Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-26 Cont ID  
Sent By rmcphers Date 2020-08-26 Time 14:32 Rev Time 0.00
Received By rmcphers Date 2020-08-26 Time 14:32 Sent To  
Notes
2020-08-26 14:33:20DRAWING SHOWS CHARGING STATIONS IN THE SERVICE AREA NOT
 THE CUSTOMER PARKING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-30 Cont ID  
Sent By rmcphers Date 2020-07-30 Time 12:04 Rev Time 0.00
Received By rmcphers Date 2020-07-30 Time 12:04 Sent To  
Notes
2020-07-30 12:13:53CAR CHARGING STATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A PARKING LOT LAYOUT SHOWING THE USE
 OF THE PARKING SPACES WHERE THE CHARGING STATIONS ARE
 BEING INSTALLED (CUSTOMER, EMPLOYEE OR SALES USE)
  
 FYI = IF CUSTOMER OR EMPLOYEE PARKING = YOU ARE ADDING
 AN "ELEMENT" (CHARGING STATION) TO THE PARKING FACILITY
 WHICH YOU WILL NEED TO PROVIDE AN ACCESSIBLE ROUTE,
 CLEAR FLOOR SPACE AND REACH RANGES TO COMPLY WITH 2017
 FBC ACCESSIBILITY - SEE CODE SECTIONS BELOW.
  
 106.1 ELEMENT. AN ARCHITECTURAL OR MECHANICAL COMPONENT
 OF A BUILDING, FACILITY, SPACE, OR SITE.
  
 201.4SCOPE OF COVERAGE.
 THIS CODE APPLIES TO FIXED OR BUILT-IN ELEMENTS OF
 BUILDINGS, STRUCTURES, SITE IMPROVEMENTS AND PEDESTRIAN
 ROUTES OR VEHICULAR WAYS LOCATED ON A SITE. UNLESS
 SPECIFICALLY STATED OTHERWISE, ADVISORY NOTES, APPENDIX
 NOTES AND FIGURES CONTAINED IN THE CODE EXPLAIN OR
 ILLUSTRATE THE REQUIREMENTS; THEY DO NOT ESTABLISH
 ENFORCEABLE REQUIREMENTS.
  
 202.3ALTERATIONS.
 WHERE EXISTING ELEMENTS OR SPACES OR COMMON AREAS ARE
 ALTERED, EACH ALTERED ELEMENT, SPACE OR AREA SHALL
 COMPLY WITH THE APPLICABLE REQUIREMENTS OF CHAPTER 2
 AND SECTION 201.1.1. SEE SECTION 208.1 FOR EXISTING
 PARKING.
  
 206.2.2WITHIN A SITE.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE
 BUILDINGS, ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS,
 AND ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
  
 228 DEPOSITORIES, VENDING MACHINES, CHANGE MACHINES,
 MAIL BOXES, AND FUEL DISPENSERS
 228.1 GENERAL.
 WHERE PROVIDED, AT LEAST ONE OF EACH TYPE OF
 DEPOSITORY, VENDING MACHINE, CHANGE MACHINE, AND FUEL
 DISPENSER SHALL COMPLY WITH 309.
  
 309 OPERABLE PARTS
  
 309.1GENERAL.
 OPERABLE PARTS SHALL COMPLY WITH 309.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-22 Cont ID  
Sent By jleahy Date 2020-08-22 Time 14:35 Rev Time 0.00
Received By jleahy Date 2020-08-22 Time 14:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-30 Cont ID  
Sent By jleahy Date 2020-07-30 Time 12:44 Rev Time 0.00
Received By jleahy Date 2020-07-30 Time 12:43 Sent To  
Notes
2020-07-30 12:45:48ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) COST OF THE CHARGER HAS TO BE INCLUDED IN THE VALUE
 OF THE PERMIT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-26 Cont ID  
Sent By rmcphers Date 2020-08-26 Time 14:33 Rev Time 0.00
Received By rmcphers Date 2020-08-20 Time 11:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-30 Cont ID  
Sent By jleahy Date 2020-07-30 Time 12:45 Rev Time 0.00
Received By jleahy Date 2020-07-20 Time 17:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-26 Cont ID  
Sent By rmcphers Date 2020-08-26 Time 14:33 Rev Time 0.00
Received By rmcphers Date 2020-08-26 Time 14:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-30 Cont ID  
Sent By rmcphers Date 2020-07-30 Time 12:21 Rev Time 0.00
Received By rmcphers Date 2020-07-30 Time 12:21 Sent To  
Notes
***NONE***