Plan Review Details - Permit 20080557
Plan Review Stops For Permit 20080557
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-17 Cont ID  
Sent By jgomez Date 2020-08-17 Time 14:08 Rev Time 0.00
Received By jgomez Date 2020-08-17 Time 14:04 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-13 Cont ID  
Sent By jgomez Date 2020-08-13 Time 09:55 Rev Time 0.00
Received By jgomez Date 2020-08-13 Time 09:50 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-12 Cont ID  
Sent By jgomez Date 2020-08-12 Time 10:59 Rev Time 0.00
Received By jgomez Date 2020-08-12 Time 10:49 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-08-17 Cont ID  
Sent By jgomez Date 2020-08-17 Time 14:04 Rev Time 0.00
Received By jgomez Date 2020-08-17 Time 14:04 Sent To  
Notes
2020-08-17 14:05:3808/17/2020 TALKED TO ROBERT DESPREZ (A/C CONTRACTOR)TO
 CLARIFY RETURN AIR DUCT. A/C REVISON SENT TO EMAIL
 PERMITS FOR PROCESSING. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-08-13 Cont ID  
Sent By jgomez Date 2020-08-13 Time 09:55 Rev Time 0.00
Received By jgomez Date 2020-08-13 Time 09:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-08-12 Cont ID  
Sent By jgomez Date 2020-08-12 Time 10:50 Rev Time 0.00
Received By jgomez Date 2020-08-12 Time 10:50 Sent To  
Notes
2020-08-12 10:59:54RESIDENTIAL (R3) MECHANICAL REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLOOR PLAN SHOWS AN 8" RETURN AIR DUCT. THE RETURN
 AIR DUCT SIZE SHOWN ON THE FLOOR PLAN NEEDS TO BE AT
 LEAST 10" AS REQUIRED BY SEC. M1602.3 EXCEPTION #1.
 REVISE AS REQUIRED.
  
 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 3- THE MECHANICAL WORK WAS NOT INCLUDED IN THE MASTER.
 PLEASE COMPLETE THE ATTACHED REVISION FORM AND INCLUDE
 THE ADDITIONAL VALUE FOR THE MECHANICAL WORK. REVISION
 FEES WILL BE ADJUSTED ACCORDINGLY. SEC. 109.3 CITY
 AMENDMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,