Plan Review Details - Permit 20070753
Plan Review Stops For Permit 20070753
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-07-30 Cont ID  
Sent By lcrespo Date 2020-07-30 Time 09:55 Rev Time 0.00
Received By lcrespo Date 2020-07-30 Time 09:55 Sent To  
Notes
2020-07-30 09:56:3407/30/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-07-29 Cont ID  
Sent By lcrespo Date 2020-07-29 Time 15:07 Rev Time 0.00
Received By lcrespo Date 2020-07-29 Time 15:07 Sent To  
Notes
2020-07-29 15:18:4907/29/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FIREPLACE PER THE 2017 FBC FG SEC. 410.1.
 2. THE RANGE SPECS DID NOT LOAD CORRECTLY ON PROJECT
 DOCS, PLEASE RELOAD, I CANNOT SEE IT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 3. ON ISOMETRIC BTU'S LIST DOES NOT MATCH AMOUNT OF
 BTU?S, YOU DID NOT MULTIPLY THE TIKI TORCHES OR
 LANTERN, IE. YOU HAVE FIVE TIKI AT 22 BTU?S TIME 5
 SHOULD EQUAL 110, YOU PUT ONLY 22 BTU?S, YOUR TOTAL
 SHOULD BE 886 BTU?S AND YOU HAVE 791 TOTAL BTU?S,
 PLEASE CORRECT ON BOTH SHEET OF ISO PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By lcrespo Date 2020-07-28 Time 09:13 Rev Time 0.00
Received By lcrespo Date 2020-07-28 Time 07:42 Sent To  
Notes
2020-07-28 09:09:3207/28/20 1ST GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ALL COOPER LINE THAT ARE UNDERGROUND SHALL BE
 SLEEVED AND SHOWN ON ISOMETRIC PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 2. PLEASE PROVIDE LISTING RATINGS FOR TIKI TORCHES AND
 LANTERNS AS APPLIANCES SHALL BE LISTED AND LABELED PER
 THE 2017 FBC FG SECS. 402.2 AND 301.3.
  
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC FG SEC. 410.1.
  
 4. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 6. PLEASE PROVIDE A LAYOUT SHOWING THE LOCATION SHOWING
 THE LOCATION OF THE TANKLESS WATER HEATER AND THE
 LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS
 IN RELATION TO THE WATER HEATER AND ALL OTHER
 APPLIANCES, IF APPLICABLE SUBMIT A DETAIL SHOWING THE
 TYPE, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 THE 2017 FBC FG SECS. 502 THRU 505. (PRINT OUT THE
 LAYOUT OF THE BUILDING I AND SEND YOU A PDF FILE IF YOU
 LIKE, JUST EMAIL ME A REQUEST, THIS SHOULD ALSO SHOW
 DISTANCES FROM TIKI TORCH AND LANTERNS TO ANY
 COMBUSTION STRUCTURES, VEGETATION AND OR TREES).
  
 7. PLEASE SHOW AND LABEL DRIP LEG, UNIONS ON TANKLESS
 AND LABEL REGULATOR AND ON ISOMETRIC PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 8. THE OLD RANGE HAS A 50 BTU'S BUT THE NEW ONE HAS 150
 BTU'S SO' PLEASE PROVIDE NEW SPECS PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 9. ON ISOMETRIC PLEASE LABEL ALL BTU'S ON A LIST AND
 SHOW THEM BROKEN DOWN ON A SCHEDULE TYPE FORMAT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. PLEASE CLEAN UP ISOMETRIC SO IT
 IS LEGIBLE OUT IN FIELD AS IT IS CONGESTED WITH NUMBERS
 AND CONFUSING TO THE EYE, THANKS
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-30 Cont ID  
Sent By lcrespo Date 2020-07-30 Time 09:55 Rev Time 0.00
Received By lcrespo Date 2020-07-30 Time 09:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-29 Cont ID  
Sent By lcrespo Date 2020-07-29 Time 15:18 Rev Time 0.00
Received By lcrespo Date 2020-07-29 Time 13:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-28 Cont ID  
Sent By lcrespo Date 2020-07-28 Time 09:21 Rev Time 0.00
Received By lcrespo Date 2020-07-20 Time 16:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-07-29 Cont ID  
Sent By lcrespo Date 2020-07-29 Time 15:07 Rev Time 0.00
Received By lcrespo Date 2020-07-29 Time 15:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-30 Cont ID  
Sent By lcrespo Date 2020-07-28 Time 09:13 Rev Time 0.00
Received By lcrespo Date 2020-07-28 Time 07:57 Sent To  
Notes
2020-07-28 09:17:43HEATER MAY REQUIRE CONDENSATE LINE WHICH SHALL BE A
 MINIMUM 1' AWAY FROM BUILDING AND IF OUT OF A CONDITION
 SPACE IT SHALL HAVE A R-3 INSULATION ACCORDING TO THE
 ENERGY CODE 2017 FBC 4034.4.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-07-28 Cont ID  
Sent By lcrespo Date 2020-07-28 Time 09:22 Rev Time 0.00
Received By lcrespo Date 2020-07-28 Time 09:22 Sent To  
Notes
***NONE***