Plan Review Details - Permit 20070229
Plan Review Stops For Permit 20070229
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-19 Cont ID  
Sent By rmcphers Date 2020-08-19 Time 14:58 Rev Time 0.00
Received By rmcphers Date 2020-08-19 Time 14:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-15 Cont ID  
Sent By rmcphers Date 2020-07-15 Time 09:06 Rev Time 0.00
Received By rmcphers Date 2020-07-15 Time 08:55 Sent To  
Notes
2020-07-15 09:03:18WINDOWS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) BUILDING APPEARS TO BE A 4 STORY CONDO BUILDING -
 PLEASE SHOW THE CORRECT MEAN ROOF HEIGHT.
 2) PLEASE PROVIDE SIGNED AND SEALED WIND DESIGN
 PRESSURES FROM AN ARCHITECT OR ENGINEER SHOWING THE
 WIND DESIGN CRITERIA FBC 1609
 3) PLEASE SHOW ON A FLOOR PLAN THE LOCATION OF THE UNIT
 WITHIN THE BUILDING FOOT PRINT- REQUIRED TO DETERMINE
 IF IN WIND ZONE 4 OR 5
 4) IF THIS IS AN END UNIT PLEASE SHOW THE DISTANCE FROM
 THE CORNER OF THE BUILDING TO THE EDGE OF THE WINDOWS
 ON THE CORNERS OF THE BUILDING - REQUIRED TO DETERMINE
 IF IN WIND ZONE 4 OR 5.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-19 Cont ID  
Sent By rmcphers Date 2020-08-19 Time 14:58 Rev Time 0.00
Received By rmcphers Date 2020-08-04 Time 13:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-15 Cont ID  
Sent By rmcphers Date 2020-07-15 Time 09:07 Rev Time 0.00
Received By rmcphers Date 2020-07-07 Time 09:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-19 Cont ID  
Sent By rmcphers Date 2020-08-19 Time 14:58 Rev Time 0.00
Received By rmcphers Date 2020-08-19 Time 14:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-15 Cont ID  
Sent By rmcphers Date 2020-07-15 Time 09:07 Rev Time 0.00
Received By rmcphers Date 2020-07-15 Time 09:06 Sent To  
Notes
2020-07-15 09:07:24SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS
 MAY TAKE 2 TO 3 WEEKS TO PROCESS - DUE TO LIMITED STAFF
 INSIDE THE BUILDING DEPT.)