Plan Review Details - Permit 20071069
Plan Review Stops For Permit 20071069
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-02 Cont ID  
Sent By pvalenti Date 2020-11-02 Time 10:19 Rev Time 0.00
Received By pvalenti Date 2020-11-02 Time 07:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-04 Cont ID  
Sent By jbrooks Date 2020-08-04 Time 10:05 Rev Time 0.00
Received By jbrooks Date 2020-08-04 Time 10:05 Sent To  
Notes
2020-08-04 10:05:26JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT SAMANTHA HILL (561) 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN
 HEADING ??SHUTTER MOUNTING CONNECTION TYPE PER PRODUCT
 APPROVAL?; PROVIDE INFORMATION FROM SHEETS 4-10 OF
 MIAMI-DADE NOA NO. 18-0410.02 USE ALPHABETICAL LETTER
 THAT CORRESPONDS WITH THE CONNECTION TYPE FOR THE TOP
 AND BOTTOM CONNECTIONS EX. A, B, B1 ETC. COLUMN HEADING
 ?SHUTTER SPAN?; PROVIDE INFORMATION FROM SHEET 3 OF
 MIAMI-DADE NOA NO. 18-0410.02, THE TOP OF THE SHUTTER
 BLADE TO THE BOTTOM OF THE SHUTTER BLADES LENGTH.
 PLEASE VERIFY ANCHOR SPACING AS PER CONNECTION TYPE,
 ANCHOR TYPE AND SUBSTRATE.
 2. FBC R 310.4. REVISE PLAN TO SHOW REQUIRED MEANS OF
 ESCAPE. INCLUDE ROOM DESIGNATION. THE EGRESS
 DESIGNATION SHOWN ON SUBMITTED DRAWING DOES NOT COMPLY
 WITH R310.4
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-02 Cont ID  
Sent By pvalenti Date 2020-11-02 Time 10:19 Rev Time 0.00
Received By pvalenti Date 2020-10-28 Time 10:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-04 Cont ID  
Sent By jbrooks Date 2020-08-04 Time 10:05 Rev Time 0.00
Received By jbrooks Date 2020-08-03 Time 14:07 Sent To  
Notes
2020-08-03 14:07:32TO BLDG < $5K
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved