Plan Review Details - Permit 20070360
Plan Review Stops For Permit 20070360
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-21 Cont ID  
Sent By shill Date 2020-08-21 Time 10:05 Rev Time 0.00
Received By shill Date 2020-08-21 Time 09:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-08-11 Cont ID  
Sent By cthroop Date 2020-08-11 Time 12:58 Rev Time 0.00
Received By cthroop Date 2020-08-11 Time 09:50 Sent To  
Notes
2020-08-11 13:04:19PLAN REVIEW GENERATOR - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR PER FBC
 107.3.5.3 AND R301.2 AS REQUIRED FOR THE GENERATOR PAD
 ENGINEERING.
 THE DESIGN PRESSURES PROVIDED ARE THE MAX. ALLOWABLE
 PRESSURES FOR THE GENERATOR PAD. PLEASE REFERENCE THE
 ALLOWABLE DESIGN PRESSURE NOTE. A DESIGN PROFESSIONAL
 SHALL PROVIDE DESIGN WIND LOAD CALCULATIONS FOR THE
 SITE. THE PRESSURES PROVIDED FOR THE GENERATOR PAD MUST
 MEET OR EXCEED THESE WIND LOAD PRESSURES.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
  
 2) STRUCTURAL DETAIL OF PAD AND DESIGN LOADS SHALL BE
 SIGNED AND SEALED BY A DESIGN PROFESSIONAL.
 SEE COMMENTS UNDER SIGNATURE REVIEW.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By cthroop Date 2020-07-28 Time 14:39 Rev Time 0.00
Received By cthroop Date 2020-07-28 Time 11:36 Sent To  
Notes
2020-07-28 14:40:38PLAN REVIEW GENERATOR - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR PER FBC
 107.3.5.3 AND R301.2 AS REQUIRED FOR THE GENERATOR PAD
 ENGINEERING.
 2) STRUCTURAL DETAIL OF PAD AND DESIGN LOADS SHALL BE
 SIGNED AND SEALED BY A DESIGN PROFESSIONAL.
 3) PROVIDE STRUCTURAL DETAIL OF GENERATOR PAD.
 4) PROVIDE A SITE PLAN. SHOW LOCATION OF PROPOSED
 GENERATOR.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-11 Cont ID  
Sent By cthroop Date 2020-08-11 Time 10:23 Rev Time 0.00
Received By cthroop Date 2020-08-11 Time 09:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By cthroop Date 2020-07-28 Time 14:41 Rev Time 0.00
Received By cthroop Date 2020-07-28 Time 11:36 Sent To  
Notes
2020-07-28 14:43:45PLAN REVIEW GENERATOR - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER
 SWITCH. ? ATS
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2) ELECTRICAL RISER
 PROVIDE CONDUCTOR SIZE AND TYPE OF CONTROL CIRCUIT
 WIRING. 215.5; WPB FBC 107.2.1
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-08-11 Cont ID  
Sent By cthroop Date 2020-08-11 Time 10:31 Rev Time 0.00
Received By cthroop Date 2020-08-11 Time 09:50 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By jesmith Date 2020-07-28 Time 14:36 Rev Time 0.00
Received By jesmith Date 2020-07-28 Time 14:36 Sent To  
Notes
2020-07-28 14:36:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20070360 313 N LAKESIDE CT
  
  
 1ST REVIEW
 GAS COMMENTS: DENIED
 1. AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE GAS/PLUMBING
 PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR
 THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION
 NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR
 LICENSED IN THAT TRADE.
 2. PER WPB FBC 107.1, ALL PLANS TO BE SIGNED AND SEALED
 BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS. AS
 DESIGNER DOES NOT PROVIDE DIGITAL SIGNATURE IN
 ACCORDANCE WITH FAC AND FS, THEN THE DESIGNER SHALL
 PROVIDE PROPERLY SIGNED/SEALED PAPER DOCUMENT IN
 ACCORDANCE WITH FAC AND FS PRIOR TO PERMIT ISSUANCE.
 CALL 561-805-6724 FOR ADDITIONAL INFORMATION.
 3. PER FBC FC 409.2, EVERY METER SHALL BE EQUIPPED WITH
 A SHUTOFF VALVE LOCATED ON THE SUPPLY SIDE OF THE
 METER.
 4. PER WPB FBC 107.2.1, PROVIDE DOCUMENTATION THAT
 REGULATOR IS APPROVED FOR EXTERIOR APPLICATION.
 5. SITE SURVEY SHOWING LOCATIONS OF GAS METER AND
 GENERATOR IS NOT LEGIBLE. PER WPB FBC 107.2.1, SUBMIT A
 LEGIBLE DRAWING/SURVEY, CLEARLY SHOWING THE SHOWING
 LOCATIONS OF GAS METER AND GENERATOR.
 6. PER WPB FBC 107.2.1, SUBMIT THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 ALL PLANS TO BE SIGNED/ SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS. PLEASE SEE COMMENTS #1 AND #2
 ABOVE.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20070360 313 N LAKESIDE CT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-21 Cont ID  
Sent By shill Date 2020-08-21 Time 10:06 Rev Time 0.00
Received By shill Date 2020-08-11 Time 15:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-11 Cont ID  
Sent By cthroop Date 2020-08-11 Time 13:11 Rev Time 0.00
Received By cthroop Date 2020-08-10 Time 09:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-10 Cont ID  
Sent By ccarvaja Date 2020-08-10 Time 08:37 Rev Time 0.00
Received By ccarvaja Date 2020-07-09 Time 10:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-08-11 Cont ID  
Sent By cthroop Date 2020-08-11 Time 10:23 Rev Time 0.00
Received By cthroop Date 2020-08-11 Time 09:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-28 Cont ID  
Sent By cthroop Date 2020-07-28 Time 14:39 Rev Time 0.00
Received By cthroop Date 2020-07-28 Time 11:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-21 Cont ID  
Sent By shill Date 2020-08-21 Time 10:05 Rev Time 0.00
Received By shill Date 2020-08-21 Time 10:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-11 Cont ID  
Sent By cthroop Date 2020-08-11 Time 13:04 Rev Time 0.00
Received By cthroop Date 2020-08-11 Time 09:50 Sent To  
Notes
2020-08-11 13:11:14PLAN REVIEW GENERATOR - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) A DESIGN PROFESSIONAL SHALL REVIEW AND APPROVE THE
 GENERATOR PAD STRUCTURAL DESIGN. PROVIDE WIND LOAD
 DESIGN PRESSURES FOR THE GENERATOR REVIEWED AND
 APPROVED BY A DESIGN PROFESSIONAL.
  
 2) DIGITAL SIGNATURES/SEALS SHALL BE IN ACCORDANCE
 WITH FS 471, FS 481 AS NOTED.
  
 3) UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
 4) FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
 OPTION
  
 YOU MAY ELECT TO PROVIDE A HARD COPY OF PLANS WITH WET
 SEAL AND SIGNATURE OF DESIGN PROFESSIONAL PRIOR TO
 PERMIT. A DROP BOX HAS BEEN INSTALLED OUTSIDE CITY HALL
 FOR THIS PURPOSE. CONTACT THE OFFICE OF DEVELOPMENT
 SERVICES @ 561-805-8700 OR [email protected] TO STATE YOUR
 INTENTIONS. CITY STAFF WILL REVIEW YOUR DOCUMENTS AND
 IF APPROVED YOU WILL RECIEVE AN E-MAIL INSTRUCTING YOU
 TO DOWNLOAD AND PRINT YOUR PERMIT AND PLANS.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By cthroop Date 2020-07-28 Time 14:40 Rev Time 0.00
Received By cthroop Date 2020-07-28 Time 11:36 Sent To  
Notes
2020-07-28 14:41:19PLAN REVIEW GENERATOR - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15
  
 2) DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 3) UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
 4) FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
 NOTE: YOU MAY PROVIDE A PAPER PLAN WITH WET SIGNATURE
 AND SEAL PRIOR TO PERMIT.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-08-07 Cont ID  
Sent By kalexand Date 2020-08-07 Time 10:17 Rev Time 0.00
Received By kalexand Date 2020-08-07 Time 10:17 Sent To I
Notes
***NONE***