2020-08-04 10:05:26 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| ALTERNATE: CONTACT SAMANTHA HILL (561) 805-6724 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF |
| PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN |
| HEADING ??SHUTTER MOUNTING CONNECTION TYPE PER PRODUCT |
| APPROVAL?; PROVIDE INFORMATION FROM SHEETS 4-10 OF |
| MIAMI-DADE NOA NO. 18-0410.02 USE ALPHABETICAL LETTER |
| THAT CORRESPONDS WITH THE CONNECTION TYPE FOR THE TOP |
| AND BOTTOM CONNECTIONS EX. A, B, B1 ETC. COLUMN HEADING |
| ?SHUTTER SPAN?; PROVIDE INFORMATION FROM SHEET 3 OF |
| MIAMI-DADE NOA NO. 18-0410.02, THE TOP OF THE SHUTTER |
| BLADE TO THE BOTTOM OF THE SHUTTER BLADES LENGTH. |
| PLEASE VERIFY ANCHOR SPACING AS PER CONNECTION TYPE, |
| ANCHOR TYPE AND SUBSTRATE. |
| 2. FBC R 310.4. REVISE PLAN TO SHOW REQUIRED MEANS OF |
| ESCAPE. INCLUDE ROOM DESIGNATION. THE EGRESS |
| DESIGNATION SHOWN ON SUBMITTED DRAWING DOES NOT COMPLY |
| WITH R310.4 |
| |