Plan Review Stops For Permit 20070500 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
P |
Date |
2020-08-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-08-28 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-08-28 |
Time |
12:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2020-08-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2020-08-26 |
Time |
09:59 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2020-08-26 |
Time |
09:47 |
Sent To |
|
|
Notes |
2020-08-26 09:59:06 | TO THE BUILDING CONTRACTOR: | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | THE PERMIT NUMBER AND "ASBESTOS' IN THE SUBJECT LINE. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2020-08-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2020-08-26 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2020-08-26 |
Time |
09:47 |
Sent To |
|
|
Notes |
2020-08-26 11:05:06 | | | | | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | SERVICES/ BUILDING DIVISION | | 2017 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 20070500 | | ADD: 205 N DIXIE HWY. | | CONT: THE WEITZ CO. | | TEL: 954-662-5887 | | E-MAIL: [email protected] | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: WED. AUGUST 26TH/2020 | | ACTION: BUILDING PROVISO/ DEFERRED SUBMITTALS | | | | 1) BUILDING PROVISO/ DEFERRED SUBMITAL: | | SHEET AE-105 JUDGE'S BENCH RAISED ACCESS FLOOR SYSTEM. | | SHOP DRAWINGS FOR RAISED ACCESS FLOOR SYSTEM DESIGN TO | | BE SUBMITTED TO THE DESIGNER OF RECORD FOR APPROVAL AND | | SHOP DRAWING STAMP OF APPROVAL BEFORE BEING SUBMITTED | | TO THE BUILDING DEPARTMENT FOR REVIEW. BLDG. PLAN | | REVIEW J. WITMER 8/26TH/ 2020 | | | | 2) BUILDING PROVISO/ DEFERRED SUBMITTAL: | | SHEET AE-106 DETAILS 8, 9 & 10 RAMP DESIGN TO | | MAGISTRATE BENCH. | | SHOP DRAWINGS FOR RAMP DESIGN TO MAGISTRATE BENCH TO BE | | SUBMITTED TO THE DESIGNER OF RECORD FOR APPROVAL AND | | SHOP DRAWING STAMP OF APPROVAL BEFORE BEING SUBMITTED | | TO THE BUILDING DEPARTMENT FOR REVIEW. | | | | BLDG. PLAN REVIEW J. WITMER 8/26TH/ 2020 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2020-08-29 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-08-29 |
Time |
23:43 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-08-29 |
Time |
22:22 |
Sent To |
|
|
Notes |
2020-08-29 22:37:59 | ELECTRICAL REVIEW STATUS: PASS, SEE COMMENTS BELOW. | | | | 1. NO FIRE ALARM HAS BEEN REVIEWED OR APPROVED. FIRE | | ALARM IS TO BE SUBMITTED AS ITS OWN STAND-ALONE PERMIT | | WITH SEPARATE DRAWINGS. FBC 107.2.1 FBC 105.1. | | | | 2. LOW VOLTAGE, CAMERAS, SECURITY, ACCESS CONTROL ARE | | ALL REQUIRED TO BE SEPARATE PERMITS. A LOW VOLTAGE | | REVIEW STOP HAS BEEN ADDED AND SEPARATE LOW VOLTAGE | | COMMENTS WILL BE LISTED THERE. FBC 107.2.1 FBC 105.1 | | | | | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
Rev No |
1 |
Status |
F |
Date |
2021-01-19 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-08-29 |
Time |
23:43 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-08-29 |
Time |
23:31 |
Sent To |
|
|
Notes |
2020-08-29 23:43:42 | FOR DEFERRED SUBMITTALS | | | | 1. PROVIDE SPECS FOR PRODUCT APPROVAL OF ALL LOW | | VOLTAGE DEVICES, CAMERAS, PANIC BUTTONS, ETC. FBC | | 107.2.1 NEC 110.2 110.3B | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2020-07-31 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-07-31 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-07-31 |
Time |
10:44 |
Sent To |
|
|
Notes |
2020-07-31 13:16:31 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER | | SEPARATE PERMITS AND SHOP DRAWINGS. | | | | 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | PETER LEDUC | | FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-08-29 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-08-29 |
Time |
23:44 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-07-28 |
Time |
10:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2020-08-20 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2020-08-20 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2020-08-20 |
Time |
08:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2020-08-20 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-08-20 |
Time |
05:51 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-08-20 |
Time |
05:42 |
Sent To |
|
|
Notes |
2020-08-20 05:51:45 | THERE ARE NO CHANGES BEING MADE TO THE PLUMBING | | SYSTEMS. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2020-08-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2020-08-26 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|