Plan Review Details - Permit 20070500
Plan Review Stops For Permit 20070500
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-08-28 Cont ID  
Sent By jleahy Date 2020-08-28 Time 12:06 Rev Time 0.00
Received By jleahy Date 2020-08-28 Time 12:06 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-08-26 Cont ID  
Sent By jwitmer Date 2020-08-26 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2020-08-26 Time 09:47 Sent To  
Notes
2020-08-26 09:59:06TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS' IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-08-26 Cont ID  
Sent By jwitmer Date 2020-08-26 Time 11:05 Rev Time 0.00
Received By jwitmer Date 2020-08-26 Time 09:47 Sent To  
Notes
2020-08-26 11:05:06 
  
 WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20070500
 ADD: 205 N DIXIE HWY.
 CONT: THE WEITZ CO.
 TEL: 954-662-5887
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 26TH/2020
 ACTION: BUILDING PROVISO/ DEFERRED SUBMITTALS
  
 1) BUILDING PROVISO/ DEFERRED SUBMITAL:
 SHEET AE-105 JUDGE'S BENCH RAISED ACCESS FLOOR SYSTEM.
 SHOP DRAWINGS FOR RAISED ACCESS FLOOR SYSTEM DESIGN TO
 BE SUBMITTED TO THE DESIGNER OF RECORD FOR APPROVAL AND
 SHOP DRAWING STAMP OF APPROVAL BEFORE BEING SUBMITTED
 TO THE BUILDING DEPARTMENT FOR REVIEW. BLDG. PLAN
 REVIEW J. WITMER 8/26TH/ 2020
  
 2) BUILDING PROVISO/ DEFERRED SUBMITTAL:
 SHEET AE-106 DETAILS 8, 9 & 10 RAMP DESIGN TO
 MAGISTRATE BENCH.
 SHOP DRAWINGS FOR RAMP DESIGN TO MAGISTRATE BENCH TO BE
 SUBMITTED TO THE DESIGNER OF RECORD FOR APPROVAL AND
 SHOP DRAWING STAMP OF APPROVAL BEFORE BEING SUBMITTED
 TO THE BUILDING DEPARTMENT FOR REVIEW.
  
 BLDG. PLAN REVIEW J. WITMER 8/26TH/ 2020

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-29 Cont ID  
Sent By fgiaquin Date 2020-08-29 Time 23:43 Rev Time 0.00
Received By fgiaquin Date 2020-08-29 Time 22:22 Sent To  
Notes
2020-08-29 22:37:59ELECTRICAL REVIEW STATUS: PASS, SEE COMMENTS BELOW.
  
 1. NO FIRE ALARM HAS BEEN REVIEWED OR APPROVED. FIRE
 ALARM IS TO BE SUBMITTED AS ITS OWN STAND-ALONE PERMIT
 WITH SEPARATE DRAWINGS. FBC 107.2.1 FBC 105.1.
  
 2. LOW VOLTAGE, CAMERAS, SECURITY, ACCESS CONTROL ARE
 ALL REQUIRED TO BE SEPARATE PERMITS. A LOW VOLTAGE
 REVIEW STOP HAS BEEN ADDED AND SEPARATE LOW VOLTAGE
 COMMENTS WILL BE LISTED THERE. FBC 107.2.1 FBC 105.1
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status F Date 2021-01-19 Cont ID  
Sent By fgiaquin Date 2020-08-29 Time 23:43 Rev Time 0.00
Received By fgiaquin Date 2020-08-29 Time 23:31 Sent To  
Notes
2020-08-29 23:43:42FOR DEFERRED SUBMITTALS
  
 1. PROVIDE SPECS FOR PRODUCT APPROVAL OF ALL LOW
 VOLTAGE DEVICES, CAMERAS, PANIC BUTTONS, ETC. FBC
 107.2.1 NEC 110.2 110.3B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-07-31 Cont ID  
Sent By pleduc Date 2020-07-31 Time   Rev Time 0.00
Received By pleduc Date 2020-07-31 Time 10:44 Sent To  
Notes
2020-07-31 13:16:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-29 Cont ID  
Sent By fgiaquin Date 2020-08-29 Time 23:44 Rev Time 0.00
Received By fgiaquin Date 2020-07-28 Time 10:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-08-20 Cont ID  
Sent By hmoser Date 2020-08-20 Time 13:11 Rev Time 0.00
Received By hmoser Date 2020-08-20 Time 08:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-08-20 Cont ID  
Sent By tklarge Date 2020-08-20 Time 05:51 Rev Time 0.00
Received By tklarge Date 2020-08-20 Time 05:42 Sent To  
Notes
2020-08-20 05:51:45THERE ARE NO CHANGES BEING MADE TO THE PLUMBING
 SYSTEMS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-26 Cont ID  
Sent By jwitmer Date 2020-08-26 Time 11:06 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***