| 20070888 815 NATHAN HALE RD |
| |
| 1ST REVIEW |
| |
| GAS COMMENTS: |
| |
| 1. THE GAS TANK-LESS WATER HEATER IS NOTED AS FUTURE. |
| IF THE CURRENT PERMIT IS OPEN A REVISION WILL BE |
| REQUIRED TO SHOW THE INSTALLATION OF THE APPLIANCE. IF |
| PERMIT IS CLOSED WITHOUT INSTALLATION OF SAID |
| APPLIANCE, A NEW GAS PERMIT APPLICATION, PLAN AND |
| MANUFACTURER'S SPECIFICATION SHEETS / INSTALLATION |
| MANUAL SHALL BE SUBMITTED FOR THE INSTALLATION. |
| ADDITIONALLY, IN EITHER CASE A PLUMBING PERMIT |
| APPLICATION, PLAN AND UPDATED MANUFACTURER'S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL SHALL BE |
| SUBMITTED AT THE TIME OF REVISION OR NEW PERMIT. |
| 2. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT INCLUDING THE |
| FUTURE TANK-LESS WATER HEATER TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, FBC FG 402.2, AND 301.3 OR |
| FBC RES G2404.3. GAS APPLIANCES SHALL BE LISTED AND |
| LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION PER FBC FG.305.1 AND FBC RES G2408.1. |
| 3. PER WPB FBC 107.2.1, INDICATE ON THE RISER DIAGRAM |
| THE TYPE OF GAS (LP OR NATURAL). |
| 4. SHOW ON THE HOUSE PLAN THE LOCATION OF THE TANKLESS |
| WATER HEATER AND THE LOCATION AND DISTANCE OF ANY |
| OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| HOUSE PLAN DOES NOT SPECIFICALLY STATE THE BBQ AND THE |
| FUTURE GAS TANKLESS WATER HEATER LOCATION; THE RISER |
| DIAGRAM AND THE SURVEY DO NOT CORRESPOND WITH EACH |
| OTHER. RECONCILE ALL THREE DOCUMENTS TO SHOW |
| CONSISTENCY OF PIPE ROUTING SAND APPLIANCE LOCATION. |
| 5. SUBMITTAL FOR REGULATORS DOES NOT INDICATE THAT THEY |
| ARE APPROVED FOR OUTDOOR INSTALLATION. PER WPB FBC |
| 107.2.1, PROVIDE DOCUMENTATION THAT REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING ARE APPROVED |
| FOR OUTDOOR INSTALLATION AS REQUIRED BY FBC FG 410.1 OR |
| FBC RES G2421.1. |
| 6. PER WPB 107.2.1, SHOW THE DISTANCE FROM THE MP |
| REGULATOR TO THE APPLIANCE(S). PROVIDE MATERIAL TYPE(S) |
| AND SIZING TABLE(S) FOR THE SAME. COMPLY WITH FBC FG. |
| 402.4 OR FBC RES G2413.4 FOR THE PROPER PIPE SIZE AND |
| BTU LOAD. |
| 7. SEE WPB FBC 107.3.4.3 CERTIFICATION BY CONTRACTOR. |
| PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER |
| 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL, |
| 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR |
| THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL |
| ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER |
| THAT TRADE. THE CONTRACTOR (QUALIFIER) THAT CREATED / |
| DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES |
| AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, |
| SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE |
| LICENSED IN AND PLANS DRAWN. FOR EACH TRADE THE |
| CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER THE TRADE |
| LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR NAME AND |
| LICENSE NUMBER. AS THE PLANS ARE NOT DIGITALLY SIGNED, |
| THE APPLICANT SHALL PROVIDE SIGNED PAPER DOCUMENT PRIOR |
| TO PERMIT ISSUANCE. CALL 561-805-6724 FOR ADDITIONAL |
| INFORMATION. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| AS THE PLANS ARE NOT SIGNED AND SEALED BY A |
| PROFESSIONAL ENGINEER OR ARCHITECT, THE GAS/PLUMBING |
| PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR |
| THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION |
| NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR |
| LICENSED IN THAT TRADE. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-246-0882 MOBILE |
| |
| 20070888 815 NATHAN HALE RD |
| |