2021-08-20 17:55:01PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [THE APPLICATION IS INCORRECT. THIS IS NOT A
 SUB-PERMIT. GENERATORS REQUIRE A SEPARATE PERMIT. THE
 FURTHER DESCRIPTION OF WORK STATES NEW CONSTRUCTION OF
 A 2-STORY SINGLE FAMILY RESIDENCE... THIS SECTION IS
 INTENEDED TO DESCRIBE THE WORK THAT IS TO BE DONE UNDER
 THIS PERMIT.SUBMIT A CORRECTED APPLICATION.] (PREVIOUS
 COMMENT) THIS PERMIT IS FOR THE INSTALLATION OF A
 RESIDENTIAL GENERATOR. CORRECT THE DESCRIPTION OF WORK
 ON THE PERMIT APPLICATION. FBC 105
  
 2) COMPLIED. SUBMIT THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE GENERATOR. FBC
 107.2.1
  
 3) COMPLIED. PROVIDE DETAILS OF THE GENERATOR PAD AND
 SPECIFY HOW IT WILL BE ATTACHED TO THE SLAB IN ORDER TO
 RESIST THE WINDLOADS. FBC-R301
  
 4) COMPLIED. THIS PROJECT IS LOCATED IN A SPECIAL FLOOD
 HAZARD. THE GENERATOR IS REQUIRED TO ABOVE THE DFE OF
 9' NAVD. FBC-R322
  
 5) [THIS REQUIREMENT NEEDS TO BE STATED ON THE SITE
 PLAN OR SHOWN ON THE DRAWINGS.] THE GENERATOR EXHAUST
 IS REQUIRED TO BE 10' FROM ANY OPENINGS INTO THE
 BUILDING PER FBC-R303.5.1.
  
 6) AN ELECTRICAL SUB-PERMIT IS REQUIRED FOR THE
 GENERATOR. FBC AMENDMENTS105
  
 7) A SEPARATE PERMIT IS REQUIRED FOR GAS. FBC
 AMENDMENTS105

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-22 Cont ID  
Sent By rmcdouga Date 2020-12-22 Time 13:36 Rev Time 0.00
Received By rmcdouga Date 2020-12-22 Time 13:35 Sent To  
Notes
2020-12-22 13:53:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS PERMIT IS FOR THE INSTALLATION OF A RESIDENTIAL
 GENERATOR. CORRECT THE DESCRIPTION OF WORK ON THE
 PERMIT APPLICATION. FBC 105
  
 2) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE GENERTATOR. FBC
 107.2.1
  
 3) PROVIDE DETAILS OF THE GENERATOR PAD AND SPECIFY HOW
 IT WILL BE ATTACHED TO THE SLAB IN ORDER TO RESIST THE
 WINDLOADS. FBC-R301
  
 4) THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD.
 THE GENERATOR IS REQUIRED TO ABOVE THE DFE OF 9' NAVD.
 FBC-R322
  
 5) THE GENERATOR EXHAUST IS REQUIRED TO BE 10' FROM ANY
 OPENINGS INTO THE BUIOLDING PER FBC-R303.5.1.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-03-05 Cont ID  
Sent By cthroop Date 2022-03-05 Time 10:37 Rev Time 0.00
Received By cthroop Date 2022-03-05 Time 10:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-08-05 Cont ID  
Sent By jleahy Date 2021-08-05 Time 15:18 Rev Time 0.00
Received By jleahy Date 2021-08-05 Time 15:06 Sent To  
Notes
2021-08-05 15:21:38ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 YOU HAVE COMMENTS FROM TWO DIFFERENT PERMITS MIXED
 TOGETHER GEN-RES AND NEW SINGLE FAMILY PLEASE
 COORDINATE COMMENT FOR EACH PERMIT SEPARATELY.
 20080737 AND 20070078

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-03 Cont ID  
Sent By cthroop Date 2020-12-03 Time 15:09 Rev Time 0.00
Received By cthroop Date 2020-12-03 Time 14:57 Sent To  
Notes
2020-12-03 15:24:29PLAN REVIEW GENERATOR / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER
 SWITCH. ATS
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2) PROVIDE CURRENT COPY OF GENERATOR SPECIFICATIONS.
 KOHLER MODEL 125ERESC.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3) CORRECT DESCRIPTION OF WORK ON GENERATOR PERMIT
 APPLICATION. DESCRIPTION IS OF NEW SFR.
 PERMITS - 105.1 REQUIRED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-08-03 Cont ID  
Sent By lcrespo Date 2021-08-03 Time 16:58 Rev Time 0.00
Received By lcrespo Date 2021-08-03 Time 14:00 Sent To  
Notes
2021-08-03 17:00:04GAS PERMIT UNDER 20080735 AND ALSO APPROVED ON MASTER
 20070078

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-12-03 Cont ID  
Sent By medwards Date 2020-12-03 Time 16:32 Rev Time 0.00
Received By medwards Date 2020-12-03 Time 13:33 Sent To  
Notes
2020-12-03 16:32:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20080737
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FG
 SECS. 402.4.1, 402.4.2. OR 2017 FBC RES. SECS.
 G2413.4.1, G2413.4.2.
  
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FG SEC. 409.4,
 2017 FBC RES. SEC. G2420.4.
  
 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FG SECS.
 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) THROUGH
 402.4 (37) OR 2017 FBC RES. SEC. G2413.
  
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 FG SEC. 402.4.1 OR 2017 FBC RES. SEC. G2413.4.1.
  
 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FG SEC. 402.2 OR 2017 FBC RES.
 SEC. G2413.2
  
 7) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC FG SEC. 304.1
  
 8) SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FG SEC.305.1 OR 2017
 FBC RES. SEC. G2408.1.
  
 9) SUBMIT A COPY OF THE SIZING TABLE USED IN THE DESIGN
 FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF
 PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC FG SEC. 402.3 OR 2017 FBC RES.
 SEC. G2413.3
  
 10) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC FG SEC. 410.1 OR 2017 FBC
 RES. SEC. G2421.1.
  
 11) PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF
 EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2 OR 2017
 FBC FG SEC 410.2.
  
 12) SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017
 FBC RES. SEC. G2419.2 OR 2017 FBC FG 408.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-05 Cont ID  
Sent By cthroop Date 2022-03-05 Time 10:37 Rev Time 0.00
Received By cthroop Date 2022-02-16 Time 10:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-20 Cont ID  
Sent By rmcdouga Date 2021-08-20 Time 17:58 Rev Time 0.00
Received By rmcdouga Date 2021-07-27 Time 10:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-21 Cont ID  
Sent By cpuell Date 2021-01-21 Time 09:32 Rev Time 0.00
Received By cpuell Date 2020-12-02 Time 17:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-08-03 Cont ID  
Sent By lcrespo Date 2021-08-03 Time 17:00 Rev Time 0.00
Received By lcrespo Date 2021-08-03 Time 14:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-12-11 Cont ID  
Sent By cthroop Date 2020-12-11 Time 16:39 Rev Time 0.00
Received By cthroop Date 2020-12-11 Time 16:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-03-02 Cont ID  
Sent By rmcdouga Date 2022-03-02 Time 14:55 Rev Time 0.00
Received By rmcdouga Date 2022-03-02 Time 14:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-08-20 Cont ID  
Sent By rmcdouga Date 2021-08-20 Time 17:55 Rev Time 0.00
Received By rmcdouga Date 2021-08-20 Time 17:55 Sent To  
Notes
2021-08-20 17:57:49THE DRAWINGS THAT WERE SUBMITTED FROM ALEXANDER
 ROCHELL, P.E. 60735 DO NOT HAVE A DIGITAL SIGNATURE.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 487 & 61G1 OR FS 471 &
 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-03 Cont ID  
Sent By cthroop Date 2020-12-03 Time 14:55 Rev Time 0.00
Received By cthroop Date 2020-12-03 Time 14:55 Sent To  
Notes
2020-12-03 14:56:56PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: ELECTRIC PLAN PAGES E-200/E-201/E-203 MISSING VALID
 DIGITAL SIGNATURE
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-23 Cont ID  
Sent By asangele Date 2022-02-23 Time   Rev Time 0.00
Received By asangele Date 2022-02-23 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-01-19 Cont ID  
Sent By kalexand Date 2021-01-19 Time 14:24 Rev Time 0.00
Received By kalexand Date 2021-01-19 Time 14:24 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved