Plan Review Details - Permit 20071007
Plan Review Stops For Permit 20071007
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-08-25 Cont ID  
Sent By cpuell Date 2020-08-25 Time 15:15 Rev Time 0.00
Received By cpuell Date 2020-08-25 Time 15:15 Sent To  
Notes
2020-08-25 15:15:538/25/20 ADDRESS CHANGED FROM 835 BELVEDERE TO 875
 BELVEDERE TO REFLECT CITY'S ROAD CENTER LINE OF NEW
 BUILDING TO BE CONSTRUCTED. CP
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By cpuell Date 2020-07-31 Time 11:01 Rev Time 0.00
Received By cpuell Date 2020-07-31 Time 11:01 Sent To  
Notes
2020-07-31 11:02:38NEW BUILDING NEWS A NEW ADDRESS, EMAILED APPLICANT WITH
 PROPOSED ADDRESS, PLEASE REACH OUT TO [email protected] TO
 DISCUSS ADDRESS POSSIBILITIES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-04-05 Cont ID  
Sent By rmcphers Date 2023-04-05 Time 09:59 Rev Time 0.00
Received By rmcphers Date 2023-04-05 Time 09:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-08 Cont ID  
Sent By rmcphers Date 2023-03-08 Time 08:12 Rev Time 0.00
Received By rmcphers Date 2023-03-08 Time 08:13 Sent To  
Notes
2023-03-08 08:12:09NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE REQUIRED ROOF DRAINAGE OVERFLOW
 SCUPPERS - FBC 1503.4.2.1 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 2) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK
 (FL10264) - THE ROOFING SYSTEM CIRCLED HAS A PRESSURE
 OF (-37.5 *) WHICH DOES NOT MEET THE REQUIRED WIND
 PRESSURES SHOWN ON DRAWING S1.
  
 3) ALL PRODUCT APPROVALS IN PROJECTDOX NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD
 OR LISTED ON THE DRAWINGS BY THE PRODUCT APPROVAL
 NUMBER - FBC WPB 107.3.4
  
 4) PLEASE PROVIDE THE EXTERIOR DOOR PRODUCT APPROVAL
 LISTED ON THE DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-12 Cont ID  
Sent By rmcphers Date 2023-01-12 Time 09:40 Rev Time 0.00
Received By rmcphers Date 2023-01-11 Time 13:11 Sent To  
Notes
2023-01-12 09:40:26NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE REQUIRED ROOF DRAINAGE OVERFLOW
 SCUPPERS - FBC 1503.4.2.1
  
 2) PLEASE SHOW THE WALLS SURROUNDING THE MOP SINK TO
 COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 3) DOORS LABELED (11) AND (12) ARE IN A SERIES AND
 REQUIRE MORE SPACE BETWEEN THEM - FBC ACCESSIBILITY
 404.2.6 DOORS IN SERIES AND GATES IN SERIES.
 THE DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN
 SERIES AND GATES IN SERIES SHALL BE 48 INCHES (1220 MM)
 MINIMUM PLUS THE WIDTH OF DOORS OR GATES SWINGING INTO
 THE SPACE.
  
 4) PLEASE SHOW THE WALL INSULATION TYPE AND "R" VALUE -
 FBC ENERGY
  
 5) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK
 (FL10284) AND (FL10264) - PLEASE CIRCLE THE ROOFING
 SYSTEM TO BE USED IN THE ROOFING PRODUCT APPROVAL -
 ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL MAY REQUIRE ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL - SEE
 GENERAL NOTES IN THE PRODUCT APPROVAL.
  
 6) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD OR LISTED ON THE
 DRAWINGS BY THE PRODUCT APPROVAL NUMBER - FBC WPB
 107.3.4
  
 7) THE HIGHER ROOF DOES NOT SHOW THE DECK TYPE - FBC
 107
  
 8) PLEASE SHOW THE WALL SHEATHING ATTACHMENT TYPE, SIZE
 AND ON CENTER SPACING TO METAL FRAMING - FBC 107
  
 9) BUILDING CONSTRUCTION TYPE IS SHOWN AS IIB - PLYWOOD
 WALL SHEATHING SHOULD BE SHOWN AS FIRE RETARDANT - FBC
 603.1
  
 10) PLEASE SHOW THE CEILING HEIGHT FOR THE ROOMS
 TOWARDS THE REAR OF THE BUILDING - FBC 1208.2
  
 11) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN REFERRING TO THE MIRROR
 HEIGHT FROM THE FLOOR - FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 12) EXTERIOR ALUMINUM SIDING IS SUBJECT TO WIND LOADS -
 PLEASE PROVIDE ATTACHMENT DETAILS OR PRODUCT APPROVALS
 - FBC 107
  
 13) SEPARATE PERMITS ARE REQUIRED FOR - EXISTING
 BUILDING DEMO., PARKING LOT, SITE WALLS/SCREEN WALLS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-15 Cont ID  
Sent By jleahy Date 2023-03-15 Time 15:47 Rev Time 0.00
Received By jleahy Date 2023-03-15 Time 15:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-01-10 Cont ID  
Sent By mpeterso Date 2023-01-10 Time 14:16 Rev Time 0.00
Received By mpeterso Date 2023-01-10 Time 14:16 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2020-12-20 Cont ID  
Sent By rrossano Date 2020-12-20 Time   Rev Time 0.00
Received By rrossano Date 2020-12-20 Time   Sent To  
Notes
2020-12-31 10:40:46DEVELOPER CAN MOVE FORWARD WITH ONSITE DEMO AT RISK.
 ENGINEERING PERMIT WILL NEED TO BE APPLIED FOR.
  
 CALL FOR LOCATES, DIAL 811 BEFORE YOU DIG. FOR MORE
 INFO ON "CALL BEFORE YOU DIG", GO TO
 HTTP://WWW.SUNSHINE811.COM (REF: UNDERGROUND FACILITY
 DAMAGE PREVENTION AND SAFETY ACT, FLORIDA STATUTE,
 CHAPTER 556.)
  
 THANKS,
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL
 33401
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
2020-12-20 09:21:35UNDER SITE PLAN REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-08-19 Cont ID  
Sent By rrossano Date 2020-08-19 Time   Rev Time  
Received By rrossano Date 2020-08-19 Time   Sent To  
Notes
2020-08-19 17:25:42UNDER STIE PLAN APPROVAL REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-04-05 Cont ID  
Sent By pleduc Date 2023-04-05 Time   Rev Time 0.00
Received By pleduc Date 2023-04-05 Time 10:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-03-02 Cont ID  
Sent By pleduc Date 2023-03-02 Time   Rev Time 0.00
Received By pleduc Date 2023-03-02 Time 11:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-20 Cont ID  
Sent By   Date 2022-12-20 Time   Rev Time  
Received By bdolan Date 2022-12-20 Time 11:10 Sent To  
Notes
2022-12-20 11:11:39ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING
 COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 CAPT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-07-31 Cont ID  
Sent By pleduc Date 2020-07-31 Time   Rev Time 0.00
Received By pleduc Date 2020-07-31 Time 16:09 Sent To  
Notes
2020-07-31 16:12:11THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM OR DEVICES
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE ENSURE COMPLIANCE
  
  
 2) ANY PROPOSED ACCESS CONTROL SHALL BE INSTALLED UNDER
 A SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE ENSURE COMPLIANCE
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2023-06-26 Cont ID  
Sent By aoliver Date 2023-06-26 Time 09:09 Rev Time 0.00
Received By aoliver Date 2023-05-22 Time 08:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-04-20 Cont ID  
Sent By asangele Date 2023-04-20 Time 09:35 Rev Time 0.00
Received By asangele Date 2023-04-20 Time 09:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-03-15 Cont ID  
Sent By jleahy Date 2023-03-15 Time 15:47 Rev Time 0.00
Received By jleahy Date 2023-03-01 Time 08:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-12 Cont ID  
Sent By asangele Date 2023-01-12 Time 15:01 Rev Time 0.00
Received By asangele Date 2023-01-12 Time 15:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-04 Cont ID  
Sent By shill Date 2021-03-04 Time 19:43 Rev Time 0.00
Received By shill Date 2021-02-09 Time 11:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-28 Cont ID  
Sent By shill Date 2020-12-28 Time 11:10 Rev Time 0.00
Received By shill Date 2020-12-09 Time 15:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-14 Cont ID  
Sent By shill Date 2020-10-14 Time 19:04 Rev Time 0.00
Received By shill Date 2020-07-30 Time 16:26 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2023-04-19 Time 16:26 Sent To  
Notes
2023-04-19 16:26:424/19/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2023-01-12 Cont ID  
Sent By rmcphers Date 2023-01-12 Time 09:42 Rev Time 0.00
Received By rmcphers Date 2023-01-12 Time 09:42 Sent To  
Notes
2023-01-12 09:42:49PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-02-19 Cont ID  
Sent By shill Date 2021-02-19 Time 09:13 Rev Time 0.00
Received By shill Date 2020-09-16 Time 14:34 Sent To  
Notes
2021-02-19 09:15:08**AFTER BUILDING AND ZONING PASS AUDIT/REVIEW, BUILDING
 REVIEWER IS TO VERIFY THAT THE PLAN THAT IMPACT FEES
 REVIEWED IS THE SAME AS PASSED BY ZONING AND BUILDING
 S.HILL
  
  
  
2021-02-16 13:10:10MU-2020-47056 - $10,841.23 - PAID
2020-09-16 14:35:039/16/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-06-21 Cont ID  
Sent By hmoser Date 2023-06-21 Time 09:28 Rev Time 0.00
Received By hmoser Date 2023-06-21 Time 09:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-04-19 Cont ID  
Sent By medwards Date 2023-04-19 Time 16:31 Rev Time 0.00
Received By medwards Date 2023-04-19 Time 16:31 Sent To  
Notes
2023-04-19 16:36:06PROVIDE THE OUTDOOR AIR FOR EACH USE OF SPACE ACCORDING
 TO FMC 403.3.1.1 AND TABLE 403.3.1.1. THE CALCULATIONS
 SUBMITTED FROM ASHRAE SEEM TO BE USING A DIFFERENT
 OCCUPANT COUNT THAN ALLOWED FROM THE 2020 FMC.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-03-09 Cont ID  
Sent By medwards Date 2023-03-09 Time 16:50 Rev Time 0.00
Received By medwards Date 2023-03-09 Time 16:50 Sent To  
Notes
2023-03-09 16:50:282ND REVIEW FMC
 PERMIT: 20071007
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OUTDOOR AIR CALCULATIONS SHALL BE CALCULATED
 BASED ON THE OCCUPANCY CLASSIFICATION AND THE OCCUPANT
 DENSITY FROM FMC TABLE 403.3.1.1 AND NOT THE ARCHITECTS
 EGRESS COUNTS. FMC 403.3.1.1
  
 2) SHOW THE REQUIRED DUCT SMOKE DETECTORS FOR THE RTUS
 THAT SHARE SUPPLY AIR. FMC 606.2.2
  
 3) PROVIDE THE ACCESS ON THE DRAWING FOR THE SERVICING
 OF THE ROOFTOP UNITS. FMC 306.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-03 Cont ID  
Sent By medwards Date 2023-01-03 Time 16:04 Rev Time 0.00
Received By medwards Date 2023-01-03 Time 16:04 Sent To  
Notes
2023-01-03 16:04:471ST REVIEW FMC
 PERMIT: 20071007
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON THE
 OCCUPANCY CLASSIFICATION THAT MOST CLOSELY RESEMBLES
 THE USE OF EACH SPACE FROM FMC TABLE 403.3.1.1. FMC
 403.3.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-04-10 Cont ID  
Sent By rwbrown Date 2023-04-10 Time 09:39 Rev Time 0.00
Received By rwbrown Date 2023-04-10 Time 09:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-03-02 Cont ID  
Sent By rwbrown Date 2023-03-02 Time 14:03 Rev Time 0.00
Received By rwbrown Date 2023-03-02 Time 14:03 Sent To  
Notes
2023-03-02 14:07:202ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 COMMENT NOT ADDRESSED - THIS COMMENT IS NOT FOR PUBLIC
 HAND WASHING REQUIREMENTS. THIS COMMENT IS FOR HOT
 WATER. A THERMOSTATIC MIXING VALVE NEEDS TO BE AT THE
 WATER HEATER FOR HOT WATER SUPPLY, NOT TEMPERED WATER
 DELIVERY. THE WATER HEATER DETAIL NEEDS TO SHOW A
 MIXING VALVE.
 1. 2020 FPC 607.1.1 - HOT WATER DELIVERY - PER THIS
 SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT
 SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER
 DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE.
 THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE
 INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1.
 THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC
 HANDWASHING PROTECTION FOR TEMPERED WATER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-05 Cont ID  
Sent By rwbrown Date 2023-01-05 Time 14:31 Rev Time 0.00
Received By rwbrown Date 2023-01-05 Time 14:31 Sent To  
Notes
2023-01-05 14:31:461ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 607.1.1 - HOT WATER DELIVERY - PER THIS
 SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT
 SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER
 DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE.
 THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE
 INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1.
 THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC
 HANDWASHING PROTECTION FOR TEMPERED WATER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status N Date 2022-11-17 Cont ID  
Sent By shill Date 2022-11-17 Time 18:52 Rev Time 0.00
Received By shill Date 2022-11-17 Time 18:52 Sent To  
Notes
2022-11-17 18:52:46PRIVATE PROVIDER RESCINDED
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status F Date 2021-02-16 Cont ID  
Sent By rgathrig Date 2021-02-16 Time 17:15 Rev Time 0.00
Received By rgathrig Date 2021-02-16 Time 17:14 Sent To  
Notes
2021-02-16 17:15:25 
  
  
 PRIVATE PROVIDER REVIEW NOT APPROVED
  
 ZONING, ENGINEERING AND IMPACT FEE OFFICE STILL NEED TO
 STILL SIGN OFF BEFORE THE PLANS ARE CONSIDERED A
 COMPLETE PERMIT PACKAGE.
  
 THE CERTIFICATE OF INSURANCE FROM THE PRIVATE PROVIDER
 DOES NOT STATE THERE IS PROFESSIONAL LIABILITY
 INSURANCE IN PLACE FOR THE SERVICES OF DOING PRIVATE
 PROVIDER PLAN REVIEW.
  
 AFFIDAVIT FOR CODE COMPLIANCE FOR PLAN REVIEW APPEAR TO
 LIST ALL THE PAGES BUT ARE SUBMITTED EARLY BECAUSE
 THERE HAS NOT BEEN A PLAN REVIEW AUDIT YET. IF ANY
 COMMENTS ARE CREATED FROM THE PLAN REVIEW AUDIT, NEW
 CODE COMPLIANCE AFFIDAVITS WILL BE REQUIRED
  
 RICHARD GATHRIGHT
 ABO
 561 805 6679
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2020-12-28 Cont ID  
Sent By shill Date 2020-12-28 Time 11:10 Rev Time 0.00
Received By shill Date 2020-12-28 Time 11:10 Sent To  
Notes
2020-12-28 11:10:30PRIVATE PROVIDER REVIEW NOT APPROVED
  
 THIS SUBMITTAL IS NOT COMPLETE BECAUSE THE PROJECT HAS
 NOT BEEN APPROVED BY OTHER AGENCIES FIRST BEFORE BEING
 SENT TO THE BUILDING DEPARTMENT
  
 RICHARD GATHRIGHT
 ABO
 561-805-6679
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2020-10-15 Cont ID  
Sent By rgathrig Date 2020-10-15 Time 16:01 Rev Time 0.00
Received By rgathrig Date 2020-10-15 Time 16:01 Sent To  
Notes
2020-10-15 16:01:15PRIVATE PROVIDER REVIEW NOT APPROVED
  
 THIS SUBMITTAL IS NOT COMPLETE BECAUSE THE PROJECT HAS
 NOT BEEN APPROVED BY OTHER AGENCIES FIRST BEFORE BEING
 SENT TO THE BUILDING DEPARTMENT
  
 RICHARD GATHRIGHT
 ABO
 561-805-6679
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2023-04-05 Cont ID  
Sent By rmcphers Date 2023-04-05 Time 10:04 Rev Time 0.00
Received By rmcphers Date 2023-04-05 Time 10:04 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2023-03-08 Cont ID  
Sent By rmcphers Date 2023-03-08 Time 08:12 Rev Time 0.00
Received By rmcphers Date 2023-03-08 Time 08:12 Sent To  
Notes
2023-03-08 08:13:41SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2023-01-12 Cont ID  
Sent By rmcphers Date 2023-01-12 Time 09:46 Rev Time 0.00
Received By rmcphers Date 2023-01-12 Time 09:46 Sent To  
Notes
2023-01-12 09:46:35SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-06-21 Cont ID  
Sent By hmoser Date 2023-06-21 Time 09:28 Rev Time 0.00
Received By hmoser Date 2023-06-21 Time 09:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-04-05 Cont ID  
Sent By rmcphers Date 2023-04-05 Time 10:12 Rev Time 0.00
Received By rmcphers Date 2023-04-05 Time 10:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-08 Cont ID  
Sent By rmcphers Date 2023-03-08 Time 08:22 Rev Time 0.00
Received By rmcphers Date 2023-03-08 Time 08:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-10 Cont ID  
Sent By mpeterso Date 2023-01-10 Time 14:18 Rev Time 0.00
Received By mpeterso Date 2023-01-10 Time 14:16 Sent To  
Notes
2023-01-10 14:19:20ALL PLANS PASSED SIGNATURE REVIEW
2023-01-03 16:05:32MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 8 Status F Date 2023-06-05 Cont ID  
Sent By asangele Date 2023-06-05 Time 11:45 Rev Time 0.00
Received By asangele Date 2023-06-05 Time 11:45 Sent To  
Notes
2023-06-05 11:46:266/5/2023
 FAILED
  
 MINOR SITE PLAN AMENDMENT IS REQUIRED
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 7 Status F Date 2023-04-20 Cont ID  
Sent By ASangele Date 2023-04-20 Time 09:35 Rev Time 0.00
Received By asangele Date 2023-04-20 Time 09:35 Sent To  
Notes
2023-04-20 09:46:46FAILED
 4/20/2023
  
 A MINOR SITE PLAN AMENDMENT IS REQUIRED.
  
 PARKING AND DRIVEWAY ENTERANCE HAS CHANGED THERE ALSO
 WAS A LOSS OF A PARKING SPOT PARKING TABLE NEEDS TO
 REFLECT THE CORRECT NUMBER OF PARKING LOCATED ON THE
 PROPERTY.
  
 COUNTY LETTER ALLOWING THE BELEVDERE ENTERANCE AS
 STATED IN THE CONTIONAL APPROVAL LETTER.
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 6 Status P Date 2023-03-23 Cont ID  
Sent By asangele Date 2023-03-23 Time 08:48 Rev Time 0.00
Received By asangele Date 2023-03-23 Time 08:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status F Date 2023-03-09 Cont ID  
Sent By LLouie Date 2023-03-09 Time 10:05 Rev Time 0.00
Received By kdefranc Date 2023-03-09 Time 10:03 Sent To  
Notes
2023-03-09 10:05:123/9/23 ??? FAILED
  
 REVIEW COMMENT TO BE ADDRESSED:
 1. THIS PROJECT NO LONGER HAS SITE PLAN APPROVAL. THE
 EXTENSION REQUEST APPROVAL EXPIRED JUNE 7, 2022.
  
  
 KEVIE DEFRANC
 SENIOR PLANNER ??? PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 4 Status F Date 2023-01-12 Cont ID  
Sent By asangele Date 2023-01-12 Time 14:59 Rev Time 0.00
Received By asangele Date 2023-01-12 Time 14:59 Sent To  
Notes
2023-01-12 15:01:171/12/2023
 FAILED
  
 THIS PROJECT NO LONGER HAS SITE PLAN APPROVAL
 EXPIRED JUNE 7,2022
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2021-03-04 Time   Rev Time 0.00
Received By   Date 2021-03-04 Time   Sent To  
Notes
2021-03-04 11:30:33*************ZONING REVIEW***************
  
 SUBMITTED SITE PLAN IS FINE.
  
 ACCORDING TO YOUR SITE PLAN APPROVAL LETTER THE
 APPROVAL IS SUBJECT TO THE FOLLOWING CONDTIONS:
  
 1. NO NEW DRAINAGE STRUCTURES ARE TO BE LOCATED WITHIN
 THE PROPOSED RIGHT-OF-WAY.
 2. THE ENGINEERING PLANS AND SURVEY SHALL REFERENCE THE
 SAME VERTICAL DATUM.
 3. PROVIDE COUNTY LETTER/APPROVAL PERTAINING TO THE
 BELVEDERE DRIVEWAY LOCATION AND CONFIGURATION.
 4. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED, AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
  
 PROVIDE DOCUMENTATION FOR #3.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISON
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2020-12-22 Cont ID  
Sent By awooten Date 2020-12-22 Time   Rev Time 0.00
Received By awooten Date 2020-12-22 Time   Sent To  
Notes
2020-12-22 10:34:34****************************ZONING REVIEW
 FAILED***********************************
  
 SUBMIT THE APPROVED SITE PLAN. THE SITE PLAN SUBMITTED
 DOES NOT MATCH WHAT WAS APPROVED.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-02 Cont ID  
Sent By awooten Date 2020-10-02 Time   Rev Time  
Received By awooten Date 2020-10-02 Time   Sent To  
Notes
2020-10-02 12:59:22************ZONING REVIEW FAILED**************
  
 THE 40 FT X 40 FT DEDICATION TO THE COUNTY AT THE
 CORNER OF PARKER AND BELVEDERE WILL AFFECT THE BUILDING
 SETBACKS. INDICATE THE NEW SETBACKS, CONSIDERING THE
 DEDICATION.
  
 REPLAT REQUIRED AS A CONDITION OF CO.
  
 SUBMIT SITE PLAN APPROVAL LETTER AND APPROVED SITE
 PLAN.
  
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  