Plan Review Details - Permit 20071220
Plan Review Stops For Permit 20071220
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-08-31 Cont ID  
Sent By cpuell Date 2020-08-31 Time 10:51 Rev Time 0.00
Received By cpuell Date 2020-08-31 Time 12:08 Sent To  
Notes
2020-08-31 12:09:57ADDRESS ESTABLISHED AS 2062 PALM BEACHLAKES BLVD,
 UPDATED PERMIT RECORDS, INFORMED APPLICANT THAT THEY
 NEED TO SUBMIT A NEW APPLICATION FORM WITH THE CORRECT
 ADDRESS.
2020-08-31 10:52:05IN THE PLAN DOCUMENTS THE TITLEBLOCK AND THE SITE
 LOCATION IT IS SHOWING THE LOCATION AS BEING 2062 PALM
 BEACH LAKES BLVD. HOWEVER ON THE APPLICATION THE
 ADDRESS OF 2020 PALM BEACH LAKES BLVD WAS GIVE. IF THE
 CORRECT ADDRESS IS 2062 PALM BEACH LAKES BLVD, THEN ALL
 YOU WOULD HAVE TO DO IS SUBMIT A NEW APPLICATION FORM
 BUT THE PERMIT NUMBER WOULD REMAIN THE SAME. IF THE
 CORRECT ADDRESS IS 2020 PALM BEACH LAKES BLVD, THEN YOU
 WOULD NEED TO UPDATE YOUR PLANS.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-08-31 Cont ID  
Sent By rmcdouga Date 2020-08-31 Time 17:38 Rev Time 0.00
Received By rmcdouga Date 2020-08-31 Time 17:38 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-08-17 Cont ID  
Sent By jwitmer Date 2020-08-17 Time 14:27 Rev Time 0.00
Received By jwitmer Date 2020-08-17 Time 14:15 Sent To  
Notes
2020-08-17 14:26:58COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-22 Cont ID  
Sent By jwitmer Date 2020-09-22 Time 09:25 Rev Time 0.00
Received By jwitmer Date 2020-09-22 Time 08:30 Sent To  
Notes
2020-09-22 09:25:28DATE: TUES. SEPT. 22ND/ 2020
 ACTION: BUILDING PROVISO/ DEFERRED SUBMITTAL
  
 1) PROVISO. W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE
 CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-09-10 Cont ID  
Sent By jwitmer Date 2020-09-10 Time 15:02 Rev Time 0.00
Received By jwitmer Date 2020-09-10 Time 14:28 Sent To  
Notes
2020-09-10 15:04:02WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20071220
 ADD: 2020 OR 2062 PALM BEACH LAKES BLVD.
 CONT: MIKE MOORE CONSTRUCTION
 TEL: 561-301-9468
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. SEPT. 10TH/ 2020
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST. 1ST ROUND COMMENTS. SHEET 3.1 IS THE
 LIFE SAFETY SHEET. THIS SHEET INDICATES WITH A NOTE
 THIS IS TO BE A 150 SEAT RESTAURANT. THE FLOOR PLAN
 DOES NOT SHOW COMPLIANCE FOR ANY ACCESSIBLE SEATING.
  
 2A) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED 3,1
 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED. NO VERSION 2.
 1ST ROUND OF COMMENTS. ACCESSIBILITY CODE. 226.1 WHERE
 DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF
 FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES
 AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. 150 X 0.05= 7.5 OR 8 SEATS. (YOU ROUND UP TO
 THE NEXT WHOLE PERSON).
  
 2B) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED 3,1
 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED.
 2017 ACCESSIBILITY CODE 226.2 DISPERSION. DINING
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES INCLUDING BARS, SEASONAL SEATING, ETC?.
  
 2C) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED 3,1
 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED.
 2017 ACCESSIBILITY CODE 206.2.5 206.2.5 RESTAURANTS AND
 CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS,
 INCLUDING RAISED OR SUNKEN DINING AREAS, AND OUTDOOR
 DINING AREAS.
  
 2D) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED 3,1
 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED.
 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. DINING
 SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES,
 LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK SURFACES
 INCLUDE WRITING SURFACES,
  
 2D)(1) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED
 3,1 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED.
 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 SHALL BE PROVIDED. KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
  
 2D)(2) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED
 3,1 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED.
 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PLEASE SEE
 SHEET 3.3 BAR COUNTER TOPS DETAILS 6 ,9? 10, 11 & 12.
  
 2E) 2ND REQUEST. RESPONSE INDICATES SEE NEW UPDATED 3,1
 SHEET. SHEET 3.1 STILL SHOWS DATE 7/27/2020, NOT
 UPDATED.
 THE FRONT ENTRY IS ASSUMED TO BE A LEVEL FLOOR SURFACE
 FROM THE EXTERIOR TO THE INTERIOR WITH NO MORE THAN A ?
 INCH THRESHOLD, BUT THE PLANS ARE SILENT AS TO THE
 REQUIRED REAR EXIT FOR THE PUBLIC.
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS TO
 THE PUBLIC WAY.
  
 3A-C) COMPLIED.
  
 4A) PROVISO/ DEFERRED SUBMITTAL. EXTERIOR DOOR (NOA
 19-1016.03).
 4B) PROVISO. W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE
 CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5) 2ND REQUEST. RESPONSE LETTER INDICATES THE WIND
 DESIGN CRITERIA IS GIVEN ON THE NEW 3,1 SHEET. SHEET
 3.1 STILL SHOWS DATE 7/27/2020, NOT UPDATED. NO VERSION
 2.
 WITH THE REPLACEMENT OF AN EXTERIOR DOOR THERE SHOULD
 BE WIND DESIGN CRITERIA PROVIDED. 2017 FBC-B 1603.1.4
 WIND DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO
 WIND LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND
 LOADS GOVERN THE DESIGN OF THE LATERAL FORCE-RESISTING
 SYSTEM OF THE STRUCTURE:
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 5.2. RISK CATEGORY.
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO
 CONTACT ME, MY CELL NUMBER IS 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-17 Cont ID  
Sent By jwitmer Date 2020-08-17 Time 16:13 Rev Time 0.00
Received By jwitmer Date 2020-08-17 Time 14:15 Sent To  
Notes
2020-08-17 16:12:18WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20071220
 ADD: 2020 OR 2062 PALM BEACH LAKES BLVD.
 CONT: MIKE MOORE CONSTRUCTION
 TEL: 561-301-9468
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 17TH/ 2020
 ACTION: DENIED
  
 1) THE JOBSITE ADDRESS LOCATION IS IN QUESTION. THE
 PERMIT APPLICATION INDICATES 2020 PALM BEACH LAKES
 WHEREAS THE PLAN TITLEBLOCK GIVES THE ADDRESS OF 2062
 PALM BEACH LAKES BLVD?
 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2) SHEET 3.1 IS THE LIFE SAFETY SHEET. THIS SHEET
 INDICATES WITH A NOTE THIS IS TO BE A 150 SEAT
 RESTAURANT. THE FLOOR PLAN DOES NOT SHOW COMPLIANCE FOR
 ANY ACCESSIBLE SEATING.
  
 2A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902. 150 X 0.05= 7.5 OR 8
 SEATS. (YOU ROUND UP TO THE NEXT WHOLE PERSON).
  
 2B) 226.2 DISPERSION. DINING SURFACES REQUIRED TO
 COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE
 OR FACILITY CONTAINING DINING SURFACES INCLUDING BARS,
 SEASONAL SEATING, ETC?.
  
 2C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 2D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, CHECK WRITING
 SURFACES, COUPON COUNTERS, AND WHERE COVERED BY THE ADA
 SCOPING PROVISIONS, EMPLOYEE WORK STATIONS.
  
 2D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PLEASE SEE
 SHEET 3.3 BAR COUNTER TOPS DETAILS 6 ,9? 10, 11 & 12.
  
 2E) THE FRONT ENTRY IS ASSUMED TO BE A LEVEL FLOOR
 SURFACE FROM THE EXTERIOR TO THE INTERIOR WITH NO MORE
 THAN A ? INCH THRESHOLD, BUT THE PLANS ARE SILENT AS TO
 THE REQUIRED REAR EXIT FOR THE PUBLIC.
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS TO
 THE PUBLIC WAY.
  
 3A) SHEET 3.3 DETAILS FOR ACCESSIBLE REST ROOMS AND
 STALLS. NEITHER THE FLOOR PLAN NOR THE ELEVATION
 DETAILS GIVE A OVERALL DIMENSION OF THE BACK WALL OF
 THE RESTROOM AND STALL. CLEARANCES AT WATER CLOSETS.
 604.3 CLEARANCE. CLEARANCES AROUND THE WATER CLOSETS
 AND IN TOILET COMPARTMENTS SHALL COMPLY WITH 604.3.
 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR
 WALL. NOTE THE MINIMUM BACK WALL MEASUREMENT SHOULD BE
 7 FOOT 1 INCH.
  
 3B) DETAILS 2, 3 & 5 ALL ELEVATION VIEWS OF THE
 RESTROOMS SHOW THE GRAB BARS MEASURED CENTER LINE TO
 THE FLOOR. 6666 2017 FBC-ACCESSIBILITY CODE SECTION
 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 3C) PLEASE NOTE DETAILS 3 & 5 SHOW THE MAXIMUM HEIGHT
 MEASURED TO THE BOTTOM OF THE MIRROR, PLEASE LOOK AT
 NOTE # E THAT STATES THE MIRROR TO BE SURROUNDED BY A
 S. S. CHANNEL FRAME. WITH THE FRAME THE BOTTOM OF THE
 REFLECTIVE SURFACE OF THE MIRROR WILL BE ABOVE 40
 INCHES ABOVE FINISHED FLOOR. 603.3 MIRRORS. 2017
 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. 603.3
 MIRRORS. 2017 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 35 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 4) SHEET 10.1 THE DOOR SCHEDULE INDICATES AN EXTERIOR
 DOOR MARKED 104. THE DOOR SCHEDULE UNDER REMARKS STATES
 PROVIDE 180 DEGREE DOOR PEEP HOLE (NOA 19-1016.03).
  
 4A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(A) EXTERIOR DOORS.
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5) WITH THE REPLACEMENT OF AN EXTERIOR DOOR THERE
 SHOULD BE WIND DESIGN CRITERIA PROVIDED. 2017 FBC-B
 1603.1.4 WIND DESIGN DATA. THE FOLLOWING INFORMATION
 RELATED TO WIND LOADS SHALL BE SHOWN, REGARDLESS OF
 WHETHER WIND LOADS GOVERN THE DESIGN OF THE LATERAL
 FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 5.2. RISK CATEGORY.
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO
 CONTACT ME, MY CELL NUMBER IS 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-14 Cont ID  
Sent By jleahy Date 2020-08-14 Time 17:23 Rev Time 0.00
Received By jleahy Date 2020-08-14 Time 17:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-09-17 Cont ID  
Sent By pleduc Date 2020-09-17 Time   Rev Time 0.00
Received By pleduc Date 2020-09-17 Time 13:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-07-29 Cont ID  
Sent By sathomas Date 2020-07-29 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-07-29 Time 00:00 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-08-12 Cont ID  
Sent By ccole Date 2020-08-12 Time 14:48 Rev Time 0.00
Received By ccole Date 2020-08-12 Time 14:48 Sent To  
Notes
2020-08-12 14:49:31GAS PIPING INSTALLATIONS AND APPLIANCE CONNECTIONS
 SHALL BE DONE UNDER SEPARATE PERMIT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-22 Cont ID  
Sent By jwitmer Date 2020-09-22 Time 09:26 Rev Time 0.00
Received By jwitmer Date 2020-09-16 Time 10:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-09-10 Time 15:02 Rev Time 0.00
Received By lmarchan Date 2020-09-03 Time 10:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-08-17 Time 16:15 Rev Time 0.00
Received By lmarchan Date 2020-07-27 Time 14:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-08-17 Cont ID  
Sent By jwitmer Date 2020-08-17 Time 16:12 Rev Time 0.00
Received By jwitmer Date 2020-08-17 Time 14:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-08-06 Cont ID  
Sent By hmoser Date 2020-08-06 Time 10:54 Rev Time 0.00
Received By hmoser Date 2020-08-06 Time 09:17 Sent To  
Notes
2020-08-06 10:54:32REFER TO SECTION 307.2.1 CONDENSATE DISPOSAL.
 SECTION 307.2.1 FBC(M) 2017
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-09-04 Cont ID  
Sent By lcrespo Date 2020-09-04 Time 17:37 Rev Time 0.00
Received By lcrespo Date 2020-09-04 Time 17:37 Sent To  
Notes
2020-09-04 17:38:2209/04/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-12 Cont ID  
Sent By ccole Date 2020-08-12 Time 10:52 Rev Time 0.00
Received By ccole Date 2020-08-11 Time 15:33 Sent To  
Notes
2020-08-12 10:55:511ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20071220
 8/11/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1 & P2 SANITARY ISOMETRIC: A) THE WATER
 CLOSET (P-1) AT WOMEN 111 IS NOT BEING VENTED BECAUSE
 IT IS NOT CONNECTING DIRECTLY INTO THE HORIZONTAL WET
 VENTED BRANCH LINE SERVING P-3 AND THE FD. AN
 INDIVIDUAL VENT IS REQUIRED IF IT IS TO BE CONNECTED
 DIRECTLY INTO THE MAIN DRAIN. B) THE HORIZONTAL WET
 VENTED SYSTEM SERVING WOMEN 112 APPEARS TO BE
 NON-COMPLIANT BECAUSE THE DRAIN LINES FOR P-3 AND THE
 LOWER P-1 ARE EACH CONNECTING VERTICALLY INTO THE
 BRANCH DRAIN LINE AND HORIZONTAL CONNECTIONS ARE
 REQUIRED- SECTIONS 912.1, 912.2 & 912.2.1 FBC P. C)
 IDENTIFY THE FIXTURE NEXT TO THE ICE MAKER.
  
 2) P1: THE MAKE, MODEL AND CAPACITY OF THE EXISTING
 GREASE INTERCEPTOR MUST BE NOTED ON THE PLANS- SECTIONS
 1003.3.4 AND 1003.3.6. THE PLAN SHOWS NEW FLOOR SINKS
 BELOW FOOD AND BEVERAGE PREP COUNTERS,
 THREE-COMPARTMENT SINKS, AND ALSO IN THE CENTER OF THE
 COMMERCIAL KITCHEN BELOW THE STEAM TABLE ALL OF WHICH
 ARE DRAINING INTO THE SANITARY INSTEAD OF THE GREASY
 WASTE LINE. PLEASE REFER TO SECTION 1003.3.1 REVISE THE
 PLANS AND SIZING CALCULATIONS ACCORDINGLY.
  
 3) P-2: SUBMIT PRODUCT SPECIFICATION SHEETS FOR THE
 WATER HEATERS, AND EQUIPMENT SCHEDULES THAT INCLUDE THE
 EFFICIENCY RATINGS OF THE UNITS- SECTION C404.22 FBC
 EC. REFER TO TABLE 604.3 AND PROVIDE CALCULATIONS TO
 VERIFY THE EXISTING WATER HEATER SERVING THE PLUMBING
 FIXTURES IN THE KITCHEN AND BAR AREA HAS THE REQUIRED
 CAPACITY.
  
 4) P-2: PROVIDE A PLUMBING DEVICE SCHEDULE THAT
 INCLUDES THE BACKFLOW PREVENTERS AND WATER HAMMER
 ARRESTORS- SEE SECTION 604.9 & TABLE 608.1.
  
 5) SHEET 3.3: THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET IN THE MEN'S TOILET 106 COMPARTMENT SHALL BE 60
 INCHES WIDE MINIMUM MEASURED PERPENDICULAR TO THE SIDE
 WALL, AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED
 WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL
 SECTION 604.8.1.1 FBC ACC.
  
 6) 3.3: SHOW THE REQUIRED TURNING SPACES IN THE TOILET
 ROOMS AND COMPARTMENT- SECTION 304.3 AND FIGURE
 604.8.1.6
  
 7) 3.3: KNEE AND TOE CLEARANCES FOR THE LAVATORIES ARE
 NOT SHOWN- SECTION 306.
  
 8) 3.3: THE REAR GRAB BEHIND THE WATER CLOSET SHALL BE
 POSITIONED IN COMPLIANCE WITH FIGURE 604.5.2.
  
 9) 3.3: THE HEIGHT OF THE GRAB BARS SHALL BE 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE PLAN
 SHOWS THE MEASUREMENT TO THE CENTERLINE OF THE BARS-
 SECTION 609.4.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2020-09-04 Cont ID  
Sent By lcrespo Date 2020-09-04 Time 17:34 Rev Time 0.00
Received By lcrespo Date 2020-09-04 Time 17:34 Sent To  
Notes
2021-01-05 06:34:04VERIFIED INTERIOR SH
  
  
2020-09-04 17:37:35A SEPARATE PERMIT FOR THE GREASE INTERSCEPTOR IS
 REQUIRED BY A LICENSED CONTRACTOR FOR THE SCOPE OF WORK
 PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 09/04/20 REVIEWED FOR CODE COMPLIANCE
 (GREASE/INTERSCEPTOR)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-22 Cont ID  
Sent By jwitmer Date 2020-09-22 Time 09:26 Rev Time 0.00
Received By jwitmer Date 2020-09-22 Time 08:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-10 Cont ID  
Sent By jwitmer Date 2020-09-10 Time 15:04 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-17 Cont ID  
Sent By jwitmer Date 2020-08-17 Time 16:14 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved