOADS
 FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS FOR
 THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2.
  
 2. PROVIDE GROUNDING ELECTRODE SYSTEM OR EQUIPMENT
 GROUNDING CONDUCTOR TO FOR THE NEW SUMMER KITCHEN SUB
 PANEL.
 PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUT. NEC 250; FBC RE 3607.3.
  
 3. PROVIDE KITCHEN OUTLET SPACING PER E3901.4.
 E3901.4.1 WALL COUNTERTOP SPACE.
 A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE 12 INCHES (305 MM) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 24 INCHES (610 MM),
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE. [210.52(C)(1)]
 EXCEPTION: RECEPTACLE OUTLETS SHALL NOT BE REQUIRED ON
 A WALL DIRECTLY BEHIND A RANGE, COUNTER-MOUNTED COOKING
 UNIT OR SINK IN THE INSTALLATION DESCRIBED IN FIGURE
 E3901.4.1. [210.52(C)(1) EXCEPTION]
  
 E3902.6 KITCHEN RECEPTACLES.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 THAT SERVE COUNTERTOP SURFACES SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 [210.8(A)(6)]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2020-10-07 Cont ID  
Sent By lcrespo Date 2020-10-07 Time 09:03 Rev Time 0.00
Received By lcrespo Date 2020-10-07 Time 09:03 Sent To  
Notes
2020-10-07 09:04:08GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-08-26 Cont ID  
Sent By lcrespo Date 2020-08-26 Time 10:25 Rev Time 0.00
Received By lcrespo Date 2020-08-26 Time 10:25 Sent To  
Notes
2020-08-26 11:22:2108/26/20 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A-6;
 A. IT SHOWS A GRILL, IS THIS GRILL CONNECTED TO A CITY
 GAS SOURCE OR IS IT A PROPANE TANK TYPE, PLEASE
 CLARIFY.
  
 B. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR GAS GRILL EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1.
  
 C. THE GAS GRILL SEEMS TO BE IN A COVERED PATIO, IF SO,
 PLEASE PROVIDE MANUFACTURES RECOMMENDATION FOR A
 VENTILATION OF A HOOD PER THE 2017 FBC RES. SEC.
 G2408.1.
  
 D. THIS GRILL MAY REQUIRE VENT TO THE BASE CABINET SO
 PLEASE PROVIDE MANUFACTURES SPECIFICATION TO VERIFY
 WHERE AND HOW MANY MAY BE NEEDED PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 2. A SUB GAS PERMIT MAY BE REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1 WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT THIS TIME.
 A SEPARATE GAS PERMIT AND PLANS MAY BE SUBMITTED.
 PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE
 ENTIRE SCOPE OF GAS WORK TO BE DONE PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-20 Cont ID  
Sent By rmcphers Date 2020-10-20 Time 08:38 Rev Time 0.00
Received By rmcphers Date 2020-10-09 Time 08:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-08 Cont ID  
Sent By medwards Date 2020-10-08 Time 07:51 Rev Time 0.00
Received By medwards Date 2020-10-06 Time 11:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-21 Cont ID  
Sent By rmcphers Date 2020-09-21 Time 12:45 Rev Time 0.00
Received By rmcphers Date 2020-08-20 Time 14:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By medwards Date 2020-10-13 Time 10:11 Rev Time 0.00
Received By medwards Date 2020-10-13 Time 10:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-10-08 Cont ID  
Sent By medwards Date 2020-10-08 Time 07:50 Rev Time 0.00
Received By medwards Date 2020-10-08 Time 06:50 Sent To  
Notes
2020-10-08 07:50:471ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20080765
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE SPECIFICATIONS FOR THE PORTABLE GAS GRILLS.
 FBC 107.2.1
  
 2) PLEASE PROVIDE THE SPECIFICATION SHEETS FOR BOTH OF
 THE NEW HOODS. FBC 107.2.1
  
 3) PLEASE SHOW THE PORTABLE GAS GRILL IN THE REMODELED
 KITCHEN FOR THE INTERIOR OF THE HOME MEETS FBC RES
 M1901.2
  
 4) PLEASE SHOW CLEARANCES REQUIRED FOR THE COOKING
 APPLIANCES TO COMBUSTIBLE MATERIALS FOR BOTH PORTABLE
 GAS GRILLS. FBC RES M1901.1
  
 5) PLEASE SHOW MAKE UP AIR REQUIRED FOR THE INDOOR
 KITCHEN HOOD. FBC RES M1503.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-10-07 Cont ID  
Sent By lcrespo Date 2020-10-07 Time 08:51 Rev Time 0.00
Received By lcrespo Date 2020-10-07 Time 08:51 Sent To  
Notes
2020-10-07 08:53:0410/07/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-26 Cont ID  
Sent By lcrespo Date 2020-08-26 Time 10:25 Rev Time 0.00
Received By lcrespo Date 2020-08-26 Time 09:57 Sent To  
Notes
2020-08-26 11:03:0708/26/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. ON SHEET A-6 PLEASE PROVIDE A SOURCE AND LOCATION OF
 HOT WATER PER THE 2017 RES R 2722.2 HOT WATER.
  
 2. ON SHEET A-6 PLUMBING ISOMETRIC BETWEEN THE SHOWER
 AND TOILET NEED TO HAVE VENT AND YOU MAY USE THE LAV
 PER THE 2017 FBC SEC. REC R 3101.2.
  
 3. ON SHEET A-6 THERE IS AN ARROW FOR DIRECTION OF
 FLOW, AND IT IS SHOWING A 2" LINE BETWEEN TWO 3"
 CONNECTIONS, PLEASE SHOW THE FLOW TO CITY LATERAL AND
 SHOW CLEAN OUT OUTSIDE BUILDING ALONG WITH DESTINATION
 OF PIPE FORM OR TO SEWER. IF YOU HAVE THE MAIN HOUSE IN
 FRONT, PLEASE LABEL ACCORDINGLY PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1.4 QUALITY OF BUILDING PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2020-10-20 Cont ID  
Sent By rmcphers Date 2020-10-20 Time 08:38 Rev Time 0.00
Received By rmcphers Date 2020-10-20 Time 08:38 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-10-07 Cont ID  
Sent By cthroop Date 2020-10-07 Time 16:22 Rev Time 0.00
Received By cthroop Date 2020-10-07 Time 16:22 Sent To  
Notes
2020-10-07 16:24:11PLAN REVIEW / ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLANS CALL FOR ROOFING SHINGLES. NOA SUBMITTED FOR
 REVIEW IS FOR CONCRETE ROOF TILES.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-13 Cont ID  
Sent By medwards Date 2020-10-13 Time 10:14 Rev Time 0.00
Received By medwards Date 2020-10-13 Time 10:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-07 Cont ID  
Sent By cthroop Date 2020-10-07 Time 16:26 Rev Time 0.00
Received By cthroop Date 2020-10-07 Time 15:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-21 Cont ID  
Sent By rmcphers Date 2020-09-21 Time 12:45 Rev Time 0.00
Received By rmcphers Date 2020-09-21 Time 12:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-10-07 Cont ID  
Sent By rthermid Date 2020-10-07 Time   Rev Time 0.00
Received By rthermid Date 2020-10-07 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-09-01 Cont ID  
Sent By rthermid Date 2020-09-01 Time   Rev Time  
Received By rthermid Date 2020-09-01 Time   Sent To I
Notes
2020-09-01 12:00:17ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 9/1/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE THE SETBACKS OF THE PROPOSED KITCHEN TO THE
 PROPERTY LINES. THE REQUIRED SIDE SETBACK IS 8 FEET.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved