Plan Review Stops For Permit 20080620 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2020-11-24 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-11-24 |
Time |
12:33 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-11-24 |
Time |
12:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-11-12 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-11-12 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-11-12 |
Time |
10:38 |
Sent To |
|
|
Notes |
2020-11-12 10:44:13 | SFR ADDITION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | 2ND REVIEW | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW THE REQUIRED SMOKE DETECTORS FOR THE | | MAIN HOUSE FBC R314.2.2 ALTERATIONS, REPAIRS AND | | ADDITIONS. | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-09-30 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-09-30 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-09-30 |
Time |
10:47 |
Sent To |
|
|
Notes |
2020-09-30 13:22:52 | SFR REMODEL AND DETACHED GUEST/GARAGE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW THE REQUIRED SMOKE DETECTORS FOR THE | | MAIN HOUSE FBC R314.2.2 ALTERATIONS, REPAIRS AND | | ADDITIONS. | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | 2) PLEASE SHOW THE REQUIRED ATTIC VENTILATION FOR THE | | ADDITION ON THE MAIN HOUSE (TRUSSED AREA AND FLAT ROOF | | AREA) - R806.1VENTILATION REQUIRED. | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE | | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE | | ENTRANCE OF RAIN OR SNOW. | | 3) R30 INSULATION WILL NOT PROVIDE THE REQUIRED AIR | | CLEARANCE FOR VENTILATION IN THE 2X8 RAFTERS PER FBC | | R806.3 VENT AND INSULATION CLEARANCE. | | WHERE EAVE OR CORNICE VENTS ARE INSTALLED, INSULATION | | SHALL NOT BLOCK THE FREE FLOW OF AIR. NOT LESS THAN A | | 1-INCH (25 MM) SPACE SHALL BE PROVIDED BETWEEN THE | | INSULATION AND THE ROOF SHEATHING AND AT THE LOCATION | | OF THE VENT. | | 4) PLEASE SHOW THE ATTACHMENT TYPE AND ON CENTER | | SPACING FOR THE 3/4" ROOF SHEATHING/DECKING ON THE MAIN | | HOUSE ADDITION. | | 5) THE GENERATOR LOCATION NEEDS TO BE 10' AWAY FROM | | OPENINGS TO COMPLY WITH FBC R303.5.1 INTAKE OPENINGS. | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, | | 6) PLEASE CIRCLE OR INDICATE HOW THE ROOF TILE IS TO BE | | ATTACHED ON THE ROOF TILE PRODUCT APPROVAL PROVIDED. IF | | ATTACHED WITH ADHESIVE PLEASE PROVIDE THE MIAMI DADE OR | | FLORIDA STATE PRODUCT APPROVAL FOR THE ADHESIVE. | | 7) PLEASE PROVIDE AN UPDATED SURVEY ALONG WITH THE SITE | | PLAN PROVIDED SHOWING ALL THE REQUIRED ITEMS PER FBC | | WPB AMENDMENTS 107.2.5 SITE PLAN. THE CONSTRUCTION | | DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT | | SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE | | THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING | | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE | | ESTABLISHED | | STREET GRADES AND THE PROPOSED FINISHED GRADES, | | DEPICTING THE PROPOSED LOT DRAINAGE AND, AS APPLICABLE, | | FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD | | ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN | | ACCURATE AND INCLUDED ON A BOUNDARY LINE SURVEY. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2020-09-24 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-09-24 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-09-24 |
Time |
11:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
2020-10-26 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-10-26 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-10-26 |
Time |
11:51 |
Sent To |
|
|
Notes |
2020-10-26 11:51:51 | THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | CONDITION(S): | | | | 1. ALL EXTERIOR DOOR AND WINDOW FRAMES SHALL HAVE WHITE | | OR BRONZE FINISH. | | 2. ALL MUNTINS SHALL HAVE AN EXTERNAL DIMENSIONAL | | PROFILE. FOR PGT PRODUCTS THIS IS A RAISED PYRAMID. FOR | | OTHER PRODUCTS, THE PRODUCT MUST HAVE AN OGEE OR A | | PYRAMID. | | 3. ALL GLASS SHALL BE CLEAR GLASS OR CLEAR GLASS WITH | | LOW-E COATING. A NON-STREET FACING BATHROOM MAY HAVE | | OBSCURED TEXTURED GLASS. | | 4. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS, | | SIGNS, PARKING LOT, GENERATOR, MECHANICAL/AC/POOL | | EQUIPMENT, DUMPSTER ENCLOSURE, IRRIGATION, LANDSCAPE, | | OTHER _____________ | | 5. THE ACCESSORY STRUCTURE AND THE ADDITION TO THE MAIN | | HOUSE SHALL FEATURE A SLIGHTLY LESS TEXTURED STUCCO | | FINISH THAN THE EXISTING STUCCO FINISH ON THE MAIN | | HOUSE TO DIFFERENTIATE IT FROM THE ORIGINAL STUCCO | | FINISH. | | 6. A SCORE LINE OF APPROXIMATELY 3/4 OF AN INCH SHALL | | BE ADDED ON THE MAIN HOUSE TO DIFFERENTIATE THE | | ADDITION FROM THE ORIGINAL PORTION OF THE HOUSE. | | | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2020-09-14 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-09-14 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-09-14 |
Time |
16:36 |
Sent To |
|
|
Notes |
2020-09-14 16:36:25 | THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | CONDITION(S): | | | | 1. ALL EXTERIOR DOOR AND WINDOW FRAMES SHALL HAVE WHITE | | OR BRONZE FINISH. | | 2. ALL MUNTINS SHALL HAVE AN EXTERNAL DIMENSIONAL | | PROFILE. FOR PGT PRODUCTS THIS IS A RAISED PYRAMID. FOR | | OTHER PRODUCTS, THE PRODUCT MUST HAVE AN OGEE OR A | | PYRAMID. | | 3. ALL GLASS SHALL BE CLEAR GLASS OR CLEAR GLASS WITH | | LOW-E COATING. A NON-STREET FACING BATHROOM MAY HAVE | | OBSCURED TEXTURED GLASS. | | 4. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS, | | SIGNS, PARKING LOT, GENERATOR, MECHANICAL/AC/POOL | | EQUIPMENT, DUMPSTER ENCLOSURE, IRRIGATION, LANDSCAPE, | | OTHER _____________ | | 5. THE ACCESSORY STRUCTURE AND THE ADDITION TO THE MAIN | | HOUSE SHALL FEATURE A SLIGHTLY LESS TEXTURED STUCCO | | FINISH THAN THE EXISTING STUCCO FINISH ON THE MAIN | | HOUSE TO DIFFERENTIATE IT FROM THE ORIGINAL STUCCO | | FINISH. | | 6. A SCORE LINE OF APPROXIMATELY 3/4 OF AN INCH SHALL | | BE ADDED ON THE MAIN HOUSE TO DIFFERENTIATE THE | | ADDITION FROM THE ORIGINAL PORTION OF THE HOUSE. | | 7. THE REAR ACCESSORY STRUCTURE SHALL HAVE A 6-FOOT ? | | 5-INCH SETBACK INSTEAD OF THE 9-FOOT SETBACK INDICATED | | IN THE PROJECT DATA TABLE. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2020-11-24 |
|
|
Cont ID |
|
Sent By |
ccarvaja |
Date |
2020-11-24 |
Time |
14:34 |
Rev Time |
0.00 |
Received By |
ccarvaja |
Date |
2020-11-19 |
Time |
11:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2020-11-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-11-12 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-10-26 |
Time |
12:57 |
Sent To |
|
|
Notes |
2020-10-26 12:57:34 | ROUTED TO BUILDING DIV AUDIT | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-10-26 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2020-10-26 |
Time |
12:10 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2020-10-21 |
Time |
08:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-10-01 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-10-01 |
Time |
07:59 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-09-23 |
Time |
16:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-09-23 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-09-23 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-09-11 |
Time |
15:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
P |
Date |
2020-09-24 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-09-24 |
Time |
09:33 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-09-11 |
Time |
15:48 |
Sent To |
|
|
Notes |
2020-09-24 09:33:40 | RECEIPT MU 2020-37211 - NO FEES DUE | 2020-09-11 15:48:11 | 9/11/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2020-09-24 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-09-24 |
Time |
11:47 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-09-24 |
Time |
11:47 |
Sent To |
|
|
Notes |
2020-09-24 11:54:48 | APPROVED WITH PROVISO: | | | | AHU IN ATTIC MUST MEET FBC EC R403.3.6 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2020-09-24 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-09-24 |
Time |
09:10 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-09-24 |
Time |
08:08 |
Sent To |
|
|
Notes |
2020-09-24 09:13:05 | NO PLUMBING WORK TO BE DONE ON STUCTURE 315 DYER RD, | | 317 DYER RD HAS PLUMBING AND GAS PERMIT 20080654 . |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
4 |
Status |
N |
Date |
2022-11-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-11-17 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-11-17 |
Time |
15:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
3 |
Status |
P |
Date |
2020-11-24 |
|
|
Cont ID |
|
Sent By |
rgathrig |
Date |
2020-11-24 |
Time |
13:24 |
Rev Time |
0.00 |
Received By |
rgathrig |
Date |
2020-11-24 |
Time |
13:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
2 |
Status |
F |
Date |
2020-11-12 |
|
|
Cont ID |
|
Sent By |
rgathrig |
Date |
2020-11-12 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
rgathrig |
Date |
2020-11-12 |
Time |
13:28 |
Sent To |
|
|
Notes |
2020-11-12 13:35:44 | PRIVATE PROVIDER REVIEW NOT APPROVED | | | | NEED TO SATISFY THE BUILDING REVIEW AND PROVIDE UPDATED | | AFFIDAVIT FOR REVISIONS REQUIRED PER THE BUILDING | | REVIEWER | | | | RICHARD GATHRIGHT | | 561 805 6679 |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
1 |
Status |
F |
Date |
2020-10-01 |
|
|
Cont ID |
|
Sent By |
rgathrig |
Date |
2020-10-01 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
rgathrig |
Date |
2020-10-01 |
Time |
13:57 |
Sent To |
|
|
Notes |
2020-10-01 13:58:02 | PRIVATE PROVIDER REVIEW FOR PERMITS 20080654 AND | | 20080620 IS DENIED. | | FS 553.791 | | PAPERWORK FOR PRIVATE PROVIDER, INSURANCE AND | | INSPECTORS IS OK. | | NEW PLAN REVIEW AFFIDAVITS WILL BE REQUIRED TO ADDRESS | | ALL THE PERMIT DOCUMENTS WHEN THE NEW PLANS AND | | DOCUMENTS ARE SUBMITTED TO ADDRESS THE PLAN REVIEW | | COMMENTS. | | WHEN THE NEW AFFIDAVITS ARE SUBMITTED, THE AFFIDAVITS | | MUST IDENTIFY THE PLANS AND DOCUMENTS REVIEWED. NAME OF | | DOCUMENT, DATE OF DOCUMENT, DESIGNER OF DOCUMENT, PAGE | | NUMBER OF DOCUMENTS, ETC. IS REQUIRED TO BE LISTED ON | | THE PLAN REVIEW COMPLIANCE AFFIDAVIT. | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT THE REVIEWER | | RICHARD GATHRIGHT | | [email protected] | | 561-805-6679 | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2020-11-12 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-11-12 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-11-12 |
Time |
10:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2020-09-30 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-09-30 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-09-30 |
Time |
13:26 |
Sent To |
|
|
Notes |
2020-09-30 13:27:15 | SEE BUILDING PLAN REVIEW |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2020-11-12 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-11-12 |
Time |
10:52 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-11-12 |
Time |
10:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2020-09-30 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-09-30 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-09-30 |
Time |
13:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2020-10-26 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-10-26 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-10-26 |
Time |
11:40 |
Sent To |
|
|
Notes |
2020-10-26 11:51:39 | THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | CONDITION(S): | | | | 1. ALL EXTERIOR DOOR AND WINDOW FRAMES SHALL HAVE WHITE | | OR BRONZE FINISH. | | 2. ALL MUNTINS SHALL HAVE AN EXTERNAL DIMENSIONAL | | PROFILE. FOR PGT PRODUCTS THIS IS A RAISED PYRAMID. FOR | | OTHER PRODUCTS, THE PRODUCT MUST HAVE AN OGEE OR A | | PYRAMID. | | 3. ALL GLASS SHALL BE CLEAR GLASS OR CLEAR GLASS WITH | | LOW-E COATING. A NON-STREET FACING BATHROOM MAY HAVE | | OBSCURED TEXTURED GLASS. | | 4. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS, | | SIGNS, PARKING LOT, GENERATOR, MECHANICAL/AC/POOL | | EQUIPMENT, DUMPSTER ENCLOSURE, IRRIGATION, LANDSCAPE, | | OTHER _____________ | | 5. THE ACCESSORY STRUCTURE AND THE ADDITION TO THE MAIN | | HOUSE SHALL FEATURE A SLIGHTLY LESS TEXTURED STUCCO | | FINISH THAN THE EXISTING STUCCO FINISH ON THE MAIN | | HOUSE TO DIFFERENTIATE IT FROM THE ORIGINAL STUCCO | | FINISH. | | 6. A SCORE LINE OF APPROXIMATELY 3/4 OF AN INCH SHALL | | BE ADDED ON THE MAIN HOUSE TO DIFFERENTIATE THE | | ADDITION FROM THE ORIGINAL PORTION OF THE HOUSE. | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2020-09-14 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-09-14 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-09-14 |
Time |
16:36 |
Sent To |
|
|
Notes |
2020-09-14 16:36:34 | THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | CONDITION(S): | | | | 1. ALL EXTERIOR DOOR AND WINDOW FRAMES SHALL HAVE WHITE | | OR BRONZE FINISH. | | 2. ALL MUNTINS SHALL HAVE AN EXTERNAL DIMENSIONAL | | PROFILE. FOR PGT PRODUCTS THIS IS A RAISED PYRAMID. FOR | | OTHER PRODUCTS, THE PRODUCT MUST HAVE AN OGEE OR A | | PYRAMID. | | 3. ALL GLASS SHALL BE CLEAR GLASS OR CLEAR GLASS WITH | | LOW-E COATING. A NON-STREET FACING BATHROOM MAY HAVE | | OBSCURED TEXTURED GLASS. | | 4. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS, | | SIGNS, PARKING LOT, GENERATOR, MECHANICAL/AC/POOL | | EQUIPMENT, DUMPSTER ENCLOSURE, IRRIGATION, LANDSCAPE, | | OTHER _____________ | | 5. THE ACCESSORY STRUCTURE AND THE ADDITION TO THE MAIN | | HOUSE SHALL FEATURE A SLIGHTLY LESS TEXTURED STUCCO | | FINISH THAN THE EXISTING STUCCO FINISH ON THE MAIN | | HOUSE TO DIFFERENTIATE IT FROM THE ORIGINAL STUCCO | | FINISH. | | 6. A SCORE LINE OF APPROXIMATELY 3/4 OF AN INCH SHALL | | BE ADDED ON THE MAIN HOUSE TO DIFFERENTIATE THE | | ADDITION FROM THE ORIGINAL PORTION OF THE HOUSE. | | 7. THE REAR ACCESSORY STRUCTURE SHALL HAVE A 6-FOOT ? | | 5-INCH SETBACK INSTEAD OF THE 9-FOOT SETBACK INDICATED | | IN THE PROJECT DATA TABLE. | | |
|
|