2020-07-13 15:21:47 | 1ST REVIEW FBC-2017 RES. |
| PERMIT-20070034 |
| 7/13/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE GAS ISOMETRIC DRAWING IS INCOMPLETE: |
| A) MODIFY THE DRAWING TO SHOW THE ENTIRE PIPING SYSTEM |
| INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST |
| REMOTE OUTLET. THE TOTAL BTUH LOAD OF THE SYSTEM, AND |
| THE INDIVIDUAL APPLIANCE LOADS SHALL BE SHOWN ON THE |
| DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES. |
| B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM |
| FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH |
| LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 & |
| G2413.4.3. INDICATE THE TYPES AND SIZES OF PIPING IN |
| THE SYSTEM, LOCATIONS OF REGULATORS, AND GAS PRESSURES |
| AT THE REGULATORS- SECTION G2421.1 FBC RES. |
| C) THE GAS PIPE SIZING TABLE 402.4(3) FBC FG INDICATED |
| ON THE DRAWING IS IS FOR COMMERCIAL USE, IT IS NOT |
| FOUND IN THE FBC RES. WHICH IS THE GOVERNING CODE FOR |
| THE PROJECT..THE TABLE IS TYPICALLY USED WHEN THE |
| MINIMUM STATIC GAS PRESSURE IS 8 IN. W.C OR GREATER. |
| THE CALCULATED DROPPED PRESSURE (THE STATIC PRESSURE |
| MINUS THE 3.0 IN. PRESSURE DROP), MUST BE GREATER THAN |
| THE HIGHEST MINIMUM GAS PRESSURE REQUIRED BY ANY OF THE |
| GAS APPLIANCES ON THE SYSTEM. PLEASE REFER TO TABLE |
| G2413.4(1) FBC RES. (402.4(2) FBC FUEL GAS) WHICH IS |
| THE TYPICAL LOW PRESSURE SIZING TABLE USED FOR |
| HOUSEHOLD APPLIANCES. |
| D) INDICATE REQUIRED CLEARANCES FOR THE WATER HEATER TO |
| OPERABLE OPENINGS OR AIR VENTS INTO THE BUILDING, FROM |
| GRADE AND FROM ANY STRUCTURES ABOVE SUCH AS A SOFFIT- |
| G2448.1 FBC RES. PLEASE NOTE THAT MANUFACTURER?S |
| SPECIFICATIONS AND INSTALLATION MANUAL SHALL BE ONSITE |
| AT TIME OF INSPECTION. |
| |
| 2) THE SIGNATURE OF THE CONTRACTOR OR QUALIFIER SHALL |
| BE ON THE DRAWING PER SECTION 107.2.1 WPB: ALL |
| INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |