Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-09-15 Cont ID  
Sent By shill Date 2020-09-15 Time 17:28 Rev Time 0.00
Received By shill Date 2020-09-15 Time 17:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-28 Cont ID  
Sent By cthroop Date 2020-08-28 Time 09:42 Rev Time 0.00
Received By cthroop Date 2020-08-28 Time 09:11 Sent To  
Notes
2020-08-28 09:43:19PLAN REVIEW GENERATOR - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER
 SWITCH. ? ATS
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-08-28 Cont ID  
Sent By ccole Date 2020-08-28 Time 13:18 Rev Time 0.00
Received By ccole Date 2020-08-28 Time 11:28 Sent To  
Notes
2020-08-28 13:18:321ST REVIEW FBC-2017 RES.
 PERMIT- 20070889
 8/28/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) LP GAS TANK AND LP REGULATOR SPECS HAVE BEEN
 SUBMITTED WHICH ARE NOT RELEVANT TO THE NATURAL GAS
 GENERATOR INSTALLATION. I AM NOT ABLE TO SEPARATE OUT
 THE RELEVANT SUBMITTALS IN THE PACKAGE YOU SUBMITTED SO
 PLEASE SEPARATELY RESUBMIT THE DORMONT FLEX CONNECTOR
 AND THE PE PIPING SPECS. ONCE THOSE ARE RECEIVED THE
 INITIAL PACKAGE SENT WILL BE VOIDED- SECTION 107.2.1
 WPB.
  
 2) GAS SURVEY: PLEASE SUBMIT THE GENERAC MANUFACTURER'S
 GUIDELINES FOR INSTALLATION CLEARANCES TO VERIFY THE
 CLEARANCES SPECIFIED ON THE DRAWING. THE GUIDELINES CAN
 SUPERSEDE THE MINIMUM 10 FT. CLEARANCE TO OPERABLE
 OPENINGS INTO THE BUILDING PER SECTION R303.5.1 FBC
 RES.
  
 3) GAS RISER:
  
 A) PROVIDE THE DELIVERY PRESSURE AT THE METER- SECTIONS
 G2413.2, G2413.4.1 & G2413.5 FBC RES.
  
 B) PROVIDE THE TOTAL DEVELOPED LENGTH FROM THE METER TO
 THE MOST REMOTE APPLIANCE- PLEASE INCLUDE THE BRANCH
 LINE TO THE POOL HEATER WHICH IS NOT SHOWN ON THE
 RISER- SECTIONS G2413.4.1 & G2413.2.
  
 C) PROVIDE THE PIPE SIZING TABLES LISTED UNDER SECTION
 G2413.4. PLEASE NOTE THAT THE TABLE 402.4(3) FROM THE
 FBC FG SUBMITTED WITH THE REGULATOR SPECS CANNOT BE
 USED BECAUSE PIPE SIZING SHALL BE DONE ACCORDING TO THE
 TABLES IN THE FBC RES. THERE IS NO RELEVANT TABLE IN
 THE FBC RES THAT ALLOWS THE 3.0 IN. WC PRESSURE DROP.
 PLEASE SEE TABLE G2413.4(1) WHICH INDICATES A TYPICAL
 0.5 IN. WC PRESSURE DROP FOR RESIDENTIAL APPLIANCES,
 AND REFER TO SECTION G2413.5 FOR FURTHER CLARIFICATION.
 PLEASE NOTE THAT THE TABLES IN THE FBC FG CAN BE USED
 IF THE RELEVANT TABLE IS CONTAINED IN THE FBC RES SUCH
 AS TABLE G2413.4(1) & {402.4(2)}.
  
 4) PLEASE RESUBMIT THE REGULATOR SPECS MARKED UP TO
 SHOW MODEL, PRESSURE DROP, AND SPRING SELECTIONS. IN
 LIEU OF MARKING UP THE SPECS, PLEASE PROVIDE THE
 INFORMATION ON THE RESUBMITTED RISER DRAWING- SECTIONS
 G2421.1 & G2421.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-09-15 Cont ID  
Sent By shill Date 2020-09-15 Time 17:30 Rev Time 0.00
Received By shill Date 2020-08-18 Time 15:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-08-28 Cont ID  
Sent By ccole Date 2020-08-28 Time 13:18 Rev Time 0.00
Received By ccole Date 2020-08-28 Time 13:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-09-15 Cont ID  
Sent By shill Date 2020-09-15 Time 17:30 Rev Time 0.00
Received By shill Date 2020-09-15 Time 17:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-09-01 Cont ID  
Sent By kalexand Date 2020-09-01 Time 22:54 Rev Time 0.00
Received By kalexand Date 2020-09-01 Time 22:54 Sent To I
Notes
2020-09-01 22:55:10ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 09/01/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1.INDICATE SETBACK DIMENSIONS FROM THE PROPOSED
 GENERATOR EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE
 CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-305(B)(4): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  
  
  