2020-09-18 15:00:48 | PLAN REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) UNDER DESIGN PARAMETERS ON SHEET T1, THE NOTE STATES |
| THIS IS A TWO STORY DWELLING. THE PLANS ARE FOR A |
| SINGLE STORY DWELLING. PLEASE CORRECT. CITY AMENDMENTS |
| FBC 107.2.1 |
| |
| 2) THE WALL SECTION ON SHEET D1 SPECIFIES A 6:12 SLOPE |
| ROOF. THE ROOF PLAN ON A4 AND THE ELEVATIONS ON A3 |
| SPECIFY A 5:12 SLOPE ROOF. PLEASE COORDINATE. CITY |
| AMENDMENTS FBC 107.2.1 |
| |
| 3) THE SHOWER DETAIL ON D1 IS FOR A SHOWER WITH A CURB |
| AND THE PLANS ON A2 SHOW A RECESSED SLAB SHOWER. PLEASE |
| COORDINATE. CITY AMENDMENTS FBC 107.2.1 |
| |
| 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL |
| MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE |
| DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE |
| SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT |
| BEFORE THEY CAN BE INSTALLED. ONLY ONE SET IS REQUIRED |
| TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS. |
| |
| 5) FBC ENERGY CONSERVATION R101.5 COMPLIANCE. |
| RESIDENTIAL BUILDINGS SHALL MEET THE PROVISIONS OF |
| FLORIDA BUILDING CODE, ENERGY CONSERVATION RESIDENTIAL |
| PROVISIONS. SUBMIT PERMIT DOCUMENTS AND FORMS TO SHOW |
| THAT THE PROPOSED RESIDENTIAL STRUCTURE COMPLIES WITH |
| THE ENERGY CODE. FBC ENERGY CONSERVATION |
| |
| 6) ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO |
| HAVE THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO |
| HAVE THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER |
| VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE |
| BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER |
| DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE |
| ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS |
| REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER |
| FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 & |
| 61G15 |
| |
| 7) BASED ON THE LATEST ICC VALUATION TABLES, THIS |
| PROJECT HAS A VALUATION OF $112,785.00. I HAVE ADJUSTED |
| THE STATED VALUATION FOR THIS PROJECT ACCORDINGLY. FBC |
| 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. |