Plan Review Details - Permit 20070880
Plan Review Stops For Permit 20070880
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-10-16 Cont ID  
Sent By pvalenti Date 2020-10-16 Time 13:52 Rev Time 0.00
Received By pvalenti Date 2020-10-16 Time 13:51 Sent To  
Notes
2020-10-16 13:54:20PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ASBESTOS REVIEW DENIED:
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-08-17 Cont ID  
Sent By jwitmer Date 2020-08-17 Time 10:38 Rev Time  
Received By jwitmer Date 2020-08-17 Time 10:32 Sent To  
Notes
2020-08-17 10:38:51TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-10-16 Cont ID  
Sent By pvalenti Date 2020-10-16 Time 15:48 Rev Time 0.00
Received By pvalenti Date 2020-10-16 Time 13:51 Sent To  
Notes
2020-10-16 14:31:43PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 109.3, THE VALUATION OF THE PROJECT APPEARS TO
 BE LOW. PROVIDE A BREAK DOWN OF THE VALUATION INCLUDING
 ALL MATERIAL, LABOR & SERVICES INVOLVED.
  
 2) FBC B 107, PROVIDE A REPORT FROM AN ACCEPTABLE
 LICENSED COMPANY SHOWING THE LOCATION OF POST TENSION
 CABLES (X-RAYED OR OTHER ACCEPTABLE METHOD). THIS IS TO
 AVOID DAMAGE TO CABLES DURING PENETRATION OF SLAB.
  
 3) FBC B 714.4.1.2, FBC B TABLE 601, PROVIDE
 INFORMATION OF MATERIAL TO BE USED TO SEAL THE FLOOR
 PENETRATIONS (2HR RATING REQUIRED).
  
 4) FBC B 2509.2, PROVIDE INFORMATION AS TO THE TYPE OF
 WATER RESISTANT WALL BOARD THAT WILL BE USED IN THE WET
 AREAS OF THE EXTENDED SHOWER SPACE.
  
 5) FBC B 1207.2, 1207.2 & 603.1, THE FOLLOWING TESTS
 ARE REQUIRED AT THE NEW FLOORING AREAS (EXISTING BATH
 TUB AREA).
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) :
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 NOTE: PLEASE FEEL FREE TO CONTACT ME IF YOU ARE UNSURE
 ABOUT AN ACCEPTABLE FLOOR UNDERLAYMENT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-17 Cont ID  
Sent By jwitmer Date 2020-08-17 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2020-08-17 Time 10:31 Sent To  
Notes
2020-08-17 11:54:35WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20070880
 ADD: 801 S OLIVE AVE. # 1018
 CONT: CHI CONSTRUCTION
 TEL: 407-808-3849
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 17TH/ 2020
 ACTION: DENIED
  
 1A) THE DECLARED VALUE OF THE WORK OF THIS PERMIT IS
 $9,750.00 DOLLARS, THIS AMOUNT SEEMS LOW. IT WOULD
 APPEAR THE VALUE OF THE CABINETS, COUNTER TOPS FOR THE
 KITCHEN AND MASTER BATH ARE NOT INCLUDED IN THE VALUE
 DECLARED. NOTE # 4 INDICATES THE REMOVAL OF FLOOR TILE
 AND NEW FLOOR TILE TO BE PROVIDED BY THE OWNER.
  
 1B) IT WOULD APPEAR THE VALUE OF THE FLOOR TILE IS NOT
 PART OF THE DECLARED VALUE AND THE OTHER UNCERTAIN
 THING IS THE SCOPE OF THE TILE? IS THE TILE FLOOR WORK
 JUST FOR THE BATHROOM OR FOR THE WHOLE FLOOR AREA OF
 THE CONDOMINIUM?
  
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) TO KEEP IN THE SCOPE OF THE LICENSING LAWS FOR A CBC
 NONE OF THE CONTRACTOR?S SERVICES CAN AFFECT THE
 STRUCTURAL MEMBERS OF THE BUILDING. THE DESIGNER OF
 RECORD SHOULD NOTE ON THE PLANS THAT THE CONTRACTOR
 MUST HAVE THE CONCRETE FLOOR SYSTEM X-RAYED TO LOCATE
 THE POSITION OF THE POST STRESSED TENTDENS. THIS COST
 MUST ALSO BE ADDED TO THE OVERALL PROJECT VALUE.
 FLORIDA STATUTE 489.105(3)(B).?BUILDING CONTRACTOR?
 MEANS A CONTRACTOR WHOSE SERVICES ARE LIMITED TO
 CONSTRUCTION OF COMMERCIAL BUILDINGS AND
 SINGLE-DWELLING OR MULTIPLE-DWELLING RESIDENTIAL
 BUILDINGS, WHICH DO NOT EXCEED THREE STORIES IN HEIGHT,
 AND ACCESSORY USE STRUCTURES IN CONNECTION THEREWITH OR
 A CONTRACTOR WHOSE SERVICES ARE LIMITED TO REMODELING,
 REPAIR, OR IMPROVEMENT OF ANY SIZE BUILDING IF THE
 SERVICES DO NOT AFFECT THE STRUCTURAL MEMBERS OF THE
 BUILDING.
  
 3) WITH THE NEW HOLE THROUGH THE FLOOR FOR THE SHOWER
 AS WELL AS THE OLD EXISTING WASTE FOR THE OLD TUB HOW
 ARE THESE HOLES TO BE FIRE SAFED? PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-B SECTION 714.4.1.2
 THROUGH PENETRATION FIRE STOP SYSTEMS. PLEASE NOTE THAT
 THE SYSTEM SHALL HAVE AN F RATING/ T RATING OF NOT LESS
 THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED RATING OF
 THE FLOOR PENETRATED. SEE TABLE 601 FOR FLOOR
 CONSTRUCTION 2 HOUR FLOOR SYSTEM IS REQUIRED.
  
 4) THE FLOOR PLAN INDICATES WITH NOTE # 2 A NEW MASTER
 BATH SHOWER BUT IS SILENT AS TO THE TYPE OF BACKER
 BOARD NOR THE HEIGHT OF THE TILE IN THE SHOWER?
 4A) 2017 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 4B) 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72INCHES ABOVE THE DRAIN INLET.
  
 5) FLOOR INSULATION (FBC-B 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING
 COMPLIANCE WITH:
  
 TYPE I AND II BUILDINGS
 5A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 5B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2020-10-16 Cont ID  
Sent By jleahy Date 2020-10-16 Time 13:33 Rev Time 0.00
Received By jleahy Date 2020-10-16 Time 13:31 Sent To  
Notes
2020-10-16 13:34:12NO ELECTRICAL WORK FOR THIS JOB JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-27 Cont ID  
Sent By jleahy Date 2020-08-27 Time 10:30 Rev Time 0.00
Received By jleahy Date 2020-08-27 Time 10:28 Sent To  
Notes
2020-08-27 10:32:49NO ELECTRIC SHOWN JLEAHY
  
 PLEASE SUBMIT AN ELECTRICAL DRAWING SHOWIN LOCATION OF
 OUTLETS AND LIGHTS IN BATH.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-16 Cont ID  
Sent By shill Date 2020-10-16 Time 16:23 Rev Time 0.00
Received By lcrespo Date 2020-10-16 Time 13:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-27 Cont ID  
Sent By jleahy Date 2020-08-27 Time 10:32 Rev Time 0.00
Received By jleahy Date 2020-07-24 Time 12:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-08-17 Cont ID  
Sent By hmoser Date 2020-08-17 Time 13:39 Rev Time 0.00
Received By hmoser Date 2020-08-17 Time 12:28 Sent To  
Notes
2020-08-17 13:39:23NO AIR CONDITIONING WORK STARTING AT THIS TIME. IF AIR
 CONDITIONING
 WORK NEEDS TO BE DONE SEPARATE APPLICATION, PLAN AND
 PERMIT
 WILL BE REQUIRED.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-10-16 Cont ID  
Sent By lcrespo Date 2020-10-16 Time 15:05 Rev Time 0.00
Received By lcrespo Date 2020-10-16 Time 15:05 Sent To  
Notes
2020-10-16 16:31:4910/16/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS BUILDING WAS ORIGINALLY BUILT AND DESIGNED
 UNDER THE FAIR HOUSING ACT GUIDELINES AS A B AND THE
 LEVEL OF ACCESSIBILITY CANNOT BE DECREASED. THE SHOWER
 CONTROL SHALL BE IN A WALL THAT CAN BE REACHED OF AN
 ENLARGED SHOWER PER 7B. THE PLANNED ALTERATIONS TO THE
 MASTER BATH DO NOT COMPLY WITH THE REQUIREMENTS OF THE
 FAIR HOUSING ACT GUIDELINES.
  
 2. A 30 INCH WIDE BY 48 INCHES DEEP CLEAR FLOOR SPACE
 IS REQUIRED ADJACENT TO THE SHOWER AND FLUSH WITH THE
 CONTROL WALL OF THE SHOWER PER FIGURE 7 (D) OF THE FAIR
 HOUSING ACT GUIDELINES REQUIREMENT # 7.
  
 3. PLEASE PROVIDE DETAILS FOR REINFORCEMENT FOR THE
 LATER INSTALLATION OF GRAB BARS IN THE SHOWER THAT IS
 REQUIRED PER THE FAIR HOUSING ACT REQUIREMENT # 6.
 SUBMIT AN ELEVATION DETAIL SHOWING THE LOCATION,
 LENGTH, WIDTH, AND TYPE OF REINFORCEMENT TO BE
 INSTALLED. REFER TO THE FAIR HOUSING ACT GUIDELINES
 FIGURE #5.
  
  
 4. PLEASE SHOW THE 30 INCHES WIDE MINIMUM BY 48 INCHES
 DEEP MINIMUM PARALLEL TO THE VANITY AND THE CLEAR FLOOR
 SPACE SHALL BE CENTERED ON THE COMPLIANT LAVATORY PER
 THE FHA GUIDELINES REQUIREMENT #7 (B) (V) AND FIGURE 37
 (C).
  
 5. THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT
 PROVIDES AN OPTION FOR THE CHANGING OF AN FHA
 COMPLIANCE STRUCTURE. THE OWNER AND DESIGNER OF RECORD
 ACKNOWLEDGE THAT THE PROPOSED BATHROOM DESIGN DOES NOT
 MEET THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES. THE OWNER AGREES TO REVERT THE UNIT TO
 COMPLIANCE AT THE TIME OF SALE IF SO, REQUESTED BY THE
 BUYER. THIS WILL BE IN A LETTER TYPE FORMAT SIGNED AND
 NOTARIZED BY THE OWNER. WE PROVIDE A SAMPLE LETTER AND
 IT MUST BE SUBMITTED TO THE BUILDING DEPARTMENT OF THE
 CITY OF WPB. IF THIS OPTION IS CHOSEN, PLEASE SEND AN
 EMAIL TO [email protected] AND I WILL SEND A COPY OF THE
 FAIR HOUSING AFFIDAVIT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-20 Cont ID  
Sent By tklarge Date 2020-08-20 Time 05:38 Rev Time 0.00
Received By tklarge Date 2020-08-19 Time 10:53 Sent To  
Notes
2020-08-19 14:01:401) THIS BUILDING WAS ORIGINALLY BUILT AND DESIGNED
 UNDER THE FAIR HOUSING ACT GUIDELINES AND THE LEVEL OF
 ACCESSIBILITY CANNOT BE DECREASED.THE PLANNED
 ALTERATIONS TO THE MASTER BATH DO NOT COMPLY WITH THE
 REQUIREMENTS OF THE FAIR HOUSING ACT GUIDELINES.
 2) A 30 INCH WIDE BY 48 INCH DEEP CLEAR FLOOR SPACE IS
 REQUIRED ADJACENT TO THE SHOWER AND FLUSH WITH THE
 CONTROL WALL OF THE SHOWER PER FIGURE 7 (D) OF THE FAIR
 HOUSING ACT GUIDELINES REQUIREMENT # 7.
 3) REINFORCEMENT FOR THE LATER INSTALLATION OF GRAB
 BARS IN THE SHOWER IS REQUIRED PER THE FAIR HOUSING ACT
 REQUIREMENT # 6. SUBMIT AN ELEVATION DETAIL SHOWING THE
 LOCATION, LENGTH, WIDTH AND TYPE OF REINFORCEMENT TO BE
 INSTALLED. REFER TO FAIR HOUSING ACT GUIDELINES FIGURE
 #5.
 4) THE HEIGHT OF THE VANITIES SHALL NOT EXCEED 34
 INCHES PER THE FAIR HOUSING ACT GUIDELINES REQUIREMENT
 #7 (B) (V). SHOW THIS ON THE FLOOR PLAN.
 5) VANITIES AND LAVATORIES SHALL BE INSTALLED WITH THE
 CENTERLINE OF THE FIXTURE A MINIMUM OF 1 FOOT 3 INCHES
 HORIZONTALLY FROM AN ADJOINING WALL OR FIXTURE PER THE
 FAIR HOUSING ACT GUIDELINES REQUIREMENT #7 (B) (V).
 6) IF KNEESPACE IS NOT PROVIDED BELOW THE VANITY A 30
 INCHES WIDE MINIMUM BY 48 INCHES DEEP MINIMUM SHALL BE
 PROVIDED PARALLEL TO THE VANITY AND THE CLEAR FLOOR
 SPACE SHALL BE CENTERED ON THE COMPLIANT LAVATORY. FHA
 GUIDELINES REQUIREMENT #7 (B) (V) AND FIGURE 37 (C).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-16 Cont ID  
Sent By pvalenti Date 2020-10-16 Time 15:49 Rev Time 0.00
Received By pvalenti Date 2020-10-16 Time 13:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-24 Cont ID  
Sent By pvalenti Date 2020-07-24 Time 12:12 Rev Time 0.00
Received By pvalenti Date 2020-07-24 Time 12:12 Sent To  
Notes
2020-07-24 12:16:24PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW DENIED:
  
 FS 471 AND FS 481, FAC 61G15-233.002; THE SIGNATURES ON
 SUBMITTED PAPER PLANS DO NOT APPEAR TO BE ORIGINALS.
 PLEASE PROVIDE ORIGINAL SIGNED SIGNATURES WITH SEAL.