Plan Review Details - Permit 20080541
Plan Review Stops For Permit 20080541
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-03 Cont ID  
Sent By cthroop Date 2020-09-03 Time 15:15 Rev Time 0.00
Received By cthroop Date 2020-09-03 Time 14:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-26 Cont ID  
Sent By cthroop Date 2020-08-26 Time 10:15 Rev Time 0.00
Received By cthroop Date 2020-08-26 Time 09:49 Sent To  
Notes
2020-08-26 10:17:18PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A STRUCTURAL REPAIR DETAIL FOR SLAB CUTS IN
 KITCHEN, M-BATH AND GUEST BATH.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-03 Cont ID  
Sent By cthroop Date 2020-09-03 Time 15:16 Rev Time 0.00
Received By cthroop Date 2020-09-03 Time 14:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-26 Cont ID  
Sent By cthroop Date 2020-08-26 Time 10:18 Rev Time 0.00
Received By cthroop Date 2020-08-26 Time 09:49 Sent To  
Notes
2020-08-26 10:19:58PLAN REVIEW - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ELECTRICAL DEVICES ARE MISSING IN GUEST BATH. SHOW
 LOCATION AND TYPE ON FLOOR PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-08-21 Cont ID  
Sent By ccole Date 2020-08-21 Time 16:24 Rev Time 0.00
Received By ccole Date 2020-08-21 Time 16:24 Sent To  
Notes
2020-08-21 16:25:40A SEPARATE PERMIT IS REQUIRED FOR THE GAS PIPING
 INSTALLTION TO THE NEW RANGE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-03 Cont ID  
Sent By cthroop Date 2020-09-03 Time 15:16 Rev Time 0.00
Received By cthroop Date 2020-08-31 Time 09:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-26 Cont ID  
Sent By cthroop Date 2020-08-26 Time 10:20 Rev Time 0.00
Received By cthroop Date 2020-08-17 Time 08:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-09-01 Cont ID  
Sent By medwards Date 2020-09-01 Time 13:10 Rev Time 0.00
Received By medwards Date 2020-09-01 Time 13:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-08-25 Cont ID  
Sent By medwards Date 2020-08-25 Time 11:36 Rev Time 0.00
Received By medwards Date 2020-08-25 Time 11:11 Sent To  
Notes
2020-08-25 11:39:57NEW KITCHEN FLOOR PLAN INDICATES A NEW HOOD ABOVE THE
 GAS RANGE. PLEASE PROVIDE MORE DETAILS ABOUT THE RANGE
 AND HOOD. IS THE HOOD VENTED TO THE OUTDOORS? IF SO,
 DOES THE RANGE REQUIRE A CERTAIN AMOUNT OF EXHAUST?
 PROVIDE THE SPEC SHEETS FOR THE NEW RANGE AND NEW HOOD.
 IF THE HOOD IS VENTED TO THE OUTDOORS A MECHANICAL SUB
 PERMIT WILL BE REQUIRED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-09-01 Cont ID  
Sent By abelisle Date 2020-09-01 Time 09:53 Rev Time 0.00
Received By abelisle Date 2020-09-01 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-21 Cont ID  
Sent By ccole Date 2020-08-21 Time 15:33 Rev Time 0.00
Received By ccole Date 2020-08-21 Time 14:13 Sent To  
Notes
2020-08-21 15:34:491ST REVIEW FBC-2017 RES.
 PERMIT-20080541
 8/21/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE PLUMBING RISER DRAWINGS FOR THE ALTERATIONS
 LISTED BELOW AS REQUIRED BY SECTION 107.3.5.3 WPB
 AMENDMENTS TO THE FBC-17:
 A) RELOCATED SINK AND DISHWASHER IN THE KITCHEN.
 B) REPLACED SHOWER AND NEW AND RELOCATED LAVATORIES IN
 THE MASTER BATH.
  
 2) CONCERNING THE RELOCATED SHOWER DRAIN IN THE MASTER
 BATH AND THE NEW SHOWER DRAIN IN THE GUEST BATH PLEASE
 NOTE THAT THE HORIZONTAL DISTANCE FROM THE CENTERLINE
 OF THE NEW SHOWER DRAIN OUTLET TO THE CENTERLINE OF THE
 INLET OF THE EXISTING TRAP SHALL NOT EXCEED 30? ?
 SECTION P3201.6 FBC RES.
  
 3) PROVIDE A SHOWER PLAN DETAIL PER SECTION P2709.1 &
 P2709.2.
  
 4) PLEASE NOTE THAT THE A BACKFLOW PREVENTER IS
 REQUIRED FOR THE SUPPLY LINE TO THE ICE MAKER- P2902.1,
 AND WATER HAMMER ARRESTORS ARE REQUIRED FOR THE SUPPLY
 LINES TO THE ICE MAKER AND THE DISHWASHER- SECTION
 P2903.5.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-03 Cont ID  
Sent By cthroop Date 2020-09-03 Time 15:16 Rev Time 0.00
Received By cthroop Date 2020-09-03 Time 14:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-25 Cont ID  
Sent By medwards Date 2020-08-25 Time 11:40 Rev Time 0.00
Received By medwards Date 2020-08-25 Time 11:40 Sent To  
Notes
***NONE***