Plan Review Details - Permit 20070974
Plan Review Stops For Permit 20070974
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-10-23 Cont ID  
Sent By pvalenti Date 2020-10-23 Time 13:24 Rev Time 0.00
Received By pvalenti Date 2020-10-23 Time 06:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-23 Cont ID  
Sent By rmcphers Date 2023-01-23 Time 11:26 Rev Time 0.00
Received By rmcphers Date 2023-01-19 Time 08:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-23 Cont ID  
Sent By pvalenti Date 2020-10-23 Time 13:26 Rev Time 0.00
Received By pvalenti Date 2020-10-13 Time 14:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-01-23 Cont ID  
Sent By rmcphers Date 2023-01-23 Time 11:21 Rev Time 0.00
Received By rmcphers Date 2023-01-23 Time 11:21 Sent To  
Notes
2023-01-23 11:26:24SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) SIGNED AND SEALED DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
 ( YOU SHOULD TRY TO UPLOAD THE SIGNED AND SEALED
 DRAWINGS SEPARATELY FROM THE PACKAGE - I CHECK THE
 ELECTRONIC SIGNATURE BY OPENING THEM IN ???ADOBE
 READER???. THE ???ADOBE READER??? STATES WHETHER THEY
 ARE AN ORIGINAL ELECTRONICALLY SIGNED DOCUMENT. WHEN
 ELECTRONICALLY SIGNED DRAWINGS ARE PRINTED OUT, THEY
 LOSE THEIR ELECTRONIC SIGNATURE. ELECTRONICALLY SIGNED
 DRAWINGS NEED TO BE MOVED AROUND IN THE COMPUTER FROM
 PLACE TO PLACE. FROM THE ARCHITECT???S OR ENGINEER???S
 COMPUTER TO YOUR COMPUTER TO THE CITY???S ELECTRONIC
 PLAN REVIEW (PROJECTDOX). )

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-23 Cont ID  
Sent By pvalenti Date 2020-10-23 Time 13:24 Rev Time 0.00
Received By pvalenti Date 2020-10-23 Time 06:21 Sent To  
Notes
2020-10-23 13:26:03PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW DENIED:
  
 FBC B 107.2, ALL PAGES OF THE SUBMITTED SHOP DRAWINGS
 NEED TO BE SIGNED AND SEALED BY THE DELEGATED ENGINEER.