Plan Review Details - Permit 20071234
Plan Review Stops For Permit 20071234
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-10-25 Cont ID  
Sent By jwitmer Date 2020-10-25 Time 13:29 Rev Time 0.00
Received By jwitmer Date 2020-10-25 Time 13:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-10-04 Cont ID  
Sent By jwitmer Date 2020-10-04 Time 11:39 Rev Time 0.00
Received By jwitmer Date 2020-10-04 Time 09:45 Sent To  
Notes
2020-10-04 11:39:48WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20071234
 ADD: 3950 GEORGIA AVE.
 CONT: BUILTMORE CONTRACTING
 TEL: 561-331-1476
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SUN. OCT. 04TH/2020
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST. THE DESIGNER OF RECORD HAS NOT
 INDICATED THIS IS A CHANGE OF OCCUPANCY AND WILL NEED
 TO SHOW AS SUCH ON THE PLANS. 2017 EXISTING BUILDING
 CODE METHOD OF PLAN DEVELOPMENT. 2017 EXISTING BUILD.
 CODE SECTION 301.1. THE REPAIRS, ALTERATIONS, CHANGE OF
 OCCUPANCY, ADDITIONS OR RELOCATION OF ALL EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS LISTED
 IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE
 DESIGNER OF RECORD. IN THE CITIES RECORDS THE LAST
 PREVIOUS TENANT WAS A PAINT AND BODY SHOP, F1
 OCCUPANCY.
  
 3) PLEASE REVIEW IN THE 2017 FL. EXISTING BUILDING CODE
 SECTION 1001.2.2. CHANGE IN OCCUPANCY CLASSIFICATION.
  
 4) SEMI-COMPLIED. SHEET A.1 DOES NOW SHOW AN ACCESSIBLE
 SEATING PLAN BUT FAILS TO SHOW AN ACCESSIBLE ROUTE TO
 THE BAR ON THE INTERIOR OF THE BUILDING. 2017
 FBC-ACCESSIBILITY CODE SECTION 206.2.4. SPACES AND
 ELEMENTS. AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT
 ACCESSIBLE BUILDINGS OR FACILITY ENTRANCES WITH ALL
 ACCESSIBLE SPACES AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
  
 2ND REQUEST. THE ON SHEET A-1 THERE IS A NOTE THAT
 STATES ACCESSIBLE SERVICE IS AT TABLES, THERE IS NO
 SEATING AT THE BAR COUNTER. PLEASE BE AWARE THIS
 STATEMENT DISCRIMINATES AGAINST THOSE PATROONS IN
 WHEELCHAIRS.
 2017 FL. ACCESSIBILITY CODE. 902.1 .DINING SURFACES
 SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1
 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT LIMITED
 TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS. PLEASE
 NOTE THAT THE REQUIREMENT 902.2 IS FOR A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCES
 COMPLYING WITH 306 SHALL BE PROVIDED. THIS HAS NOT
 OCCURRED NOR DOES THE CUT SECTION/ DETAIL SHOW KNEE TOE
 CLEARANCES NOR THE ACCESSIBLE BAR COUNTER TOP AT 34
 INCHES.
  
 THE OTHER ISSUE IS WHAT APPEARS TO BE THE POINT OF SALE
 IN THE COUNTERTOP IS THE SAME AREA TO BE USED WITH THE
 ACCESSIBLE SEATING AREA (ACCESSIBLE WHEELCHAIR)?
  
 4)(A) SHOW COMPLIANCE, 2ND REQUEST.902.2 CLEAR FLOOR OR
 GROUND SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305
 POSITIONED FOR A FORWARD APPROACH SHALL BE PROVIDED.
 KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 4)(B) SHOW THE ACCESSIBLE TABLE HEIGHTS.902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 5) 2ND REQUEST. PLEASE ALSO NOTE THE COUNTERTOP FOR THE
 REGISTER ALSO NEEDS TO BE COMPLIANT WITH CHECK WRITING
 SURFACES. 2017 ACCESS. CODE 904.3.3 CHECK WRITING
 SURFACES. WHERE PROVIDED, CHECK WRITING SURFACES SHALL
 COMPLY WITH 902.3. 902.3HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION.
 UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE
 SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL
 APPROACH TO AN ELEMENT.
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTERTOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 6A) 2ND REQUEST. THE SITE PLAN DOES NOT SHOW THE
 ACCESSIBLE RAMP FROM THE BUILDING SHOWING THE
 ACCESSIBLE ROUTE TO THE RESTROOMS.
 SHEET A-1 DOES NOT SHOW RESTROOM FACILITIES, PLEASE
 SHOW HOW COMPLIANCE WITH THE 2017 EXISTING BUILDING
 CODE SECTION 1010.6 SEPARATE FACILITIES WILL BE
 ACHIEVED. THIS CODE SECTION ALSO REFERS YOU BACK TO
 SECTION 810.2 EXISTING BUILDING CODE.
  
 6B) THE PLAN IS SILENT TO IF THERE ARE ANY MORE
 RESTROOMS FOR THE SITE AND COMPLIANCE WITH 2017 FBC-B
 TABLE 2902.1 MINIMUM NUMBER OF REQUIRED PLUMBING
 FIXTURES. PLEASE PROVIDE A TABLE FOR TOTAL OCCUPANT
 LOAD BROKE DOWN TO OCCUPANCY TYPE AND REQUIRED
 FIXTURES.
  
 7) THE VALUE OF WORK FOR THE PERMIT SEEMS LOW, AND WITH
 COMPLYING WITH THE COMMENTS THE VALUE OF THE PROJECT
 WILL INCREASE. PLEASE ALSO BE AWARE OF THE
 ACCESSIBILITY CODE REQUIREMENTS OF DISPROPORTIONATE
 COST.
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS LISTED FOR EACH
 ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN THE
 ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE COST
 OF THE 2017 ACCESSIBILITY CODE.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-19 Cont ID  
Sent By jwitmer Date 2020-08-19 Time 10:00 Rev Time 0.00
Received By jwitmer Date 2020-08-19 Time 08:30 Sent To  
Notes
2020-08-19 10:00:11WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20071234
 ADD: 3950 GEORGIA AVE.
 CONT: BUILTMORE CONTRACTING
 TEL: 561-331-1476
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 19TH/2020
 ACTION: DENIED
  
 1) THE TITLEBLOCK INDICATES THE PROPOSED WORK IS TO BE
 A BEER GARDEN. PLEASE NOTE THE OCCUPANTS AT 3950
 GEORGIA DIDN?T APPLY FOR THEIR BUSINESS TAX LICENSE
 (OLD OCCUPATIONAL TAX) AS A BEER GARDEN, BUT AS TROY?S
 BARBEQUE AS OF 08/05/2020? YOU MAY WANT TO CONTACT YOUR
 CLIENT TO SEE WHAT ADDITIONAL WORK WILL BE INVOLVED.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. IT WOULD
 APPEAR THAT WITH BARBEQUED MEET WHERE IS THE COOKER,
 INSIDE OR OUT? IS A HOOD AND ANSUL SYSTEM REQUIRED?
  
 2) THE DESIGNER OF RECORD HAS NOT INDICATED THIS IS A
 CHANGE OF OCCUPANCY AND WILL NEED TO SHOW AS SUCH ON
 THE PLANS. 2017 EXISTING BUILDING CODE METHOD OF PLAN
 DEVELOPMENT. 2017 EXISTING BUILD. CODE SECTION 301.1.
 THE REPAIRS, ALTERATIONS, CHANGE OF OCCUPANCY,
 ADDITIONS OR RELOCATION OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE DESIGNER OF
 RECORD. IN THE CITIES RECORDS THE LAST PREVIOUS TENANT
 WAS A PAINT AND BODY SHOP, F1 OCCUPANCY.
  
 3) PLEASE REVIEW IN THE 2017 FL. EXISTING BUILDING CODE
 SECTION 1001.2.2. CHANGE IN OCCUPANCY CLASSIFICATION.
  
 4) ON SHEET A-1 THERE IS A NOTE THAT STATES ACCESSIBLE
 SERVICE IS AT TABLES, THERE IS NO SEATING AT THE BAR
 COUNTER. PLEASE BE AWARE THIS STATEMENT DISCRIMINATES
 AGAINST THOSE PATROONS IN WHEELCHAIRS.
 2017 FL. ACCESSIBILITY CODE. 902.1 .DINING SURFACES
 SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1
 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT LIMITED
 TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 4)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) PLEASE ALSO NOTE THE COUNTER TOP FOR THE REGISTER
 ALSO NEEDS TO BE COMPLIANT WITH CHECK WRITING SURFACES.
 2017 ACCESS. CODE 904.3.3 CHECK WRITING SURFACES. WHERE
 PROVIDED, CHECK WRITING SURFACES SHALL COMPLY WITH
 902.3. 902.3HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION.
 UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE
 SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL
 APPROACH TO AN ELEMENT.
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 6) SHEET A-1 DOES NOT SHOW RESTROOM FACILITIES, PLEASE
 SHOW HOW COMPLIANCE WITH THE 2017 EXISTING BUILDING
 CODE SECTION 1010.6 SEPARATE FACILITIES WILL BE
 ACHIEVED. THIS CODE SECTION ALSO REFERS YOU BACK TO
 SECTION 810.2 EXISTING BUILDING CODE.
  
 7) THE VALUE OF WORK FOR THE PERMIT SEEMS LOW, AND WITH
 COMPLYING WITH THE COMMENTS THE VALUE OF THE PROJECT
 WILL INCREASE. PLEASE ALSO BE AWARE OF THE
 ACCESSIBILITY CODE REQUIREMENTS OF DISPROPORTIONATE
 COST.
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS LISTED FOR EACH
 ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN THE
 ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE COST
 OF THE 2017 ACCESSIBILITY CODE.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-10-28 Cont ID  
Sent By equinone Date 2020-10-28 Time 16:07 Rev Time 0.00
Received By equinone Date 2020-10-28 Time 16:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-13 Cont ID  
Sent By jleahy Date 2020-10-13 Time 14:01 Rev Time 0.00
Received By jleahy Date 2020-10-13 Time 14:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-14 Cont ID  
Sent By jleahy Date 2020-08-14 Time 17:56 Rev Time 0.00
Received By jleahy Date 2020-08-14 Time 17:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-10-23 Cont ID  
Sent By pleduc Date 2020-10-23 Time   Rev Time 0.00
Received By pleduc Date 2020-10-23 Time 10:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-10-06 Cont ID  
Sent By pleduc Date 2020-10-06 Time   Rev Time 0.00
Received By pleduc Date 2020-10-06 Time 13:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By pleduc Date 2020-07-28 Time   Rev Time 0.00
Received By pleduc Date 2020-07-28 Time 09:49 Sent To  
Notes
2020-07-28 10:31:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHET A 1.0 - THERE IS AN INDICATION OF BUSINESS
 OCCUPANCY. THIS APPEARS TO BE A CHANGE OF OCCUPANCY
 FROM THE PREVIOUS OCCUPANCY.
  
 PER NFPA 101, CH 6, THE OCCUPANCY IS ASSEMBLY AND SAHLL
 COMPLY WITH THE REQUIREMENTS OF NFPA 101, CH 12
  
 6.1.2.1* DEFINITION ? ASSEMBLY OCCUPANCY. AN OCCUPANCY
 (1) USED
 FOR A GATHERING OF 50 OR MORE PERSONS FOR DELIBERATION,
 WORSHIP,
 ENTERTAINMENT, EATING, DRINKING, AMUSEMENT, AWAITING
 TRANSPORTATION, OR
 SIMILAR USES; OR (2) USED AS A SPECIAL AMUSEMENT
 BUILDING, REGARDLESS OF
 OCCUPANT LOAD.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET A 1.0 - THERE ARE NO DIMENSIONS PROVIDED TO
 CONFIRM OCCUPANCY LOAD AND EGRESS REQUIREMENTS OR THAT
 ALL THE INDICATED TABLES AND CHAIRS CAN FIT INTO THE
 SPACE AS PROPOSED.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE.
  
  
 2 A ) SHEET A 1.0 - THERE IS AN INDICATION OF A BAR
 AREA WITH A WOOD BAR TOP, HOWEVER, THERE ARE NO
 INDICATIONS OF BAR STOOLS.
  
 PLEASE CONFIRM THAT BAR STOOLS WILL NOT BE PLACED AT
 THE BAR.
  
 IF PROPOSED, THEY SHALL BE INCLUDED IN THE FLOOR PLAN
 AND CONTAINED IN THE OCCUPANCY LOAD.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE.
  
  
  
 3) SHEET A 1.0 - THERE IS AN INDICATION OF WHAT APPEARS
 TO BE A RAMP WITH RAILINGS; HOWEVER, THERE ARE NO
 DETAILS TO CONFIRM COMPLIANCE WITH THE LIFE SAFETY
 CODE.
  
 RAMPS AND RAILING SHALL COMPLY WITH NFPA 101 CH 7 MEANS
 OF EGRESS.
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES,
 UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR
 7.2.2.4.1.6.
  
 7.5.5.3 NEW RAMPS SHALL BE IN ACCORDANCE WITH TABLE
 7.2.5.3(A),
 EXISTING RAMPS SHALL BE PERMITTED TO REMAIN IN USE OR
 BE
 REBUILT, PROVIDED THAT THEY MEET THE REQUIREMENTS SHOWN
 IN
 TABLE 7.2.5.3(B),
  
 PLEASE REVIEW, CORRECT, PROVIDE DETAILS AND ENSURE
 COMPLIANCE.
  
  
  
  
 4) SHEET A 1.0 - THERE IS AN INDICATION OF AN EXIT SIGN
 OVER AN EXTERIOR DOOR, HOWEVER, THERE IS NO DOOR
 SCHEDULE TO CONFIRM COMPLIANCE WITH THE EXIT DOOR
 HARDWARE, LOCKS OR LATCHES.
  
 PER NFPA 101 CH 7
  
 7.2 MEANS OF EGRESS COMPONENTS.
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO
 THE GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE
 SPECIAL
 REQUIREMENTS OF 7.2.1.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE.
  
  
  
  
 4A) SHEET A 1.0 - THERE IS AN INDICATION OF A REAR
 42"X80" DOOR BUT THOUGH IT DOES NOT APPEAR TO BE AN
 EXIT DOOR, THERE IS NO INDICATION OF HARDWARE OR IF
 WILL BE A FUNCTIONING DOOR.
  
 PLEASE PROVIDE DETAILS.
  
  
  
  
 5) SHEET A 1.0 - THERE IS AN INDICATION OF A DOUBLE
 LINE AROUND THE PERIMETER OF THEOPEN PATIO.
  
 WHAT DOES THIS EXTERIOR FEATURE CONSIST OF? IS IT A
 RAILING, A HALF WALL, SINGLE POSTS WITH FULL OPENINGS?
  
 PLEASE REVIEW, CORRECT WITH DETAILS AND ENSURE
 COMPLIANCE WITH APPLICABLE CODES.
  
  
  
 6) SHEET A 1.0 - THERE ARE INDICATIONS OF TWO OVERHEAD
 DOORS THAT LEAD TO THE EXTERIOR PATIO, HOWEVER, THSES
 DOORS CAN NOT FUNCTION AS EXIT DOORS.
  
 TWO EXITS ARE REQUIRED IN AN ASSEMBLY OCCUPANCY AND
 THEY SHALL BE SEPARATED FROM EACH OTHER PER NFPA 101 CH
 12 & 7
  
 12.2.4* NUMBER OF MEANS OF EGRESS.
 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE
 WITH SECTION 7.4, OTHER THAN EXITS FOR FENCED OUTDOOR
 ASSEMBLY
 OCCUPANCIES IN ACCORDANCE WITH 12.2.4.4.
  
 12.2.5 ARRANGEMENT OF MEANS OF EGRESS.
 12.2.5.1 GENERAL.
 12.2.5.1.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH
 SECTION 7.5.
 12.2.5.1.2 A COMMON PATH OF TRAVEL SHALL BE PERMITTED
 FOR THE FIRST
 20 FT (6100 MM) FROM ANY POINT WHERE THE COMMON PATH
 SERVES
 ANY NUMBER OF OCCUPANTS, AND FOR THE FIRST 75 FT (23 M)
 FROM ANY
 POINT WHERE THE COMMON PATH SERVES NOT MORE THAN 50
 OCCUPANTS.
  
 7.4* NUMBER OF MEANS OF EGRESS.
 7.4.1 GENERAL.
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS
 THAN TWO,
 EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED
 IN CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE
 OR BALCONY WHERE THE COMMON PATH OF TRAVEL LIMITATIONS
 OF
 CHAPTERS 11 THROUGH 43 ARE MET.
  
 7.5 ARRANGEMENT OF MEANS OF EGRESS.
 7.5.1 GENERAL.
 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL
 BE ARRANGED, SO
 THAT EXITS ARE READILY ACCESSIBLE AT ALL TIMES.
  
 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH
 7.5.1.3.1
 THROUGH 7.5.1.3.7.
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS
 REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH
 EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE
 POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER
 EMERGENCY
 CONDITION.
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE
 REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE
 ANOTHER NOT
 LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL
 DIMENSION OF THE BUILDING OR AREA TO BE SERVED,
 MEASURED IN A
 STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS,
 EXIT ACCESSES, OR
 EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3
 THROUGH
 7.5.1.3.5.
  
 PLEASE REVIEW AND CORRECT
  
  
 6A) SHEET A 1.0 - THERE ARE INDICATIONS OF TWO OVERHEAD
 DOORS THAT LEAD TO THE EXTERIOR PATIO, HOWEVER, THERE
 IS NO INDICATIONS OF THE DEPTH, IF ANY, OF THE STEP
 DOWN.
  
 PLEASE PROVIDE DETAILS.
  
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-03 Cont ID  
Sent By tklarge Date 2020-11-03 Time 08:57 Rev Time 0.00
Received By tklarge Date 2020-10-22 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-15 Cont ID  
Sent By ccarvaja Date 2020-10-15 Time 13:41 Rev Time 0.00
Received By ccarvaja Date 2020-09-30 Time 14:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-19 Cont ID  
Sent By jwitmer Date 2020-08-19 Time 10:03 Rev Time 0.00
Received By jwitmer Date 2020-07-27 Time 11:29 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By lmarchan Date 2020-11-16 Time 09:31 Rev Time 0.00
Received By lmarchan Date 2020-11-04 Time 09:53 Sent To  
Notes
2020-11-16 09:31:25RECEIPT - MU-2020-43448 - $12,597.54 - PAID
2020-11-04 09:53:4011/4/20 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-11-03 Cont ID  
Sent By lmarchan Date 2020-11-03 Time 12:08 Rev Time 0.00
Received By lmarchan Date 2020-11-03 Time 12:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-11-03 Cont ID  
Sent By tklarge Date 2020-11-03 Time 08:56 Rev Time 0.00
Received By tklarge Date 2020-11-03 Time 08:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-10-15 Cont ID  
Sent By tklarge Date 2020-10-15 Time 11:06 Rev Time 0.00
Received By tklarge Date 2020-10-15 Time 09:54 Sent To  
Notes
2020-10-15 10:01:131) THE SITE PLAN DOES NOT CLEARLY SHOW A DEFINED
 ACCESSIBLE ROUTE FROM THE SUBJECT BUILDING TO THE
 EXISTING COMMON AREA ACESSIBLE RESTROOMS.SHOW
 COMPLIANCE WITH FBC-ACCESSIBILITY SECS. 402,403, 405.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-12 Cont ID  
Sent By abelisle Date 2020-08-12 Time 06:26 Rev Time 0.00
Received By abelisle Date 2020-08-11 Time 18:00 Sent To  
Notes
2020-08-11 19:24:541ST REVIEW FBC-2017 PLUMBING
 PERMIT-20071234
 8/11/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- PLEASE INDICATE THE USE AND OCCUPANCY ON THE PLANS
  
 2- A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 PLUMBING CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 3- A SEPERATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR. WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 4- INTERCEPTORS SHALL BE DESIGNED AND SIZED BY THE
 GREASE INTERCEPTOR MANUFACTURE. FACTORY SIZING
 CALCULATIONS REQUIRED FROM THE MANUFACTURE FBC 2017 P
 1003.2
  
 5- PROVIDE HIGH LOW DRINKING FOUNTAIN. PLEASE INDICATE
 ON THE PLAN WHERE ONE WILL BE PROVIDED. FBC 2017
 A211.2, FBC 2017 P410.3
  
 6- PROVIDE SPECIFICATIONS FOR THE TANKLESS WATER HEATER
 AND THE BACKFLOW DEVICE TO BE INSTALLED.
  
 7- BAR AREA SHALL HAVE AN ACCESSIBLE TOP ELEVATION AS
 PER FBC 2017 A 902.1 A902.2 A902.3
  
 8- CLEAR WASTE AND DRINKING FOUNTAIN SHALL NOT
 DISCHARGE INTO GREASE INTERCEPTOR. REVISE PLUMBING
 ISOMETRIC TO REFLECT DRINKING FOUNTAIN AND HAND SINK
 DRAIN LINES CONNECTING TO SANITARY BUILDING MAIN DRAIN.
 FBC P 1003.2
  
 9- PLUMBING SYSTEM SHALL HAVE NOT LESS THAN ONE VENT
 PIPE THAT EXTENDS TO THE OUTDOORS FBC P 904.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-25 Cont ID  
Sent By jwitmer Date 2020-10-25 Time 13:29 Rev Time 0.00
Received By jwitmer Date 2020-10-25 Time 13:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-04 Cont ID  
Sent By jwitmer Date 2020-10-04 Time 11:46 Rev Time 0.00
Received By jwitmer Date 2020-10-04 Time 09:45 Sent To  
Notes
2020-10-04 11:46:44SHEET A3 THE ELECTRICAL SHEET DOES NOT HAVE AN DIGITAL
 SIGNATURE. 61G15-23.005 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS (DIGITAL
 SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-08-19 Cont ID  
Sent By jwitmer Date 2020-08-19 Time 10:00 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-08-19 10:02:2261G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 THE DIGITAL SEAL WILL NOT OPEN FOR VERIFICATION.