2020-08-28 13:18:32 | 1ST REVIEW FBC-2017 RES. |
| PERMIT- 20070889 |
| 8/28/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) LP GAS TANK AND LP REGULATOR SPECS HAVE BEEN |
| SUBMITTED WHICH ARE NOT RELEVANT TO THE NATURAL GAS |
| GENERATOR INSTALLATION. I AM NOT ABLE TO SEPARATE OUT |
| THE RELEVANT SUBMITTALS IN THE PACKAGE YOU SUBMITTED SO |
| PLEASE SEPARATELY RESUBMIT THE DORMONT FLEX CONNECTOR |
| AND THE PE PIPING SPECS. ONCE THOSE ARE RECEIVED THE |
| INITIAL PACKAGE SENT WILL BE VOIDED- SECTION 107.2.1 |
| WPB. |
| |
| 2) GAS SURVEY: PLEASE SUBMIT THE GENERAC MANUFACTURER'S |
| GUIDELINES FOR INSTALLATION CLEARANCES TO VERIFY THE |
| CLEARANCES SPECIFIED ON THE DRAWING. THE GUIDELINES CAN |
| SUPERSEDE THE MINIMUM 10 FT. CLEARANCE TO OPERABLE |
| OPENINGS INTO THE BUILDING PER SECTION R303.5.1 FBC |
| RES. |
| |
| 3) GAS RISER: |
| |
| A) PROVIDE THE DELIVERY PRESSURE AT THE METER- SECTIONS |
| G2413.2, G2413.4.1 & G2413.5 FBC RES. |
| |
| B) PROVIDE THE TOTAL DEVELOPED LENGTH FROM THE METER TO |
| THE MOST REMOTE APPLIANCE- PLEASE INCLUDE THE BRANCH |
| LINE TO THE POOL HEATER WHICH IS NOT SHOWN ON THE |
| RISER- SECTIONS G2413.4.1 & G2413.2. |
| |
| C) PROVIDE THE PIPE SIZING TABLES LISTED UNDER SECTION |
| G2413.4. PLEASE NOTE THAT THE TABLE 402.4(3) FROM THE |
| FBC FG SUBMITTED WITH THE REGULATOR SPECS CANNOT BE |
| USED BECAUSE PIPE SIZING SHALL BE DONE ACCORDING TO THE |
| TABLES IN THE FBC RES. THERE IS NO RELEVANT TABLE IN |
| THE FBC RES THAT ALLOWS THE 3.0 IN. WC PRESSURE DROP. |
| PLEASE SEE TABLE G2413.4(1) WHICH INDICATES A TYPICAL |
| 0.5 IN. WC PRESSURE DROP FOR RESIDENTIAL APPLIANCES, |
| AND REFER TO SECTION G2413.5 FOR FURTHER CLARIFICATION. |
| PLEASE NOTE THAT THE TABLES IN THE FBC FG CAN BE USED |
| IF THE RELEVANT TABLE IS CONTAINED IN THE FBC RES SUCH |
| AS TABLE G2413.4(1) & {402.4(2)}. |
| |
| 4) PLEASE RESUBMIT THE REGULATOR SPECS MARKED UP TO |
| SHOW MODEL, PRESSURE DROP, AND SPRING SELECTIONS. IN |
| LIEU OF MARKING UP THE SPECS, PLEASE PROVIDE THE |
| INFORMATION ON THE RESUBMITTED RISER DRAWING- SECTIONS |
| G2421.1 & G2421.2 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |