Plan Review Details - Permit 20071161
Plan Review Stops For Permit 20071161
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2020-09-12 Time 09:12 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-08-06 Cont ID  
Sent By jwitmer Date 2020-08-06 Time 16:03 Rev Time 0.00
Received By jwitmer Date 2020-08-06 Time 15:16 Sent To  
Notes
2020-08-06 16:02:58PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-12 Cont ID  
Sent By jwitmer Date 2020-09-12 Time 09:32 Rev Time 0.00
Received By jwitmer Date 2020-09-12 Time 09:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-06 Cont ID  
Sent By jwitmer Date 2020-08-06 Time 16:00 Rev Time 0.00
Received By jwitmer Date 2020-08-06 Time 15:16 Sent To  
Notes
2020-08-06 15:19:32WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20071161
 ADD: 550 OKEECHOBEE BLVD.
 CONT: EXCELL TILE CORP.
 TEL: 561-818-1955
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 06/2020
 ACTION: DENIED
  
 1) THE SUBMITTED FLOOR PLAN, THE CONTRACTOR MUST TAKE
 OWNERSHIP OF THE PLAN.
 CERTIFICATION BY CONTRACTOR.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE. 107.3.4.3
 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE EXCEPTION
 TO ENGINEERED PLANS UNDER 471.003(H) ELECTRICAL/
 PLUMBING/ MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES
 THE CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN
 THAT TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS
 THE SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH
 TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER
 THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR
 NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE
 DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED
 AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO
 SUBMIT ALL THESE TRADES UNDER ONE SHEET.
  
 2A) THE SUBMITTED FLOOR PLAN SHOWS THE MASTER BATH
 SHOWER AS PART OF THE 1 HOUR FIRE RATED PARTITION
 BETWEEN THE TWO UNITS. UNDER THE SCOPE OF WORK THE
 BACKER BOARD OF CONCRETE BOARD PLEASE PROVIDE EITHER A
 UL LISTING OR GYPSUM ASSOCIATION LISTING FOR THIS TYPE
 OF ASSEMBLY. 2017 FBC-B SECTION 708.3. FIRE PARTITIONS
 SHALL NOT HAVE A FIRE RESISTANCE RATING OF NOT LESS
 THAN 1 HOUR.
  
 2B) BOTH REQUIREMENTS NEED TO BE MET, 2A & 2B. 2017
 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE
 FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS AND
 CEILING PANELS IN SHOWER AREAS SHALL BE OF MATERIALS
 LISTED IN TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH
 MANUFACTURER?S RECOMMENDATIONS. WATER RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C840 AND THE MANUFACTURE?S
 RECOMMENDATIONS.
  
  
 3) PLEASE SHOW ON THE FLOOR PLAN WHICH WALL WILL HAVE
 THE SHOWER VALVE AND SHOWER HEAD. AGAIN THE CONCERN IS
 IF THEY ARE IN THE FIRE RATED WALL PROTECTION AROUND
 THE OPENING IN THE 1 HOUR FIRE PARTITION. SHOW
 COMPLIANCE WITH THE 2017 FBC-B 708.7 PENETRATIONS.
 PENETRATIONS OF FIRE RATED WALLS SHALL COMPLY WITH
 SECTION 714.
 SEE 714.3.2 MEMBRANE PENETRATIONS.
  
 4) THE SCOPE OF WORK INDICATES THE MASTER BATHROOM
 FLOOR AND SHOWER ENCLOSURE ARE TO BE COVERED UNDER THE
 SCOPE OF WORK FOR THIS PERMIT? IS THE TUB DECK & SKIRT
 ALSO BEING REPLACE? 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-15 Cont ID  
Sent By jesmith Date 2020-09-15 Time 12:05 Rev Time 0.00
Received By jesmith Date 2020-09-15 Time 12:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-08-06 Time 14:30 Rev Time 0.00
Received By lmarchan Date 2020-07-24 Time 12:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-09-15 Cont ID  
Sent By jsmith Date 2020-09-15 Time 12:04 Rev Time 0.00
Received By jesmith Date 2020-09-15 Time 12:01 Sent To  
Notes
2020-09-15 12:04:3420071161 550 OKEECHOBEE BLVD 1610
  
 PLUMBING COMMENTS: APPROVED
  
 PLUMBING PROVISO
 PENETRATION AT SHOWER VALVE AND SHOWER ARM/HEAD SHALL
 COMPLY WITH FBC 708.7 PENETRATIONS, PENETRATIONS OF
 FIRE RATED WALLS SHALL COMPLY WITH SECTION 714. SEE
 714.3.2 MEMBRANE PENETRATIONS.
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
2020-09-10 13:38:58FOR JERRY SMITH

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-06 Cont ID  
Sent By jwitmer Date 2020-08-06 Time 16:31 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-08-06 16:31:46WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- PLUMBING PLAN REVIEW
 W. P. B. PERMIT PRIME: 20071161
 W. P. B. PLUMBING PERMIT: 20071163
 ADD: 550 OKEECHOBEE BLVD.
 PLUMB.CONT: SBL CONSTRUCTION GROUP
 TEL: 561-676-6060
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 06/2020
 ACTION: DENIED
  
 1) THERE WERE NO PLANS SUBMITTED FOR PLUMBING. THE
 PLUMBING CONTRACTOR MUST DRAW THEIR OWN PLANS FOR THE
 SHOWER PAN.
 CERTIFICATION BY CONTRACTOR.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE. 107.3.4.3
 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE EXCEPTION
 TO ENGINEERED PLANS UNDER 471.003(H) ELECTRICAL/
 PLUMBING/ MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES
 THE CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN
 THAT TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS
 THE SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH
 TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER
 THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR
 NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE
 DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED
 AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO
 SUBMIT ALL THESE TRADES UNDER ONE SHEET.
  
 2) PLEASE PROVIDE DETAILS FOR THE SHOWER PAN COMPLYING
 WITH SECTION 417.5.2 OF THE 2017 FBC-P.
  
 3) THE SCOPE OF WORK INDICATES THE SHOWER VALVE IS TO
 BE REPLACED BUT DOES NOT PROVIDE THE SPEC SHEET ON THE
 SHOWER VALVE AND COMPLIANCE WITH SECTION 424.3
 INDIVIDUAL SHOWER VALVES 2017 FBC-P. SHOWER VALVES
 SHALL BE REQUIRED WITH A MEANS TO LIMIT THE MAXIMUM
 SETTING OF THE VALVE TO 120 DEGREES FAHRENHEIT.
  
 4) PLEASE SHOW ON THE FLOOR PLAN WHICH WALL WILL HAVE
 THE SHOWER VALVE AND SHOWER HEAD. AGAIN THE CONCERN IS
 IF THEY ARE IN THE FIRE RATED WALL PROTECTION AROUND
 THE OPENING IN THE 1 HOUR FIRE PARTITION. SHOW
 COMPLIANCE WITH THE 2017 FBC-B 708.7 PENETRATIONS.
 PENETRATIONS OF FIRE RATED WALLS SHALL COMPLY WITH
 SECTION 714.
 SEE 714.3.2 MEMBRANE PENETRATIONS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-12 Cont ID  
Sent By jwitmer Date 2020-09-12 Time 09:31 Rev Time 0.00
Received By jwitmer Date 2020-09-12 Time 09:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-08-06 Cont ID  
Sent By jwitmer Date 2020-08-06 Time 16:03 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-08-06 16:01:53CERTIFICATION BY CONTRACTOR.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE. 107.3.4.3
 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE EXCEPTION
 TO ENGINEERED PLANS UNDER 471.003(H) ELECTRICAL/
 PLUMBING/ MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES
 THE CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN
 THAT TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS
 THE SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH
 TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER
 THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR
 NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE
 DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED
 AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO
 SUBMIT ALL THESE TRADES UNDER ONE SHEET.
  
  