Plan Review Details - Permit 20070442
Plan Review Stops For Permit 20070442 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2020-09-02 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-09-02 |
Time |
20:26 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-09-02 |
Time |
20:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2020-08-05 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-08-05 |
Time |
21:48 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-08-05 |
Time |
21:37 |
Sent To |
|
|
Notes |
2020-08-05 21:48:28 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. SAME AS PREVIOUS REVIEW | | | | CAMERAS AND RECORDER DO NOT APPEAR TO BE LISTED ON CUT | | SHEETS PROVIDED. NEC 110.2, 110.3B FBC 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-07-23 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-07-23 |
Time |
21:34 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-07-23 |
Time |
21:00 |
Sent To |
|
|
Notes |
2020-07-23 21:33:16 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. CAMERAS AND RECORDER DO NOT APPEAR TO BE LISTED ON | | CUT SHEETS PROVIDED. NEC 110.2, 110.3B FBC 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-09-02 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-09-02 |
Time |
20:26 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-08-24 |
Time |
15:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-08-05 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-08-05 |
Time |
21:48 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-07-24 |
Time |
10:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-07-23 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-07-23 |
Time |
21:34 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-07-10 |
Time |
15:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2020-09-02 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-09-02 |
Time |
20:26 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-09-02 |
Time |
20:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2020-08-05 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-08-05 |
Time |
21:48 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-08-05 |
Time |
21:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2020-07-23 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-07-23 |
Time |
21:34 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-07-23 |
Time |
21:34 |
Sent To |
|
|
Notes |
|
|
|