Plan Review Details - Permit 20071441
Plan Review Stops For Permit 20071441
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-08-20 Cont ID  
Sent By jesmith Date 2020-08-20 Time 15:24 Rev Time 0.00
Received By jesmith Date 2020-08-20 Time 12:13 Sent To  
Notes
2020-08-20 15:24:5020071441 525 SUNSET RD
  
 GAS COMMENTS: APPROVED
  
 CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR
 MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL
 GAS INSPECTION. CALL 561-805-6692 FOR FURTHER
 INFORMATION.
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 PROVIDE PAPER BACKUP WITH PRINTED NAME "MARK GIMMLER"
 AS WELL AS SIGNATURE TO THE BUILDING DEPARTMENT.
  
 PROVISO:
 STRUCTURE IS BUILT IN 1925. PERMIT RECORDS ONLY GO BACK
 TO 2006 AND CONTAIN NO REFERENCE TO EXISTING GAS PIPE
 NOR IS THERE ANY RECORD OF THE IN HOME APPLIANCES SUCH
 AS THE RANGE, DRYER, TANKLESS WATER HEATER. FLORIDA
 PUBLIC UTILITIES RECORDS SHOW THAT THE GAS WAS TURNED
 ON IN 2006 AND THE METER WAS EXISTING AT THAT TIME.
 ADDITIONALLY IT IS NOT KNOWN WHETHER OR NOT THE
 EXISTING TANKLESS WATER HEATER REPLACED AN EXISTING GAS
 OR ELECTRIC WATER HEATER IN ANOTHER LOCATION. AT THE
 PLUMBING INSPECTOR'S DISCRETION, SHOW THAT ANY EXISTING
 GAS SYSTEM INFRASTRUCTURE AND PLUMBING WATER PIPE TO
 THE TANKLESS WATER HEATER, INCLUSIVE OF PIPING AND
 APPLIANCES, IS CODE COMPLIANT. THIS MAY REQUIRE
 PROVIDING DOCUMENTATION OF, OPENING OF WALLS AND
 FLOORS, PRESSURE TESTS, ETC., AS DETERMINED BY THE
 PLUMBING INSPECTOR. PLEASE CALL TIM LARGE AT
 561-805-6692 FOR ADDITIONAL INFORMATION AND/OR
 CLARIFICATION.
  
 THE MANUFACTURER?S SPECIFICATION/INSTALLATION MANUAL
 FOR POOL HEATER SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FBC FG 305.1.
  
 REGULATORS INSTALLED OUTDOORS SHALL BE INSTALLED IN A
 POSITION THAT PREVENTS MOISTURE (RAIN, SNOW) AND
 FOREIGN PARTICLES FROM ENTERING THE VENT AS REQUIRED BY
 THE MANUFACTURER?S START UP MANUAL TDC-0851-001
 REGULATOR: B-SERIES INSTALLATION
  
 FBC FG TABLES FOR 2PSI AND LOW PRESSURE GALVANIZED
 PIPING AS WELL AS THE SUBMITTED TABLE 402.4 (22) FOR
 2PSI PE PIPING SHALL BE ONSITE AT THE TIME OF
 INSPECTION
  
 PROVIDE TRACER WIRE FOR PE PIPING PER FBC FG 404.17.3.
 SIZE SHALL BE NOT LESS THAN 18 AWG AND THE INSULATION
 TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  
 PE PIPING SHALL NOT PASS UNDER BUILDING PER
 FBC.404.17.1.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20071441 525 SUNSET RD

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-08-10 Cont ID  
Sent By medwards Date 2020-08-10 Time 11:54 Rev Time 0.00
Received By medwards Date 2020-08-10 Time 10:50 Sent To  
Notes
2020-08-10 11:55:001ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20071441
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) APPLICATION GIVES AN ADDRESS OF 525 SUNSET RD, THE
 ISOMETRIC DRAWING GIVES AN ADDRESS OF 818 AVON RD.
 PLEASE GIVE THE CORRECT ADDRESS ON BOTH FORMS. FBC FS
 107.2.1
  
 2) PLEASE PROVIDE A DETAILED SCOPE OF WORK: APPLICATION
 STATES ?INSTALLING NATURAL GAS LINE TO CUSTOMER
 APPLIANCES? THE SUBMITTED PACKET SHOWS SPECS. FOR
 SEVERAL APPLIANCES BUT THE ISOMETRIC SHOWS A LINE FOR
 EXISTING APPLIANCES AND A NEW LINE ATTACHING AT METER
 AND RUNNING TO A NEW POOL HEATER. THIS IS CONFUSING, IS
 THIS A NEW GAS LINE FOR THE ENTIRE SYSTEM? IS THIS AN
 EXISTING GAS LINE THAT YOU ARE ATTACHING A NEW GAS LINE
 FOR THE POOL HEATER? IS THERE EXISTING GAS LINES AT
 THIS HOME AND YOU ARE CHANGING OUT ALL THE APPLIANCES
 FOR NEW ONES? PLEASE SHOW THE EXISTING GAS LINE WITH
 ALL APPLIANCES ATTACHED TO IT ALONG WITH THE TOTAL
 LONGEST LENGTH TO THE MOST REMOTE APPLIANCE FROM THE
 METER. FBC FS 107.2.1
  
 3) DESIGNER OF SYSTEM MUST PRINT AND SIGN HIS COMPLETE
 NAME, NOT JUST INITIALS, ON THE ISOMETRIC DRAWING. FBC
 FS 107.2.1
  
 4) IS THE EXISTING GAS PIPING SYSTEM A 2 PSI SYSTEM?
 FBC FS 107.2.1
  
 5) PLEASE PROVIDE THE SPECS FOR THE REGULATOR USED. FBC
 FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-11 Cont ID  
Sent By cthroop Date 2020-09-11 Time 09:47 Rev Time 0.00
Received By cthroop Date 2020-09-11 Time 09:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-20 Cont ID  
Sent By jesmith Date 2020-08-20 Time 15:28 Rev Time 0.00
Received By jesmith Date 2020-08-20 Time 15:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-12 Cont ID  
Sent By lcrespo Date 2020-08-12 Time 17:51 Rev Time 0.00
Received By lcrespo Date 2020-08-07 Time 16:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-08-20 Cont ID  
Sent By jesmith Date 2020-08-20 Time 12:14 Rev Time 0.00
Received By jesmith Date 2020-08-20 Time 12:13 Sent To  
Notes
2020-08-20 15:26:25STRUCTURE IS BUILT IN 1925. PERMIT RECORDS ONLY GO BACK
 TO 2006 AND CONTAIN NO REFERENCE TO EXISTING GAS PIPE
 NOR IS THERE ANY RECORD OF THE IN HOME APPLIANCES SUCH
 AS THE RANGE, DRYER, TANKLESS WATER HEATER. FLORIDA
 PUBLIC UTILITIES RECORDS SHOW THAT THE GAS WAS TURNED
 ON IN 2006 AND THE METER WAS EXISTING AT THAT TIME.
 ADDITIONALLY IT IS NOT KNOWN WHETHER OR NOT THE
 EXISTING TANKLESS WATER HEATER REPLACED AN EXISTING GAS
 OR ELECTRIC WATER HEATER IN ANOTHER LOCATION. AT THE
 PLUMBING INSPECTOR'S DISCRETION, SHOW THAT ANY EXISTING
 GAS SYSTEM INFRASTRUCTURE AND PLUMBING WATER PIPE TO
 THE TANKLESS WATER HEATER, INCLUSIVE OF PIPING AND
 APPLIANCES, IS CODE COMPLIANT. THIS MAY REQUIRE
 PROVIDING DOCUMENTATION OF, OPENING OF WALLS AND
 FLOORS, PRESSURE TESTS, ETC., AS DETERMINED BY THE
 PLUMBING INSPECTOR. PLEASE CALL TIM LARGE AT
 561-805-6692 FOR ADDITIONAL INFORMATION AND/OR
 CLARIFICATION.

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-08-12 Cont ID  
Sent By lcrespo Date 2020-08-12 Time 17:50 Rev Time 0.00
Received By lcrespo Date 2020-08-12 Time 17:50 Sent To  
Notes
2020-08-12 17:50:48PLUMBING FOR POOL UNDER PERMIT 19060571

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-11 Cont ID  
Sent By cthroop Date 2020-09-11 Time 09:46 Rev Time 0.00
Received By cthroop Date 2020-09-11 Time 09:46 Sent To  
Notes
2020-09-11 09:47:30GAS ISO WITH CONTRACTORS SIGNATURE VERIFIED BY AM. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-08-20 Cont ID  
Sent By jesmith Date 2020-08-20 Time 15:27 Rev Time 0.00
Received By jesmith Date 2020-08-20 Time 15:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-12 Cont ID  
Sent By lcrespo Date 2020-08-12 Time 17:51 Rev Time 0.00
Received By lcrespo Date 2020-08-12 Time 17:51 Sent To  
Notes
2020-08-10 11:57:00DESIGNER OF ISOMETRIC MUST PRINT AND SIGN THEIR NAME
 AND INCLUDE THE DATE. PROVIDE THE CORRECTED ADDRESS ON
 THE ISOMETRIC.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  