Plan Review Details - Permit 20080399
Plan Review Stops For Permit 20080399
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-10 Cont ID  
Sent By jgomez Date 2020-11-10 Time 17:20 Rev Time 0.00
Received By jgomez Date 2020-11-10 Time 17:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By jgomez Date 2020-09-23 Time 13:12 Rev Time 0.00
Received By jgomez Date 2020-09-22 Time 17:41 Sent To  
Notes
2020-09-23 13:14:48BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- PLANS SUBMITTED ARE SIGNED BY A LICENSED ENGINEER.
 BASED ON THE SCOPE OF WORK SHOWN ON PLANS, IT LOOKS
 LIKE THE SCOPE OF WORK FALLS UNDER THE SCOPE OF
 ARCHITECTURE NO ENGINEERING. THE ARCHITECTURAL SCOPE OF
 WORK SHOWN IS NOT INCIDENTAL TO ENGINEERING. PLANS
 SHOWING THE PROPOSED USE OF THE SPACE NEEDS TO BE DONE
 BY A LICENSED ARCHITECT. CHAPTER 481 FLORIDA STATUES
 AND 61G1 FLORIDA ADMINISTRATIVE CODE.
 (NOTE: SEE DEFINITIONS BELOW FOR ARCHITECTURE AND
 ENGINEERING DEFINITIONS).
  
 2- PROVIDE COMPLETE LIFESAFETY PLAN SHOWING COMPLIANCE
 WITH THE EGRESS REQUIREMENTS. PROVIDE THE OCCUPANT LOAD
 AND EGRESS CAPABILITIES. SEC. 107.3.5.1 CITY
 AMENDMENTS.
  
 3- TYPE OF CONSTRUCTION IS INCORRECT. THIS BUILDING IS
 NOT TYPE 5B CONSTRUCTION. REVISE AS REQUIRED. SEC.
 602.1 FBC-BUILDING.
  
 4- PROVIDE COMPLETE INFORMATION FOR THE EGRESS DOORS.
 SEC. 1010.1 FBC-BUILDING
 FIRE RATING, SWING IN THE DIRECTION OF TRAVEL,
 HARDWARE, LOCKING MECHANISM, ETC.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 ARCHITECTURE:
 481.203. DEFINITIONS. AS USED IN THIS PART:
 (6) ARCHITECTURE MEANS THE RENDERING OR OFFERING TO
 RENDER SERVICES IN CONNECTION WITH THE DESIGN AND
 CONSTRUCTION OF A STRUCTURE OR GROUP OF STRUCTURES
 WHICH HAVE AS THEIR PRINCIPAL PURPOSE HUMAN HABITATION
 OR USE, AND THE UTILIZATION OF SPACE WITHIN AND
 SURROUNDING SUCH STRUCTURES. THESE SERVICES INCLUDE
 PLANNING, PROVIDING PRELIMINARY STUDY DESIGNS, DRAWINGS
 AND SPECIFICATIONS, JOB-SITE INSPECTION, AND
 ADMINISTRATION OF CONSTRUCTION CONTRACTS.
  
 ENGINEERING
 471.005. DEFINITIONS. AS USED IN THIS CHAPTER, THE
 TERM:
 (7)ENGINEERING? INCLUDES THE TERM PROFESSIONAL
 ENGINEERING AND MEANS ANY SERVICE OR CREATIVE WORK, THE
 ADEQUATE PERFORMANCE OF WHICH REQUIRES ENGINEERING
 EDUCATION, TRAINING, AND EXPERIENCE IN THE APPLICATION
 OF SPECIAL KNOWLEDGE OF THE MATHEMATICAL, PHYSICAL, AND
 ENGINEERING SCIENCES TO SUCH SERVICES OR CREATIVE WORK
 AS CONSULTATION, INVESTIGATION, EVALUATION, PLANNING,
 AND DESIGN OF ENGINEERING WORKS AND SYSTEMS, PLANNING
 THE USE OF LAND AND WATER, TEACHING OF THE PRINCIPLES
 AND METHODS OF ENGINEERING DESIGN, ENGINEERING SURVEYS,
 AND THE INSPECTION OF CONSTRUCTION FOR THE PURPOSE OF
 DETERMINING IN GENERAL IF THE WORK IS PROCEEDING IN
 COMPLIANCE WITH DRAWINGS AND SPECIFICATIONS, ANY OF
 WHICH EMBRACES SUCH SERVICES OR WORK, EITHER PUBLIC OR
 PRIVATE, IN CONNECTION WITH ANY UTILITIES, STRUCTURES,
 BUILDINGS, MACHINES, EQUIPMENT, PROCESSES, WORK
 SYSTEMS, PROJECTS, AND INDUSTRIAL OR CONSUMER PRODUCTS
 OR EQUIPMENT OF A MECHANICAL, ELECTRICAL, HYDRAULIC,
 PNEUMATIC, OR THERMAL NATURE, INSOFAR AS THEY INVOLVE
 SAFEGUARDING LIFE, HEALTH, OR PROPERTY; AND INCLUDES
 SUCH OTHER PROFESSIONAL SERVICES AS MAY BE NECESSARY TO
 THE PLANNING, PROGRESS, AND COMPLETION OF ANY
 ENGINEERING SERVICES. A PERSON WHO PRACTICES ANY BRANCH
 OF ENGINEERING; WHO, BY VERBAL CLAIM, SIGN,
 ADVERTISEMENT, LETTERHEAD, OR CARD, OR IN ANY OTHER
 WAY, REPRESENTS HIMSELF OR HERSELF TO BE AN ENGINEER
 OR, THROUGH THE USE OF SOME OTHER TITLE, IMPLIES THAT
 HE OR SHE IS AN ENGINEER OR THAT HE OR SHE IS LICENSED
 UNDER THIS CHAPTER; OR WHO HOLDS HIMSELF OR HERSELF OUT
 AS ABLE TO PERFORM, OR DOES PERFORM, ANY ENGINEERING
 SERVICE OR WORK OR ANY OTHER SERVICE DESIGNATED BY THE
 PRACTITIONER WHICH IS RECOGNIZED AS ENGINEERING SHALL
 BE CONSTRUED TO PRACTICE OR OFFER TO PRACTICE
 ENGINEERING WITHIN THE MEANING AND INTENT OF THIS
 CHAPTER.
  
 ENGINEERS
 SEC. 471.003
  
 (3) NOTWITHSTANDING THE PROVISIONS OF THIS CHAPTER OR
 OF ANY OTHER LAW, NO LICENSED ENGINEER WHOSE PRINCIPAL
 PRACTICE IS CIVIL OR STRUCTURAL ENGINEERING, OR
 EMPLOYEE OR SUBORDINATE UNDER THE RESPONSIBLE
 SUPERVISION OR CONTROL OF THE ENGINEER, IS PRECLUDED
 FROM PERFORMING ARCHITECTURAL SERVICES WHICH ARE PURELY
 INCIDENTAL TO HER OR HIS ENGINEERING PRACTICE, NOR IS
 ANY LICENSED ARCHITECT, OR EMPLOYEE OR SUBORDINATE
 UNDER THE RESPONSIBLE SUPERVISION OR CONTROL OF THE
 ARCHITECT, PRECLUDED FROM PERFORMING ENGINEERING
 SERVICES WHICH ARE PURELY INCIDENTAL TO HER OR HIS
 ARCHITECTURAL PRACTICE. HOWEVER, NO ENGINEER SHALL
 PRACTICE ARCHITECTURE OR USE THE DESIGNATION
 ?ARCHITECT? OR ANY TERM DERIVED THEREFROM, AND NO
 ARCHITECT SHALL PRACTICE ENGINEERING OR USE THE
 DESIGNATION ?ENGINEER? OR ANY TERM DERIVED THEREFROM.
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2020-11-20 Cont ID  
Sent By equinone Date 2020-11-20 Time 08:40 Rev Time 0.00
Received By equinone Date 2020-11-20 Time 08:40 Sent To  
Notes
2020-11-20 08:41:27NO ELECTRICAL WORK BEING DONE. EQ

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-11-16 Cont ID  
Sent By equinone Date 2020-11-16 Time 11:44 Rev Time 0.00
Received By equinone Date 2020-11-16 Time 11:44 Sent To  
Notes
2020-11-16 11:47:01PREVIOUS COMMENTS:
  
 NO ELECTRIC SHOWN, PLEASE SUBMIT A PLAN SHOWING ANY
 ELECTRICAL WORK IF NONE PLEASE NOTE ON PLANS.
  
 NEW DRAWING (11/5/2020 - T1.0 COVER SHEET- OVERALL 1ST
 FLOOR PLAN) STATE THAT NO ELECTRICAL WORK IS BEING DONE
 UNDER THIS PERMIT. EQ

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-09-11 Cont ID  
Sent By jleahy Date 2020-09-11 Time 10:59 Rev Time 0.00
Received By jleahy Date 2020-09-11 Time 10:56 Sent To  
Notes
2020-09-11 11:01:27ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN, PLEASE SUBMIT A PLAN SHOWING ANY
 ELECTRICAL WORK IF NONE PLEASE NOTE ON PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-11-06 Cont ID  
Sent By pleduc Date 2020-11-06 Time   Rev Time 0.00
Received By pleduc Date 2020-11-06 Time 15:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-08-31 Cont ID  
Sent By pleduc Date 2020-08-31 Time   Rev Time 0.00
Received By pleduc Date 2020-08-31 Time 14:31 Sent To  
Notes
2020-08-31 14:53:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 01 & 02 - THERE ARE NO INDICATIONS THAT THESE
 NEW DOORS ARE IN A REQUIRED PATH OF EGRESS.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT
 ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR
 DIRECTIONAL EXIT SIGNS
 WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT
 OBVIOUS.
  
 PLEASE PROVIDE A LIFE SAFETY SHEET SHOWING THE REQUIRED
 EGRESS PATHS FROM THIS BUILDING/AREA, INCLUDING
 OCCUPANCY LOADS AND EXIT SIGNAGE.
  
  
  
 2) SHEET 01 & 02 - THERE ARE NO INDICATIONS OF REQUIRED
 EXIT SIGNS PER # 1 ABOVE.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT
 ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR
 DIRECTIONAL EXIT SIGNS
 WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT
 OBVIOUS.
  
 IF REQUIRED, PLEASE PROVIDE THE APPLICABLE EXIT
 SIGNAGE.
  
  
  
 3) SHEET 01 & 02 - THE DOORS ARE INDICATED AS SWINGING
 IN. BASED ON # 1 ABOVE, ARE THE DOORS REQUIRED TO SWING
 IN THE PATH OF TRAVEL.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS.
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE
 OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING
 IN THE
 DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR
 MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED
 BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH
 CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS
 THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS
 DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND CORRECT OR PROVIDE A DETAILED
 NARRATIVE WITH FIRE CODE REFERENCES.
  
  
 4) SHEET 01 & 02 - THERE IS NO INDICATION OF DOOR
 HARDWARE
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
  
 PLEASE PROVIDE DETAILS.
  
  
 5) INFORMATIONAL - A CARD READER IS NOTED. THE INSTALL
 OF ACCESS CONTROL SHALL BE UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
 ANY ACCESS CONTROL SHALL NOT RESTRICT EGRESS AND COMPLY
 WITH NFPA 101, CH 7, MEANS OF EGRESS WHERE APPLICABLE.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 6) INFORMATIONAL - ANY REMOVAL AND/OR CONSTRUCTION OF
 WALLS AND /OR CEILINGS REQUIRE AN EVALUATION OF THE
 FIRE ALARM AND/OR FIRE SPRINKLER SYSTEMS BY APPLICABLE
 LICENSED CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-20 Cont ID  
Sent By equinone Date 2020-11-20 Time 08:40 Rev Time 0.00
Received By equinone Date 2020-11-20 Time 08:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-19 Cont ID  
Sent By lmarchan Date 2020-11-19 Time 10:40 Rev Time 0.00
Received By lmarchan Date 2020-11-05 Time 08:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-23 Cont ID  
Sent By jgomez Date 2020-09-23 Time 13:19 Rev Time 0.00
Received By jgomez Date 2020-08-27 Time 09:05 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-10 Cont ID  
Sent By jgomez Date 2020-11-10 Time 17:21 Rev Time 0.00
Received By jgomez Date 2020-11-10 Time 17:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-23 Cont ID  
Sent By jgomez Date 2020-09-23 Time 13:17 Rev Time 0.00
Received By jgomez Date 2020-09-23 Time 13:17 Sent To  
Notes
2020-09-23 13:19:12THE PLANS NEED TO BE DONE BY ARCHITECT. SEE BUILDING
 REVIEW COMMENTS. JG.