Plan Review Stops For Permit 20070480 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2020-09-01 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-09-01 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-09-01 |
Time |
10:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-08-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-08-21 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-08-21 |
Time |
15:29 |
Sent To |
|
|
Notes |
2020-08-21 15:31:10 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC R 301, THE ENGINEERING FOR THE DIVERSITECH PAD | | REQUIRES THAT WIND LOADS BE DETERMINED BY OTHERS; THIS | | WAS NOT PROVIDED. PROVIDE WIND LOADS AS PER NOTE ON THE | | ENGINEERING. | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-08-01 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-08-01 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-08-01 |
Time |
11:39 |
Sent To |
|
|
Notes |
2020-08-01 11:50:29 | PLAN REVIEW GENERATOR - BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | PROVIDE STRUCTURAL DETAIL OF GENERATOR PAD | | | | 1) STRUCTURAL DETAIL OF THE PRE-CAST GENERATOR PAD | | SHALL HAVE A VALID DIGITAL SIGNATURE OF THE DESIGN | | PROFESSIONAL PER FS 471 & FAC 61G15. | | | | 2) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR WITH A | | VALID DIGITAL SIGNATURE OF THE DESIGNER AS REQUIRED FOR | | THE GENERATOR PAD ENGINEERING PER FBC 107.3.5.3 AND | | R301.2. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2020-08-01 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-08-01 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-08-01 |
Time |
11:39 |
Sent To |
|
|
Notes |
2020-08-01 11:49:17 | PROVISO: PROVIDE ATS SPEC'S TO CITY INSPECTOR. CT |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2020-08-01 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-08-01 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-08-01 |
Time |
11:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-09-01 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-09-01 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-08-27 |
Time |
15:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-08-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-08-21 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-08-17 |
Time |
07:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-08-13 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-08-13 |
Time |
09:21 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-07-22 |
Time |
14:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2020-08-01 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-08-01 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-08-01 |
Time |
11:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2020-09-09 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-09-09 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-09-09 |
Time |
16:39 |
Sent To |
|
|
Notes |
2020-09-09 16:40:26 | ORIGINAL SIGNATURE SLAB PLAN WAS SUBMITTED ON 7/24 | | JLEAHY |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2020-09-01 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-09-01 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-09-01 |
Time |
10:12 |
Sent To |
|
|
Notes |
2020-09-01 10:37:20 | PLAN REVIEW - SIGNATURES | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 3RD REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | RE: GENERATOR PAD SPECS. | | | | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | ORIGINALS. A SCAN OF A WET SIGNATURE IS NOT CONSIDERED | | A DIGITAL SIGNATURE. | | | | EITHER UPLOAD A DIGITALLY SIGNED DOCUMENT OR DROP OFF | | (OR MAIL) ONE PAPER ORIGINAL: | | | | BUILDING DIVISION, FIRST FLOOR | | CITY OF WEST PALM BEACH | | 401 CLEMATIS ST | | WEST PALM BEACH, FL 33401 | | | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2020-08-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-08-21 |
Time |
15:31 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-08-21 |
Time |
15:31 |
Sent To |
|
|
Notes |
2020-08-21 15:31:55 | ORIGINAL ENGINEERING WAS SUBMITTED, BUT IT APPEARS THAT | | ADDITIONAL ENGINEERING WILL BE FORTHCOMING |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-08-01 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-08-01 |
Time |
11:50 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-08-04 |
Time |
07:18 |
Sent To |
|
|
Notes |
2020-08-04 07:21:59 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | SIGNATURE REVIEW DENIED AS WINDLOAD PAGE IS MISSING | | (SEE PRESSURE DESIGN NOTE OF CONCRETE PAD PAGE). | | ORIGINAL SIGNATURES ARE ON THE SUBMITTED CONCRETE PAD | | PAGE. | | | | | 2020-08-01 11:51:09 | PLAN REVIEW GENERATOR - DIGITAL SIGNATURES AND SEALS | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1) DESIGN PROFESSIONALS DIGITAL SIGNATURE IS REQUIRED | | ON ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC | | 61G15 | | | | 2) DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH | | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE | | NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | 3) UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | 4) FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY | | DIGITAL SIGATURES AND SEALS PER FS 668.003. | | | | NOTE: YOU MAY PROVIDE A PAPER PLAN WITH WET SIGNATURE | | AND SEAL PRIOR TO PERMIT. | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2020-08-12 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2020-08-12 |
Time |
23:58 |
Rev Time |
0.00 |
Received By |
kalexand |
Date |
2020-08-12 |
Time |
23:58 |
Sent To |
I |
|
Notes |
|
|