| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SUNDAY AUGUST 02ND/ 2020 |
| ACTION: DENIED |
| |
| 1) THE OWNER IS TAKING EXCEPTION TO THE CONTRACTING |
| LAWS AND MUST FILE OUT A OWNER/ BUILDER FORM BEFORE |
| RESUBMITTING TO THE BUILDING DEPARTMENT. FORMS CAN BE |
| FOUND ON LINE. |
| |
| 2) THE STATED VALUE IS TO BE FOR THE VALUE OF THE |
| WINDOWS, LABOR AND HAULING AWAY OF ANY TRASH. THE VALUE |
| SEAMS LOW ON LABOR. LABOR IS USUALLY EQUAL TO THE COST |
| OF THE WINDOWS. THE CALCULATED VALUE IS $8,702.00 |
| DOLLARS. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 109.3* |
| BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 3) AS PERMITTING BY OWNER BUILDER YOU ARE TAKING |
| RESPONSIBILITY FOR THE FLOOR PLAN YOU DREW. JUST AS A |
| CONTRACTOR CAN CERTIFY THEIR OWN PLAN THE OWNER BUILDER |
| MUST ALSO TAKE THAT SAME RESPONSIBILITY BY SIGNING |
| THEIR NAME TO THE PLAN, AND THEN PRINTING THEIR NAME ON |
| THE PLAN. |
| 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET |
| OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| AND PLANS DRAWN. FOR EACH TRADE THE CONTRACTOR |
| RESPONSIBLE FOR THE DESIGN UNDER THE TRADE LICENSED IN |
| MUST PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE |
| NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY ONE |
| INDUVIAL, THEY WOULD HAVE TO BE LICENSED AS A BUILDING, |
| ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT ALL THESE |
| TRADES UNDER ONE SHEET. |
| |
| 4) THE SUBMITTED MIAMI-DADE NOA 18-0129.08 FOR MULLIONS |
| DOES NOT IDENTIFY WHICH TYPE OF MULLION THAT IS GOING |
| TO BE INSTALLED AND TRIBUTARY AREA THE MULLION IS GOING |
| TO TAKE THE LOAD OF AND PRESSURES. |
| PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO THE BUILDING DEPARTMENT. FOR ALL MULLIONS |
| PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 5) THE 2 ENGINEERING SHEETS LISTED AS 4100A & 4120AARE |
| DEFINITELY NOT A MIAMI-DADE NOA AND APPEAR NOT TO BE A |
| FLORIDA APPROVAL SINCE THERE IS NO LISTING NUMBER. |
| PLEASE NOTE FOR EITHER MIAMI-DADE NOA.S, FLORIDA |
| APPROVALS AND ALL OTHER APPROVALS WITH THE STATE OF |
| FLORIDA, THE PRODUCTS MUST HAVE THIRD PARTY |
| CERTIFICATION. THE CITY REQUIRES THE SAME 10 |
| REQUIREMENTS FOR A LOCAL APPROVAL AS REQUIRED BY THE |
| STATE. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| CODE 61G20-3.005, RULE 9N-3. |
| |
| 6) AS OWNER BUILDER YOU CAN FIND THE WIND DESIGN |
| PRESSURES YOU WILL NEED TO SUBMIT, GO TO THE WEBSITE: |
| FLORIDABUILDING.ORG, 2017 FLORIDA BUILDING CODE/ 6TH |
| EDITION/ TO THE RESIDENTIAL CODE BOOK THEN YOU WILL |
| NEED TO FIND 2 TABLES TO BE ABLE TO CALCULATE THE |
| PRESSURES: |
| TABLE R301.2(2) |
| TABLE R301.2(3) |
| |
| 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |