Plan Review Details - Permit 20080672
Plan Review Stops For Permit 20080672
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-19 Cont ID  
Sent By lmarchan Date 2020-08-19 Time 11:05 Rev Time 0.00
Received By lmarchan Date 2020-08-18 Time 08:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-17 Cont ID  
Sent By hmoser Date 2020-08-17 Time 11:25 Rev Time 0.00
Received By hmoser Date 2020-08-14 Time 10:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-08-19 Cont ID  
Sent By medwards Date 2020-08-19 Time 09:16 Rev Time 0.00
Received By medwards Date 2020-08-19 Time 08:28 Sent To  
Notes
2020-08-19 09:19:13I CALLED CONTRACTOR, THE CLOSEST HAVE A DROPPED CEILING
 AND THE RETURN AIR GRILL IN THE BEDROOMS IS ABOVE THAT
 CEILING SO NO RETURN AIR IS PASSING THROUGH THE CLOSET.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-08-17 Cont ID  
Sent By hmoser Date 2020-08-17 Time 11:12 Rev Time 0.00
Received By hmoser Date 2020-08-17 Time 09:44 Sent To  
Notes
2020-08-17 11:12:25PLAN DENIED
 REFER TO SECTION M1602.2 RETURN AIR OPENINGS
 RETURN AIR CAN'T BE TAKEN FROM A CLOSET 2017
 RESIDENTIAL CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-605-6732
 FAX 561-805-6676

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-17 Cont ID  
Sent By hmoser Date 2020-08-17 Time 11:25 Rev Time 0.00
Received By hmoser Date 2020-08-17 Time 11:25 Sent To  
Notes
***NONE***