Plan Review Details - Permit 20080735
Plan Review Stops For Permit 20080735
Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-03-15 Cont ID  
Sent By jleahy Date 2021-03-15 Time 08:09 Rev Time 0.00
Received By jleahy Date 2021-03-15 Time 08:09 Sent To  
Notes
2021-03-15 08:13:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PERMIT STATES BUILDING A NEW SFH $15,000 SEEMS LOW FOR
 A HOUSE.
  
 WHAT IS THE PERMIT FOR? GENERATOR !! IF SO THAT'S WHAT
 THE PERMIT SHOULD SAY.
  
 PLEASE SUBMIT A NEW APPLICATION STATING WHAT EXACTLY
 PERMIT IS FOR.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-15 Cont ID  
Sent By jleahy Date 2021-01-15 Time 09:10 Rev Time 0.00
Received By jleahy Date 2021-01-15 Time 09:04 Sent To  
Notes
2021-01-15 09:12:47WHY ARE THERE ELECTRICAL PLANS SUBMITTED WITH A GAS
 PERMIT? JLEAHY
  
 PLEASE EXPLAIN OR CHANGE PERMIT TO A RESUB PERMIT TYPE.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-03-19 Cont ID  
Sent By ccole Date 2021-03-19 Time 16:44 Rev Time 0.00
Received By ccole Date 2021-03-19 Time 15:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-02-16 Cont ID  
Sent By medwards Date 2021-02-16 Time 17:21 Rev Time 0.00
Received By medwards Date 2021-02-16 Time 17:21 Sent To  
Notes
2021-02-16 17:21:391ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20080735
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ACTUAL BTU?S OF THIS SYSTEM IS 3,147,000. THE PE
 PIPING FROM THE JOINT AT MAIN LINE GOING TO THE HOUSE
 IS UNDERSIZED. THIS PE PIPING SHOULD BE 1 ?? AND NOT 1
 ??. FBC G TABLE 402.4 (22).
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-12-09 Cont ID  
Sent By medwards Date 2020-12-09 Time 10:31 Rev Time 0.00
Received By medwards Date 2020-12-09 Time 10:31 Sent To  
Notes
2020-12-09 10:32:58ORIGINAL REVIEW WAS COMPLETED FOR THE GAS IN STOP FOR
 PERMIT# 20080737. I COPIED AND PASTED THE COMMENTS TO
 THIS PERMIT.
 ME
2020-12-09 10:31:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20080737
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FG
 SECS. 402.4.1, 402.4.2. OR 2017 FBC RES. SECS.
 G2413.4.1, G2413.4.2.
  
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FG SEC. 409.4,
 2017 FBC RES. SEC. G2420.4.
  
 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FG SECS.
 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) THROUGH
 402.4 (37) OR 2017 FBC RES. SEC. G2413.
  
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 FG SEC. 402.4.1 OR 2017 FBC RES. SEC. G2413.4.1.
  
 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FG SEC. 402.2 OR 2017 FBC RES.
 SEC. G2413.2
  
 7) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC FG SEC. 304.1
  
 8) SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FG SEC.305.1 OR 2017
 FBC RES. SEC. G2408.1.
  
 9) SUBMIT A COPY OF THE SIZING TABLE USED IN THE DESIGN
 FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF
 PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC FG SEC. 402.3 OR 2017 FBC RES.
 SEC. G2413.3
  
 10) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC FG SEC. 410.1 OR 2017 FBC
 RES. SEC. G2421.1.
  
 11) PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF
 EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2 OR 2017
 FBC FG SEC 410.2.
  
 12) SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017
 FBC RES. SEC. G2419.2 OR 2017 FBC FG 408.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-03-19 Time   Rev Time 0.00
Received By ccarvaja Date 2021-03-12 Time 12:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-16 Cont ID  
Sent By medwards Date 2021-02-16 Time 17:29 Rev Time 0.00
Received By medwards Date 2021-01-11 Time 10:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-09 Cont ID  
Sent By medwards Date 2020-12-09 Time 10:37 Rev Time 0.00
Received By medwards Date 2020-12-02 Time 09:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status N Date 2021-03-19 Cont ID  
Sent By ccole Date 2021-03-19 Time 15:08 Rev Time 0.00
Received By ccole Date 2021-03-19 Time 15:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-02-16 Cont ID  
Sent By medwards Date 2021-02-16 Time 17:28 Rev Time 0.00
Received By medwards Date 2021-02-16 Time 17:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-01-15 Cont ID  
Sent By ccole Date 2021-01-15 Time 07:19 Rev Time 0.00
Received By ccole Date 2021-01-15 Time 07:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-12-09 Cont ID  
Sent By ccole Date 2020-12-09 Time 08:43 Rev Time 0.00
Received By ccole Date 2020-12-09 Time 07:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-03-19 Cont ID  
Sent By ccole Date 2021-03-19 Time 16:44 Rev Time 0.00
Received By ccole Date 2021-03-19 Time 15:09 Sent To  
Notes
2021-03-19 16:51:493RD SIGNATURE REVIEW
 PERMIT- 20080735
 3/19/2021
  
 CODES IN EFFECT:
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A100 & A101A ARE NOT DIGITALLY SIGNED AND
 SEALED BY THE ARCHITECT- FL STATUTE 481.221 AND SECTION
 61G1-16.005 FLORIDA ADMINISTRATIVE CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-02-16 Cont ID  
Sent By medwards Date 2021-02-16 Time 17:26 Rev Time 0.00
Received By medwards Date 2021-02-16 Time 17:26 Sent To  
Notes
2021-02-16 17:27:43THE REVISED DRAWING OF THE SITE PLAN DOES NOT HAVE THE
 DIGITAL SIGNATURE OR SEAL FROM THE DESIGNER, PLEASE
 PROVIDE A DIGITALLY SIGNED AND SEALED SITE DRAWING.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-09 Cont ID  
Sent By medwards Date 2020-12-09 Time 10:36 Rev Time 0.00
Received By medwards Date 2020-12-09 Time 10:36 Sent To  
Notes
***NONE***