Plan Review Details - Permit 20070076
Plan Review Stops For Permit 20070076
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-02-11 Cont ID  
Sent By rmcphers Date 2021-02-11 Time 14:21 Rev Time 0.00
Received By rmcphers Date 2021-02-11 Time 14:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-01-08 Cont ID  
Sent By rmcphers Date 2021-01-08 Time 14:15 Rev Time 0.00
Received By rmcphers Date 2021-01-08 Time 14:15 Sent To  
Notes
2021-01-08 14:16:18WALL SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE SIGNED AND SEALED ATTACHMENT DETAILS
 FROM AN ARCHITECT OR ENGINEER TO COMPLY WITH THE WIND
 LOADS FBC 1609 - PLEASE SHOW THE WIND DESIGN CRITERIA
 USED FOR DESIGN FBC 1603.1
 (SIGNED AND SEALED DRAWING HAS BEEN VERSIONED OVER IN
 PROJECTDOX)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-07-23 Cont ID  
Sent By rmcphers Date 2020-07-23 Time 08:50 Rev Time 0.00
Received By rmcphers Date 2020-07-23 Time 08:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-02-03 Cont ID  
Sent By fgiaquin Date 2021-02-03 Time 21:52 Rev Time 0.00
Received By fgiaquin Date 2021-02-03 Time 21:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-01-11 Cont ID  
Sent By fgiaquin Date 2021-01-11 Time 20:59 Rev Time 0.00
Received By fgiaquin Date 2021-01-11 Time 20:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-23 Cont ID  
Sent By fgiaquin Date 2020-07-23 Time 20:59 Rev Time 0.00
Received By fgiaquin Date 2020-07-23 Time 20:08 Sent To  
Notes
2020-07-23 20:59:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOW VOLTAGE SHOWN IN SAME JBOX AS HIGH VOLTAGE. NEC
 725.136B
  
 2. DISCONNECT MUST BE WITHIN SIGHT OF SIGN. NEC 600.6A1
  
 3. REFERENCE PERMIT NUMBER OF ELECTRICAL PERMIT FOR
 "PRIMARY ELECTRIC DONE BY OTHERS". FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-11 Cont ID  
Sent By rmcphers Date 2021-02-11 Time 14:22 Rev Time 0.00
Received By rmcphers Date 2021-01-25 Time 15:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-11 Cont ID  
Sent By fgiaquin Date 2021-01-11 Time 21:01 Rev Time 0.00
Received By fgiaquin Date 2020-12-31 Time 11:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-30 Cont ID  
Sent By ccarvaja Date 2020-07-30 Time 18:03 Rev Time 0.00
Received By ccarvaja Date 2020-07-02 Time 10:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-02-11 Cont ID  
Sent By rmcphers Date 2021-02-11 Time 14:21 Rev Time 0.00
Received By rmcphers Date 2021-02-11 Time 14:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-01-08 Cont ID  
Sent By rmcphers Date 2021-01-08 Time 14:16 Rev Time 0.00
Received By rmcphers Date 2021-01-08 Time 14:16 Sent To  
Notes
2021-01-08 14:16:48SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-23 Cont ID  
Sent By rmcphers Date 2020-07-23 Time 08:50 Rev Time 0.00
Received By rmcphers Date 2020-07-23 Time 08:50 Sent To  
Notes
2020-07-23 08:52:23SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED.

Review Stop Z ZONING
Rev No 3 Status P Date 2021-02-08 Cont ID  
Sent By eschneid Date 2021-02-08 Time 16:03 Rev Time 0.25
Received By eschneid Date 2021-02-08 Time 15:41 Sent To  
Notes
2021-02-08 16:15:33PERMITTED: 72 SF
 PROPOSED: 6.7 SF
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-01-11 Cont ID  
Sent By eschneid Date 2021-01-11 Time 09:54 Rev Time 0.25
Received By eschneid Date 2021-01-11 Time 09:54 Sent To  
Notes
2021-01-11 09:55:53FAILED
  
 FACADE IDENTITY SIGN
  
 1) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA PERMIT A MAXIMUM LETTER HEIGHT OF 18 INCHES
 FOR A FASCIA IDENTITY SIGN UNLESS CITYPLACE RETAIL IS
 GRANTED A WAIVER II (MINOR PLANNED DEVELOPMENT
 AMENDMENT) BY THE CITY TO INCREASE THE DIMENSION OF THE
 SIGN. THE SUBMITTED WAIVER I CANNOT BE USED TO INCREASE
 THE LETTER DIMENSIONS IN EXCESS OF 18 INCHES IN HEIGHT.
 IF APPROVED, THE WAIVER II MAY INCREASE THE SIGNS
 DIMENSION BY UP TO 25 PERCENT, SO THE LETTER HEIGHT
 COULD THEN BE 22 INCHES TALL AS SHOWN.
  
 2) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA PERMIT A FASCIA IDENTITY SIGNS TO HAVE A
 MAXIMUM HEIGHT OF 16 FEET FROM FINISHED GRADE. PROVIDE
 THE DIMENSION LINE TO VERIFY COMPLIANCE. NOTE: ADDING
 THE PROVIDED DIMENSIONS SHOWS THAT IT EXCEEDS THE
 PERMITTED 16 FEET.
  
 3) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT REVERSE CHANNEL LETTERS ARE
 FABRICATED OUT OF ALUMINUM WITH A MINIMUM METAL
 THICKNESS OF .060 INCHES. PROVIDE THE INFORMATION TO
 VERIFY THIS REQUIREMENT ON THE PLANS.
  
 4) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THE STUD MOUNTS TO BE SERIES 316
 STAINLESS STEEL ANCHOR BOLTS. PROVIDE VERIFICATION OF
 THIS REQUIREMENT ON THE PLANS.
  
 5) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THE SPACERS FOR THE STUD MOUNTS TO BE
 PAINTED THE COLOR OF THE WALL. PROVIDE VERIFICATION OF
 THIS REQUIREMENT ON THE PLANS.
  
 6) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRES THAT ALL CONDUIT, JUNCTION BOXES,
 TRANSFORMERS AND OTHER NECESSARY EQUIPMENT IS CONCEALED
 AND NOT VISIBLE TO THE PUBLIC. PROVIDE VERIFICATION
 THAT THE POWER SUPPLY BOX AND ITS RELATED COMPONENTS
 MEET THIS REQUIREMENT. IT APPEARS THEY ARE MOUNTED TO
 THE INSIDE OF THE WALL AND VISIBLE TO THE PUBLIC ACCESS
 EASEMENT WITHIN THE PEDESTRIAN ARCADE.
  
 PERMITTED: 72
 PROPOSED: 8.63 SF
  
 STAFF HAS NOTED THAT THE SIGN IS ALREADY INSTALLED, SO
 THE PENALTY FEE FOR INSTALLING THE SIGN WITHOUT A
 PERMIT HAS BEEN ADDED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-07-30 Cont ID  
Sent By eschneid Date 2020-07-30 Time 15:15 Rev Time 0.25
Received By eschneid Date 2020-07-30 Time 15:15 Sent To  
Notes
2020-07-30 15:17:46FAILED
  
 1) THE ROSEMARY SQUARE TENANT SIGN CRITERIA ONLY PERMIT
 FASCIA IDENTITY SIGNS IF CITYPLACE RETAIL, LLC, HAS
 PROVIDED WRITTEN WAIVER I APPROVAL WITH THE PERMITS
 SUBMITTAL.
  
 2) THE ROSEMARY SQUARE TENANT SIGN CRITERIA PERMIT A
 MAXIMUM LETTER HEIGHT OF 18 INCHES FOR A FASCIA
 IDENTITY SIGN UNLESS CITYPLACE RETAIL IS GRANTED A
 WAIVER II (MINOR PLANNED DEVELOPMENT AMENDMENT) BY THE
 CITY. THE WAIVER II MAY INCREASE THE SIGNS DIMENSION BY
 UP TO 25 PERCENT, SO THE LETTER HEIGHT COULD THEN BE 22
 INCHES TALL AS SHOWN.
  
 3) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT SIGNS ARE MOUNTED WITHIN THE LEASE LINES. PROVIDE
 VERIFICATION THAT THE SIGN LOCATION ABOVE THE
 PEDESTRIAN ARCADE IS WITHIN THE BRIO LEASE LINES. THE
 DIMENSION LINE FOR BRIO IS SHOWN PAST THE WALL OF THE
 STOREFRONT AND INCLUDING THE ARCADE. UNLESS THE LEASE
 LINE IS SHOWN INCLUDING THE AREA COVERED BY THE ARCADE,
 THE DIMENSION LINE NEEDS TO BE REDUCED TO SHOW ONLY THE
 LEASE AREA (NOT THE ARCADE).
  
 3) THE CURRENT ROSEMARY SQUARE TENANT SIGN CRITERIA
 REQUIRE THAT FASCIA IDENTITY SIGNS ARE LOCATED ABOVE OR
 ADJACENT TO ENTRIES OR STOREFRONTS ONLY. THE PROPOSED
 SIGN IS LOCATED OVER THE PEDESTRIAN ARCADE. IF THIS
 AREA IS WITHIN THE LEASE LINE (SEE COMMENT #3) THEN
 CITYPLACE RETAIL, LLC, MAY GRANT A WAIVER I (WRITTEN
 APPROVAL) TO PERMIT THE ALTERNATE PLACEMENT OF THE SIGN
 NOT ABOVE OR ADJACENT TO ENTRIES OR STOREFRONT.
  
 4) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT FASCIA IDENTITY SIGNS MAY NOT EXCEED 40% OF THE
 WIDTH OF THE AVAILABLE AREA, WHICH IS BETWEEN THE TWO
 COLUMNS. PROVIDE THE DIMENSIONS TO VERIFY COMPLIANCE.
  
 5) THE ROSEMARY SQUARE TENANT SIGN CRITERIA PERMIT A
 FASCIA IDENTITY SIGNS TO HAVE A MAXIMUM HEIGHT OF 16
 FEET FROM FINISHED GRADE. PROVIDE THE DIMENSION LINE TO
 VERIFY COMPLIANCE. NOTE: ADDING THE PROVIDED DIMENSIONS
 SHOWS THAT IT EXCEEDS 16 FEET.
  
 6) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT REVERSE CHANNEL LETTERS ARE FABRICATED OUT OF
 ALUMINUM WITH A MINIMUM METAL THICKNESS OF .060 INCHES.
 PROVIDE THE INFORMATION TO VERIFY THIS REQUIREMENT ON
 THE PLANS.
  
 7) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE THE
 STUD MOUNTS TO BE SERIES 316 STAINLESS STEEL ANCHOR
 BOLTS. PROVIDE VERIFICATION OF THIS REQUIREMENT ON THE
 PLANS.
  
 8) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE THE
 SPACERS FOR THE STUD MOUNTS TO BE PAINTED THE COLOR OF
 THE WALL. PROVIDE VERIFICATION OF THIS REQUIREMENT ON
 THE PLANS.
  
 9) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRES
 THAT ALL CONDUIT, JUNCTION BOXES, TRANSFORMERS AND
 OTHER NECESSARY EQUIPMENT IS CONCEALED AND NOT VISIBLE
 TO THE PUBLIC. PROVIDE VERIFICATION THAT THE POWER
 SUPPLY BOX AND ITS RELATED COMPONENTS MEET THIS
 REQUIREMENT. IT APPEARS THEY ARE MOUNTED TO THE INSIDE
 OF THE WALL AND VISIBLE TO THE PEDESTRIAN ARCADE.
  
 PERMITTED: UNKNOWN
 PROPOSED: 8.63 SF
  
 STAFF HAS NOTED THAT THE SIGN IS ALREADY INSTALLED, SO
 THE PENALTY FEE FOR INSTALLING THE SIGN WITHOUT A
 PERMIT HAS BEEN ADDED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  