Plan Review Details - Permit 20071087
Plan Review Stops For Permit 20071087
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-08-28 Cont ID  
Sent By rmcphers Date 2020-08-28 Time 15:04 Rev Time 0.00
Received By rmcphers Date 2020-08-28 Time 15:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-09 Cont ID  
Sent By fgiaquin Date 2020-09-09 Time 20:44 Rev Time 0.00
Received By fgiaquin Date 2020-09-09 Time 20:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-13 Cont ID  
Sent By fgiaquin Date 2020-08-13 Time 22:14 Rev Time 0.00
Received By fgiaquin Date 2020-08-13 Time 21:28 Sent To  
Notes
2020-08-13 22:14:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE LOW FOR AMOUNT OF WORK SHOWN. RAISE VALUE OR
 VALUE WILL BE SET BY BUILDING OFFICIAL. FBC109.3
  
 2. DISCONNECT MUST BE WITHIN SIGHT OF SIGN PER 600.6A1
  
 3. LOW VOLTAGE AND HIGH VOLTAGE SHOWN TOGETHER IN JBOX
 FROM POWER SUPPLY. MUST BE SEPARATED NEC 725.136B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-09 Cont ID  
Sent By fgiaquin Date 2020-09-09 Time 20:44 Rev Time 0.00
Received By fgiaquin Date 2020-08-28 Time 15:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-28 Cont ID  
Sent By rmcphers Date 2020-08-28 Time 15:05 Rev Time 0.00
Received By rmcphers Date 2020-07-23 Time 10:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-28 Cont ID  
Sent By rmcphers Date 2020-08-28 Time 15:05 Rev Time 0.00
Received By rmcphers Date 2020-08-28 Time 15:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-07-31 Cont ID  
Sent By rthermid Date 2020-07-31 Time   Rev Time  
Received By rthermid Date 2020-07-31 Time   Sent To I
Notes
***NONE***