Plan Review Details - Permit 20070690
Plan Review Stops For Permit 20070690
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-08-18 Cont ID  
Sent By cthroop Date 2020-08-18 Time 10:09 Rev Time 0.00
Received By cthroop Date 2020-08-18 Time 06:07 Sent To  
Notes
2020-08-18 10:10:52E-MAIL SENT TO CONTRACTOR TO DOWNLOAD THE NEW GENERAC
 SPECS. GEN. WEIGHT MUST MEET OR EXCEED PAD DESIGN
 MINIMUM WEIGHT. CT

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-17 Cont ID  
Sent By fgiaquin Date 2020-08-17 Time 21:59 Rev Time 0.00
Received By fgiaquin Date 2020-08-17 Time 20:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-10-19 Cont ID  
Sent By lcrespo Date 2020-10-19 Time 19:05 Rev Time 0.00
Received By lcrespo Date 2020-10-19 Time 19:05 Sent To  
Notes
2020-10-19 19:05:4210/19/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-08-04 Cont ID  
Sent By lcrespo Date 2020-08-04 Time 17:28 Rev Time 0.00
Received By lcrespo Date 2020-08-04 Time 17:28 Sent To  
Notes
2020-08-04 17:29:3908/04/20 1ST GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS A RECORD OF EXISTING
 GAS OF 687 BTU'S. ON THE ISOMETRIC THAT WAS SUBMITTED
 THIS TOTAL SHOULD BE ADDED ON AND VERIFIED BY GAS
 CONTRACTOR. THE BTU LOAD OF THE EXISTING GAS SYSTEM
 MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. YOU HAVE SUBMITTED A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE BUT THEY ARE INCORRECT, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE TO THAT RUN, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION PER THE 2017 FBC RES. SECS. G2412.4,
 G2412.8, G2413.1, G2413.2, G2413.3.
  
 2. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2.
  
 4. MINIMUM AND MAXIMUM BTU LOADS DOES NOT MATCH THE
 SPECS ON ISOMETRIC, PLEASE CHANGE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. SUBMIT MANUFACTURER'S SPECIFICATION FOR FLEXIBLE
 HOSE TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC.
 G2408.1.
  
 NOTE: THE CITY OF WEST PALM BEACH MAY PROVIDE AN
 ISOMETRIC OF EXISTING GAS AT A NOMINAL FEE, PLEASE
 EMAIL CRAIG MCPHERSON AT [email protected] OR CALL
 561-805-6684.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-19 Cont ID  
Sent By lcrespo Date 2020-10-19 Time 19:05 Rev Time 0.00
Received By lcrespo Date 2020-10-13 Time 13:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-18 Cont ID  
Sent By cthroop Date 2020-08-18 Time 10:09 Rev Time 0.00
Received By cthroop Date 2020-07-27 Time 13:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-19 Cont ID  
Sent By lcrespo Date 2020-10-19 Time 19:04 Rev Time 0.00
Received By lcrespo Date 2020-10-19 Time 19:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-08-04 Cont ID  
Sent By lcrespo Date 2020-08-04 Time 17:28 Rev Time 0.00
Received By lcrespo Date 2020-08-04 Time 17:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-18 Cont ID  
Sent By cthroop Date 2020-08-18 Time 10:04 Rev Time 0.00
Received By cthroop Date 2020-08-18 Time 06:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-07-31 Cont ID  
Sent By rthermid Date 2020-07-31 Time P Rev Time  
Received By rthermid Date 2020-07-31 Time   Sent To I
Notes
***NONE***