Plan Review Details - Permit 20070393
Plan Review Stops For Permit 20070393
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-23 Cont ID  
Sent By rmcphers Date 2020-07-23 Time 11:05 Rev Time 0.00
Received By rmcphers Date 2020-07-23 Time 11:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-15 Cont ID  
Sent By rmcphers Date 2020-07-15 Time 10:42 Rev Time 0.00
Received By rmcphers Date 2020-07-15 Time 10:42 Sent To  
Notes
2020-07-15 10:43:55ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A DRAWING THAT SHOWS THE ROOFING
 LAYOUT, MEAN ROOF HEIGHT, ROOF SLOPE, SIZE OF ROOF ETC.
 2) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE
 CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT
 APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND SEALED
 ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR
 ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A
 HIGHER WIND PRESSURE - SEE NOTES ON THE PRODUCT
 APPROVAL.
 3) PLEASE PROVIDE THE FRONT PAGES FOR THE FLAT DECK
 FLORIDA (FL) ROOFING PRODUCT APPROVAL PROVIDED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-23 Cont ID  
Sent By rmcphers Date 2020-07-23 Time 11:06 Rev Time 0.00
Received By rmcphers Date 2020-07-16 Time 10:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-15 Cont ID  
Sent By rmcphers Date 2020-07-15 Time 10:46 Rev Time 0.00
Received By rmcphers Date 2020-07-09 Time 08:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-07-23 Cont ID  
Sent By rmcphers Date 2020-07-23 Time 11:05 Rev Time 0.00
Received By rmcphers Date 2020-07-23 Time 11:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-15 Cont ID  
Sent By rmcphers Date 2020-07-15 Time 10:44 Rev Time 0.00
Received By rmcphers Date 2020-07-15 Time 10:44 Sent To  
Notes
2020-07-15 10:45:31IF SIGNED AND SEALED ADDITIONAL ATTACHMENT ENGINEERING
 IS REQUIRED = SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE
 ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC PLAN
 REVIEW. DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS
 MAY TAKE 2 TO 3 WEEKS TO PROCESS - DUE TO LIMITED STAFF
 INSIDE THE BUILDING DEPT.)