Plan Review Details - Permit 20070739
Plan Review Stops For Permit 20070739
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-08 Cont ID  
Sent By jwitmer Date 2020-11-08 Time 13:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-09-10 Cont ID  
Sent By jwitmer Date 2020-09-10 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2020-09-10 Time 08:58 Sent To  
Notes
2020-09-10 09:30:24WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20070739
 ADD: 8101 IBIS BLVD.
 CONT: MERCURIO CONSTRUCTION LLC
 TEL: 561-346-5147
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. SEPT. 10TH/ 2020
 ACTION: DENIED
  
 1) THE SUBMITTED INFORMATION IS MORE LIKE A
 INFORMATIONAL BROCHURE BUT DOES NOT PROVIDE CODE
 REQUIRED INFORMATION.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.3.5
 MINIMUM PLAN REVIEW CRITERIA
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING REVIEW
  
 MISSING CODE DATA:
 STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 DESIGN LOADS
 WIND REQUIREMENTS
 FOUNDATION
 ANCHORING OF THE COLUMNS TO THE FOUNDATION
 MECHANISMS ON TOP OF THE TOWERS, HOW ARE THEY ANCHORED
 TO THE COLUMNS FOR HIGH WIND EVENTS
 WILL THERE BE SOME TYPE OF MESH/ SCREEN AS IN A DRIVING
 RANGE, IF SO AT WHAT HEIGHT IS THE MESH AND AT WHAT
 HEIGHT IS THE POLE AS THEY ATTACH TO
 WILL THE SCREEN MESH HAVE TO BE DROPPED IN A HIGH WIND
 EVENT
  
 2) SINCE THE SCOPE OF WORK WILL DEAL WITH ELEMENTS THAT
 COULD BE OVERTURNED IN A HIGH WIND EVENT THE PLANS AND
 CALCULATIONS WOULD NEED TO BE DESIGNED BY A DESIGN
 PROFESSIONAL.
 107.1 GENERAL. . THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 REQUIRED BY THE BUILDING OFFICIAL, AND MAY REQUIRE ONLY
 ONE SET OF SUBMITTALS.
  
 3) NO TRANSMITTAL LETTER WHERE UPDATES TO THE PLANS
 WERE MADE. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-11 Cont ID  
Sent By jwitmer Date 2020-08-11 Time 09:46 Rev Time 0.00
Received By jwitmer Date 2020-08-11 Time 08:58 Sent To  
Notes
2020-08-11 09:38:41WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20070739
 ADD: 8101 IBIS BLVD.
 CONT: MERCURIO CONSTRUCTION LLC
 TEL: 561-346-5147
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. AUGUST 11TH/ 2020
 ACTION: DENIED
  
 1) THE SUBMITTED INFORMATION IS MORE LIKE A
 INFORMATIONAL BROCHURE BUT DOES NOT PROVIDE CODE
 REQUIRED INFORMATION.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.3.5
 MINIMUM PLAN REVIEW CRITERIA
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING REVIEW
  
 MISSING CODE DATA:
 SITE PLAN
 SET BACK / SEPARATION (ASSUMED PROPERTY LINES)
 OCCUPANCY GROUP
 MINIMUM TYPE OF CONSTRUCTION
  
 STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 DESIGN LOADS
 WIND REQUIREMENTS
 STRUCTURAL CALCULATIONS/ IF REQUIRED.
 FOUNDATION
 ANCHORING OF THE COLUMNS TO THE FOUNDATION
 MECHANISMS ON TOP OF THE TOWERS, HOW ARE THEY ANCHORED
 TO THE COLUMNS FOR HIGH WIND EVENTS
 WILL THERE BE SOME TYPE OF MESH/ SCREEN AS IN A DRIVING
 RANGE, IF SO AT WHAT HEIGHT IS THE MESH AND AT WHAT
 HEIGHT IS THE POLE AS THEY ATTACH TO
 WILL THE SCREEN MESH HAVE TO BE DROPPED IN A HIGH WIND
 EVENT
  
 2) SINCE THE SCOPE OF WORK WILL DEAL WITH ELEMENTS THAT
 COULD BE OVERTURNED IN A HIGH WIND EVENT THE PLANS AND
 CALCULATIONS WOULD NEED TO BE DESIGNED BY A DESIGN
 PROFESSIONAL.
 107.1 GENERAL. . THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 REQUIRED BY THE BUILDING OFFICIAL, AND MAY REQUIRE ONLY
 ONE SET OF SUBMITTALS.
  
 3) PLEASE NOTE BECAUSE OF THE COVID 19 PANDEMIC WE ARE
 ONLY ACCEPTING DIGITAL PLANS. PLAN REVIEWER ARE WORKING
 FROM HOME. PERMIT APPLICATIONS AND PAPER PLANS CAN BE
 DROPPED OFF AT THE BUILDING DEPARTMENT, THEN SCANNED IN
 TO THE PROGRAM PROJECT DOX, WHERE IN THE FUTURE YOU
 COULD UPLOAD PLANS.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-11-18 Cont ID  
Sent By jleahy Date 2020-11-18 Time 16:29 Rev Time 0.00
Received By jleahy Date 2020-11-18 Time 16:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-11 Cont ID  
Sent By jleahy Date 2020-09-11 Time 16:25 Rev Time 0.00
Received By jleahy Date 2020-09-11 Time 16:17 Sent To  
Notes
2020-09-11 16:26:46SEE FIRST SET OF COMMENTS JLEAHY
  
 NEED TO KNOW LOCATION OF SERVICE AND PANELBOARD THAT
 FEEDS THE TOWERS WIRE SIZES AND CIRCUIT SIZES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-18 Cont ID  
Sent By jleahy Date 2020-08-18 Time 13:14 Rev Time 0.00
Received By jleahy Date 2020-08-18 Time 13:08 Sent To  
Notes
2020-08-18 13:18:43FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED AN ELECTRICAL SITE LAYOUT, WHERE IS POWER COMING
 FROM WHAT SIZE CIRCUITS, CONDUIT RUNS TOWER TO TOWER OR
 ARE THEY ALL INDIVIDUAL CIRCUITS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-18 Cont ID  
Sent By jleahy Date 2020-11-18 Time 16:29 Rev Time 0.00
Received By jleahy Date 2020-11-05 Time 08:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-11 Cont ID  
Sent By lmarchan Date 2020-09-11 Time 16:34 Rev Time 0.00
Received By lmarchan Date 2020-09-01 Time 16:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-18 Cont ID  
Sent By jleahy Date 2020-08-18 Time 13:19 Rev Time 0.00
Received By jleahy Date 2020-07-29 Time 09:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-11-08 Cont ID  
Sent By jwitmer Date 2020-11-08 Time 13:59 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-09-11 Cont ID  
Sent By jleahy Date 2020-09-11 Time 16:28 Rev Time 0.00
Received By jleahy Date 2020-09-11 Time 16:28 Sent To  
Notes
2020-09-11 16:30:10SEE FIRST SET OF COMMENTS ALL PLANS SUBMITTED SHALL BE
 SIGNED PER CITY CODE. JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-08-18 Cont ID  
Sent By jleahy Date 2020-08-18 Time 13:18 Rev Time 0.00
Received By jleahy Date 2020-08-18 Time 13:18 Sent To  
Notes
2020-08-18 13:19:51ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLAN IS NOT DIGITALLY SIGNED BY THE DESIGNER OF
 RECORD
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
  

Review Stop Z ZONING
Rev No 3 Status P Date 2020-11-16 Cont ID  
Sent By llouie Date 2020-11-16 Time   Rev Time 0.00
Received By llouie Date 2020-11-16 Time   Sent To  
Notes
2020-11-16 08:50:41NO MINOR PD AMENDMENT PER AVANN, PLANNING AND ZONING
 ADMINISTRATOR.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-09-03 Cont ID  
Sent By llouie Date 2020-09-03 Time   Rev Time 0.00
Received By llouie Date 2020-09-03 Time   Sent To  
Notes
2020-09-03 11:48:54NO MINOR PD AMENDMENT REQUIRED PER AVANN, PLANNING AND
 ZONING ADMINISTRATOR.

Review Stop Z ZONING
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By llouie Date 2020-08-05 Time   Rev Time  
Received By llouie Date 2020-08-05 Time   Sent To  
Notes
2020-08-05 15:34:06** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE IN WRITING, WHAT THE PROPOSED TOWERS ARE
 FOR AND HOW MANY ARE PROPOSED IN THIS PERMIT
 APPLICATION.
  
 2.) AN UPDATED, SIGNED AND SEALED SURVEY OF THE
 PROPERTY IS REQUIRED.
  
 3.) A SITE PLAN SHOWING THE LOCATION FOR EACH OF THE
 PROPOSED TOWERS IS REQUIRED. INCLUDE SETBACK DIMENSIONS
 FROM STRUCTURE/CONCRETE PAD TO THE PROPERTY LINE(S).
  
 4.) SOME DETAILS OF THE TOWER (I.E. OVERALL HEIGHT, HOW
 BIG IS THE CONCRETE PAD, ETC.) IS MISSING.
  
 5.) A MINOR PD AMENDMENT, TO BE APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION IS
 REQUIRED PRIOR TO THE APPROVAL OF THIS PERMIT. PLEASE
 CONTACT STAFF FOR MORE INFORMATION.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: CS
  