Plan Review Details - Permit 20080249
Plan Review Stops For Permit 20080249
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-11 Cont ID  
Sent By pvalenti Date 2020-09-11 Time 10:25 Rev Time 0.00
Received By pvalenti Date 2020-09-11 Time 10:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-08-25 Cont ID  
Sent By jbrooks Date 2020-08-25 Time 10:36 Rev Time 0.00
Received By jbrooks Date 2020-08-25 Time 10:36 Sent To  
Notes
2020-08-25 10:37:27JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT SAMANTHA HILL (561) 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FOR FLORIDA STATE PRODUCT APPROVAL
 FL1850 IS INCOMPLETE, PROVIDE THE FOLLOWING ADDITIONAL
 INFORMATION: COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS
 WILL INCLUDE THE CODE VERSION, PRODUCT APPROVAL NUMBER,
 STATUS, GENERAL INFORMATION ABOUT THE PRODUCT)
 EVALUATION REPORT. PROVIDE TWO COMPLETE SETS FOR THE
 PROPOSED ACCORDION SHUTTERS USED. SECOND REQUEST.
 2. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN
 HEADING ?SHUTTER MOUNTING CONNECTION TYPE PER PRODUCT
 APPROVAL?; PROVIDE INFORMATION FROM SHEETS 6 & 7 OF
 FL1850 USE ALPHABETICAL LETTER THAT CORRESPONDS WITH
 THE CONNECTION TYPE FOR THE TOP AND BOTTOM CONNECTIONS.
 COLUMN HEADING ?ANCHOR SPACING? PROVIDE INFORMATION
 FROM SHEETS 12-16 FL1850. EXAMPLE SUBSTRATE CONCRETE
 BLOCK, MAXIMUM SPAN 7?-0? A.S.D DESIGN NEGATIVE
 PRESSURE RATING (PSF) 40 WALL HEADER C WALL SILL F
 USING TAPPER PLUS; ANCHOR SPACING IS 8? MAXIMUM. COLUMN
 HEADING SUBSTRATE: CONC. BLOCK, WOOD FRAME, POURED
 CONC. PROVIDE INFORMATION AS TO THE TYPE OF
 CONSTRUCTION OR ATTACHMENT SURFACE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-13 Cont ID  
Sent By jbrooks Date 2020-08-13 Time 11:29 Rev Time 0.00
Received By jbrooks Date 2020-08-13 Time 11:29 Sent To  
Notes
2020-08-13 11:29:56JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT SAMANTHA HILL (561) 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
  
 1. FBC R 301 FAC9N-3 FOR FLORIDA STATE PRODUCT APPROVAL
 FL1850 IS INCOMPLETE, PROVIDE THE FOLLOWING ADDITIONAL
 INFORMATION: COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS
 WILL INCLUDE THE CODE VERSION, PRODUCT APPROVAL NUMBER,
 STATUS, GENERAL INFORMATION ABOUT THE PRODUCT)
 EVALUATION REPORT. PROVIDE TWO COMPLETE SETS FOR THE
 PROPOSED ACCORDION SHUTTERS USED.
 2. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
 3. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON
 SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF
 USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON
 W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A ( .9
 FACTOR). REDUCE ANCHOR SPACING BY MUTIPLYING SPACING
 SHOWN ON SCHEDULE BY THE FACTOR.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-11 Cont ID  
Sent By pvalenti Date 2020-09-11 Time 10:25 Rev Time 0.00
Received By pvalenti Date 2020-09-03 Time 09:21 Sent To  
Notes
2020-09-03 09:21:31DIGITAL PERMIT
2020-09-01 07:41:10ROUTED TO BLDG. MISC 1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-25 Cont ID  
Sent By jbrooks Date 2020-08-25 Time 10:37 Rev Time 0.00
Received By jbrooks Date 2020-08-20 Time 15:24 Sent To  
Notes
2020-08-20 15:24:33ROUTED TO BLDG MISC. 1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-13 Cont ID  
Sent By jbrooks Date 2020-08-13 Time 11:30 Rev Time 0.00
Received By jbrooks Date 2020-08-11 Time 13:21 Sent To  
Notes
2020-08-11 13:21:27ROUTED TO MISC 1