2020-07-23 13:28:53 | 1) SHEET AE-310 DEATIL #1 - THERE IS A NOTE THAT REFERS |
| TO SHT. AE-330, DETAIL #9 FOR A ROOF DRAIN DETAIL. |
| THERE IS NO SHEET AE- 330 IN THESE PLANS. CLARIFY. |
| 2) SHT.AE- 323 - SUBMIT A SECTION DETAIL OF THE |
| EXFILTRATION TRENCH SHOWN AT THE BASE OF THE FOOTERS. |
| WPB AMEND. TO FBC SEC. 107.2.1. |
| 3) SHT. P-11 - THE SANITARY DRAIN LINE FROM THE BAR |
| AREA SHALL DISCHARGE TO THE GREASE INTERCEPTOR |
| FBC-PLUMBING SEC.1003.3.1. |
| 4) SHT. M-8 - WORK NOTE #3 REFERS TO THE CONDENSATE |
| DRAIN ROUTED TO NEAREST PLUMBING BOX. CONDENSATE IS NOT |
| PERMITTED TO DISCHARGE INTO THE CITY'S SANITARY SYSTEM |
| PER CITY ORDINANCE CHAPTER 90, ARTICLE III, SEC.90-126 |
| (B)(5). |
| 5) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE |
| FOLLOWING ITEMS: HOT FOOD WELL, STEAMER, FOOD DIGESTER, |
| SODA AND WATER DISPENSER,COFFEE BREWER, ICED TEA |
| BREWER, ICED TEA BREWER, COFFEE MAKER, & WATER FILTER. |
| THE TYPE OF BACKFLOW DEVICE SHALL COMPLY WITH |
| FBC-PLUMBING TABLE 608.1 FOR THE SPECIFIC APPLICATION. |
| 6) SUBMIT SPECIFICATIONS/DETAILS ON THE TYPE OF GREASE |
| INTERCEPTOR TO BE INSTALLED. IF AN EXISTING INTERCEPTOR |
| IS BEING USED, SUBMIT VERIFICATION THAT THE EXISTING |
| UNIT HAS THE CAPACITY FOR THE ADDITIONAL LOAD. |
| 7) SHT. P-9 - GREASE INTERCEPTOR SIZING TABLE - IN THE |
| ROW FOR 4 INCH PIPE, WHERE DID THE 150 GPM COME FROM? |
| ALSO, WHERE DID THE COEFFICIENT OF 0.0455 COME FROM? I |
| COULD NOT FIND EITHER OF THOSE ITEMS IN THE SIZING |
| STANDARD PDI- G101. |
| 8) SHT. P-10 - WORK NOTE #1 REFERS TO SHT. P-7. THE IS |
| NO SUCH SHEET IN THIS SUBMITTAL. CLARIFY. |
| 9) SHT. P-10 - SIZE THE MAIN BRANCH LINES ON THE WATER |
| RISER. WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| 10) HOSE BIBBS SHALL BE EQUIPPED WITH SEPARATE SHUTOFF |
| VALVES. FBC-PLUMBING SEC.606.2 (2). |
| 11) SHT. P-10 - SHOW THE SIZE OF EACH WATER LINE AT THE |
| MANIFOLD. WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| 12) SHOW THE TANKLESS WATER HEATER ON THE WATER RISER |
| AND ALSO ON THE PLAN VIEW. |
| 13) SUBMIT WATER AND SANITARY RISERS FOR THE NEW TOILET |
| ROOMS AND OTHER PLUMBING ON THE LOWER AND UPPER LEVELS. |
| WPB AMEND. TO FBC SEC. 107.2.1. |
| 14) IS THERE A SUMP PUMP BEING INSTALLED IN THE |
| ELEVATOR PIT? IF SO, SUBMIT PIPING ISOMETRIC. SHOW |
| COMPLIANCE WITH FBC-PLUMBING SECS.301.6, 1003.4. |
| 15) SHT.P-9 - THE VENTED CLEANOUT ADJACENT TO FIXTURE |
| PK 6 DOES NOT COMPLY WITH THE PLUMBING CODE AND CREATES |
| A FLAT, DRY VENT. EVERY DRY VENT CONNECTING TO A |
| HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF |
| THE HORIZONTAL DRAIN PIPE. FBC-PLUMBIBNG SEC.905.3. |
| 16) SHT. P-9 - THE VENTED CLEANOUT FOR THE FLOOR SINKS |
| FOR FIXTURES PK 42 & PK44 DOES NOT COMPLY WITH THE |
| PLUMBING CODE AND CREATES A FLAT, DRY VENT. EVERY DRY |
| VENT CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT |
| ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. |
| FBC-PLUMBIBNG SEC.905.3. THIS ALSO OCCURS AT THE VENTED |
| WALL CLEANOUT BY FIXTURE PK1. |
| 17) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| FOLLOWING EQUIPMENT: STEAMER, FOOD DIGESTOR, AND |
| DISHMACHINE. WPB AMEND. TO FBC SEC. 107.2.1. |
| 18) THE SINK IN COPY ROOM E129 MAY BE REQUIRED TO |
| COMPLY WITH THE FBC-ACCESSIBIRITY SECS.212.3, 606. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |