Plan Review Details - Permit 20071304
Plan Review Stops For Permit 20071304
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-24 Cont ID  
Sent By dbattles Date 2020-09-24 Time 10:57 Rev Time 0.00
Received By dbattles Date 2020-09-24 Time 10:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-14 Cont ID  
Sent By rmcdouga Date 2020-08-14 Time 13:30 Rev Time 0.00
Received By rmcdouga Date 2020-08-14 Time 08:20 Sent To  
Notes
2020-08-14 11:33:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 A- PROPOSED REVISIONS TO APPROVED PLANS
  
 1) REVISED SHEETS A111A&B, A121A&B, A181A&B HAVE THE
 MECHANICAL DUCTS AND OTHER MECHANICAL INFORMATION ON
 THEM. THESE ARE ARCHITECTURAL FLOOR PLANS. REVISED PLAN
 SHEETS REPLACE THE ORIGINALS, THEREFORE THESE SHEETS
 CAN NOT BE APPROVED BECAUSE REQUIRED FLOOR PLAN
 INFORMATION IS OBSCURED BY THE MECHANICAL ITEM OVERLAY.
 YOU WILL NEED TO REVISE THE APPROPRIATE MECAHNICAL
 DRAWINGS OR SUBMIT THESE PLANS AS NEW SHEETS WITH
 DIFFERENT SHEET NUMBERS AND MECHANICAL LABELS. CITY
 AMENDMENTS FBC 107.2.1.3
  
 2) THE PLANS DO NOT HAVE THE ENGINEER'S OR ARCHITECT'S
 DIGITAL SIGNATURE AS REQUIRED BY FS 471 AND 481. SEE
 THE SIGNATURE REVIEW STOP.
  
 SHOP DRAWINGS:
  
 B - STRUCTURAL STEEL CALCULATIONS
  
 1) THE ELECTRONICALLY SUBMITTED STEEL FRAMING
 CALCULATIONS ARE REQUIRED TO HAVE (DEWEY A. LEBANC
 P.E.) THE ENGINEER'S DIGITAL SIGNATURE. I WAS UNABLE TO
 VERIFY THE SIGNATURE. FS 471 & FAC 61G-15 SEE THE
 SIGNATURE REVIEW STOP.
  
 2) THE STEEL FRAMING CALCULATIONS ARE REQUIRED TO BE
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD
 (ARCHITECT/ENGINEER OR BOTH) IN RESPONSIBLE CHARGE.
 CITY AMENDMENTS FBC107.3.4.1
  
 3) PARTS OF THE STEEL FRAMING CALCULATIONS ARE NOT
 LEGIBLE. CITY AMENDMENTS FBC 107.2.1
  
 C - STEEL TRUSSES
  
 1) THE ELECTRONICALLY SUBMITTED STEEL TRUSS DRAWINGS
 ARE REQUIRED TO HAVE THE TRUSS ENGINEER'S DIGITAL
 SIGNATURE. FS 471 & FAC 61G-15 SEE THE SIGNATURE REVIEW
 STOP.
  
 2) THE STEEL TRUSS DRAWINGS ARE REQUIRED TO BE REVIEWED
 FOR CONFORMANCE WITH THE DESIGN OF THE BUILDING BY THE
 DESIGNER OF RECORD (ARCHITECT/ENGINEER OR BOTH) IN
 RESPONSIBLE CHARGE. CITY AMENDMENTS FBC107.3.4.1
  
 3) THE TRUSS PLACEMENT PLANS HAS AN ADDRESS OF 901 S
 FLAGLER. THE ADDRESS OF THIS PROJECT IS 351 PEMBROKE
 PLACE. CITY AMENDMENTS FBC 107.2.1.3
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-10 Cont ID  
Sent By jleahy Date 2020-08-10 Time 14:47 Rev Time 0.00
Received By jleahy Date 2020-08-10 Time 14:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-07-31 Cont ID  
Sent By pleduc Date 2020-07-31 Time   Rev Time 0.00
Received By pleduc Date 2020-07-30 Time 10:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2020-10-02 Cont ID  
Sent By lcrespo Date 2020-10-02 Time 18:21 Rev Time 0.00
Received By lcrespo Date 2020-10-02 Time 18:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-14 Cont ID  
Sent By rmcdouga Date 2020-08-14 Time 13:30 Rev Time 0.00
Received By rmcdouga Date 2020-07-28 Time 10:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-09-24 Cont ID  
Sent By hmoser Date 2020-09-24 Time 10:47 Rev Time 0.00
Received By hmoser Date 2020-09-24 Time 10:47 Sent To  
Notes
2020-10-05 08:57:29NO MECHANICAL REQUIRED FOR
 REVISION NUMBER FOUR HM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By medwards Date 2020-08-05 Time 07:37 Rev Time 0.00
Received By hmoser Date 2020-08-04 Time 13:36 Sent To  
Notes
2020-08-05 07:36:44PLAN DENIED
 COULD NOT FIND REVISION # 4 ON MECHANICAL ON PLAN.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-10-02 Cont ID  
Sent By lcrespo Date 2020-10-02 Time 18:08 Rev Time 0.00
Received By lcrespo Date 2020-10-02 Time 18:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-12 Cont ID  
Sent By tklarge Date 2020-08-10 Time 15:42 Rev Time 0.00
Received By lcrespo Date 2020-08-10 Time 15:42 Sent To  
Notes
2020-08-10 15:46:0408/10/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW NOT IN
 ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G10-11.010 SEALS AND 61G15-23.005.
  
 2. PLUMBING RISER DIAGRAM REQUIRED FOR AS BUILT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13)
 COMMERCIAL PLUMBING.
  
 3. GAS RISER DIAGRAM REQUIRED FOR AS BUILT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.5.1.5 (9) COMMERCIAL
 GAS.
  
 4. SUBMIT A NARRATIVE OF THE CHANGES MADE TO ALL PHASES
 OF PLUMBING AND GAS FOR AS BUILT PER THE WPB AMENDMENTS
 TO THE FBC WPB A 107.4.
  
 5. PROVIDE A SHUT OFF VALVE SCHEDULE ON WHERE THE RISER
 SHUT OFF VALVE TO EACH LOCATION WOULD BE AND TAG
 DESCRIBING IT USE PER THE 2017 FBC SEC. P 606.4.
  
 6. ON SHEET 027 PLEASE DELETE ALL LETTER CORRESPONDING
 TO EACH SECTIONAL CUT OF PIPE AS THIS CLUTTER THE
 DRAWING AND THE CLARITY IS OBSTRUCTED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1.4 QUALITY OF
 BUILDING PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-24 Cont ID  
Sent By dbattles Date 2020-09-24 Time 10:57 Rev Time 0.00
Received By dbattles Date 2020-09-24 Time 10:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-08-14 Cont ID  
Sent By rmcdouga Date 2020-08-14 Time 11:10 Rev Time 0.00
Received By rmcdouga Date 2020-08-14 Time 11:10 Sent To  
Notes
2020-08-14 11:12:07ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE PAPER DRAWINGS. NO PHOTOCOPY OR
 OTHER FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS
 471 & 61G15
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-08-03 Cont ID  
Sent By jroach Date 2020-08-03 Time 09:38 Rev Time 0.00
Received By jroach Date 2020-08-03 Time 09:38 Sent To  
Notes
2020-08-03 09:39:24ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.03.2020
 PERMIT NO.: 19020191 (REVISION 20071304)
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. ALL WORK WITHIN THE SOUTH DIXIE HIGHWAY RIGHT-OF-WAY
 SHALL BE SUBJECT TO THE REVIEW AND PERMITTING BY THE
 FLORIDA DEPARTMENT OF TRANSPORTATION (FDOT).
  
 2. THE DEVELOPER, ITS SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF ANY
 STREET TREES, TREE GRATES, AND RIGHT OF WAY LANDSCAPING
 AND IRRIGATION APPROVED WITH THIS PETITION. ALL PERMITS
 SHALL BE OBTAINED PRIOR TO COMMENCEMENT OF CONSTRUCTION
 OF SUCH IMPROVEMENTS.
  
 3. FINAL APPROVAL OF THE ENGINEERING DESIGN SHALL BE
 BASED UPON SUBMITTAL OF A SEPARATE PERMIT APPLICATION
 TO, AND REVIEW BY, THE CITY?S PUBLIC WORKS AND
 ENGINEERING DEPARTMENTS.
  
 4. ALL UTILITY ELEMENTS (I.E. BACKFLOW PREVENTERS,
 ETC.) SHALL BE SCREENED WITH LANDSCAPING TO THE MAXIMUM
 EXTENT ALLOWED BY THE CONTROLLING UTILITY AGENCY.
  
 5. THE DEVELOPER SHALL INSTALL AT ITS EXPENSE ALL
 RIGHT-OF-WAY UTILITY IMPROVEMENTS ASSOCIATED WITH THE
 PROPOSED DEVELOPMENT. APPLICABLE CAPACITY CHARGES,
 INSTALLATION CHARGES, DEPOSITS, AND OTHER NORMAL FEES
 CHARGED BY THE PUBLIC UTILITIES DEPARTMENT SHALL BE
 ASSESSED AT THE TIME OF REQUEST FOR PERMITS/REVIEW.
  
 6. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY:
  
  6.1. THE PROPERTY SHALL BE RE-PLATTED IN ACCORDANCE
 WITH ALL APPLICABLE STATUTES, REGULATIONS, AND THE
 CITY?S POLICIES AND PROCEDURES.
  
  6.2. MAINTENANCE AND SIDEWALK EASEMENTS (AS NECESSARY)
 SHALL BE DEDICATED BY PLAT OR ANOTHER LEGAL INSTRUMENT
 DETERMINED TO BE SUFFICIENT BY THE CITY.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved