Plan Review Details - Permit 20080463
Plan Review Stops For Permit 20080463
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-21 Cont ID  
Sent By rmcdouga Date 2020-09-21 Time 08:50 Rev Time 0.00
Received By rmcdouga Date 2020-09-21 Time 08:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-09-09 Cont ID  
Sent By rmcdouga Date 2020-09-09 Time 15:32 Rev Time 0.00
Received By rmcdouga Date 2020-09-09 Time 15:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-23 Cont ID  
Sent By fgiaquin Date 2020-09-23 Time 20:35 Rev Time 0.00
Received By fgiaquin Date 2020-09-23 Time 19:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-31 Cont ID  
Sent By fgiaquin Date 2020-08-31 Time 21:43 Rev Time 0.00
Received By fgiaquin Date 2020-08-27 Time 21:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-28 Cont ID  
Sent By jgomez Date 2020-09-28 Time 14:11 Rev Time 0.00
Received By jgomez Date 2020-09-14 Time 09:33 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-09 Cont ID  
Sent By rmcdouga Date 2020-09-09 Time 15:33 Rev Time 0.00
Received By rmcdouga Date 2020-08-11 Time 07:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-09-16 Cont ID  
Sent By lcrespo Date 2020-09-16 Time 10:33 Rev Time 0.00
Received By lcrespo Date 2020-09-16 Time 10:29 Sent To  
Notes
2020-09-16 10:34:2209/16/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-12 Cont ID  
Sent By lcrespo Date 2020-08-12 Time 16:55 Rev Time 0.00
Received By lcrespo Date 2020-08-12 Time 16:55 Sent To  
Notes
2020-08-12 17:08:3308/12/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR
 THE MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP
 FROM ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. IT
 REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE DOES NOT
 EXCEED THE LISTED MAXIMUM FLOW RATE OF THE SUCTION
 OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 2. SUBMIT LEGIBLE COPIES OF THE POOL PUMP CURVE.
 INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS.
 4.4.9, 4.4.9.1.
  
 3. SUBMIT SPECIFICATIONS FOR THE PUMP AND CARTRIDGE
 FILTER PER THE WPB AMEND. TO FBC SEC. 107.2.1.
  
 4. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-28 Cont ID  
Sent By jgomez Date 2020-09-28 Time 14:10 Rev Time 0.00
Received By jgomez Date 2020-09-28 Time 13:58 Sent To  
Notes
2020-09-28 14:11:03POOL DRAWINGS AND CALCULATIONS WITH ENGINEER'S ORIGINAL
 SEAL/SIGNATURE MATCH APPROVED ONES. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-09-21 Cont ID  
Sent By rmcdouga Date 2020-09-21 Time 08:51 Rev Time 0.00
Received By rmcdouga Date 2020-09-21 Time 08:51 Sent To  
Notes
2020-09-21 08:54:32THE FIRST SHEET OF DRAWINGS STATES THAT IT IS DIGITALLY
 SIGNED. I WAS NOT ABLE TO VERIFY THE DIGITAL SIGNATURE.
 ALSO THE HANDWRITTEN SIGNATURE OF THE ENGINEER SHOULD
 NOT BE ON A DIGITALLY SIGNED DOCUMENT. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-09 Cont ID  
Sent By rmcdouga Date 2020-09-09 Time 15:32 Rev Time 0.00
Received By rmcdouga Date 2020-09-09 Time 15:32 Sent To  
Notes
2020-09-09 15:49:41ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-08-28 Cont ID  
Sent By kalexand Date 2020-08-28 Time 16:45 Rev Time 0.00
Received By kalexand Date 2020-08-28 Time 16:45 Sent To I
Notes
***NONE***