Plan Review Details - Permit 20061445
Plan Review Stops For Permit 20061445
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2020-07-05 Cont ID  
Sent By jwitmer Date 2020-07-05 Time 16:55 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-07-05 16:38:04NEW BUILDING, NO ASBESTOS. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-14 Cont ID  
Sent By jwitmer Date 2020-08-14 Time 08:27 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-05 Cont ID  
Sent By jwitmer Date 2020-07-05 Time 16:58 Rev Time 0.00
Received By jwitmer Date 2020-07-05 Time 16:36 Sent To  
Notes
2020-07-05 16:54:52WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061445
 ADD: 701 S. OLIVE AVE. # 728
 CONT: EXCEL TILE
 TEL: 561-818-1955
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. JULY 05/2020
 ACTION: DENIED
  
 1) THE PROPOSED WORK INDICATES NEW FLOOR TILE IN THE
 GUEST BATHROOM. NO MENTION OF THE REQUIRED FLOOR
 INSULATION. SHOW COMPLIANCE WITH:
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING
 COMPLIANCE WITH:
  
 TYPE I AND II BUILDINGS
 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2)PLEASE PROVIDE WHAT TYPE OF WALLBOARD IS GOING TO BE
 INSTALLED IN THE SHOWER LOCATION. 2017 FBC-B 2509.2
 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALLS AND CEILING PANELS IN
 SHOWER AREAS SHALL BE OF MATERIALS LISTED IN TABLE
 2509.2 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER?S
 RECOMMENDATIONS. WATER RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C840 AND THE MANUFACTURE?S
 RECOMMENDATIONS.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2020-07-21 Cont ID  
Sent By jleahy Date 2020-07-21 Time 10:22 Rev Time 0.00
Received By jleahy Date 2020-07-21 Time 10:20 Sent To  
Notes
2020-07-21 10:22:45NOTE STATE NO ELECTRICAL WORK TO BE DONE JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2020-08-14 Cont ID  
Sent By jwitmer Date 2020-08-14 Time 08:26 Rev Time 0.00
Received By jwitmer Date 2020-08-05 Time 16:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-21 Cont ID  
Sent By jleahy Date 2020-07-21 Time 10:22 Rev Time 0.00
Received By jleahy Date 2020-06-30 Time 13:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-08-07 Cont ID  
Sent By ccole Date 2020-08-07 Time 12:46 Rev Time 0.00
Received By ccole Date 2020-08-07 Time 11:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-16 Cont ID  
Sent By ccole Date 2020-07-16 Time 15:36 Rev Time 0.00
Received By ccole Date 2020-07-16 Time 15:36 Sent To  
Notes
2020-07-16 16:25:231ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20061445
 7/16/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 107.2.1 WPB AND PROVIDE PLUMBING
 PLANS:
 A) SHOW THE EXISTING AND REMODELED BATHROOM FLOOR
 PLANS.
 B) PROVIDE A SANITARY ISOMETRIC DRAWING.
 C) PROVIDE A SHOWER PAN DETAIL.
  
 2) FAIR HOUSING ACCESSIBILITY GUIDELINES: BECAUSE THE
 BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH THE
 ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT AND
 THE DESIGN GUIDELINES FOR USABLE BATHROOMS IN DWELLING
 UNITS, THE ALTERATIONS THAT ARE PROPOSED IN THE
 BATHROOMS SHALL ALSO BE IN COMPLIANCE WITH THE FAIR
 HOUSING ACT. THE FAIR HOUSING ACCESSIBILITY GUIDELINES
 ARE INCLUDED IN THE FLORIDA ACCESSIBILITY CODE- 2017
 SIXTH EDITION. COMPLIANCE WITH THE GUIDELINES REQUIRES
 THAT CLEAR FLOOR SPACES FOR WHEELCHAIR APPROACHES TO
 BATH FIXTURES SHALL EITHER BE MAINTAINED AS ORIGINALLY
 DESIGNED OR PROVIDED WHERE NEW FIXTURES ARE BEING
 INSTALLED. SUBMITTED DOCUMENTS INDICATE REPLACEMENT OF
 FIXTURES IN THE GUEST BATHROOM. PLEASE NOTE THAT A
 GUEST BEDROOM IS NOT SHOWN ON THE SUBMITTED FLOOR PLAN.
 BASED ON THE DRAWING IT IS NOT CLEAR IF USABLE BATHROOM
 TYPE A OR B WAS CHOSEN AS THE ORIGINAL DESIGN. THE
 DESIGNER OF RECORD MUST INDICATE WHICH TYPE DESIGN WAS
 USED ON THE PLAN, AND THEN PROVIDE ENLARGED DIMENSIONED
 DRAWINGS OF THE REMODELED BATHROOM WITH CLEAR FLOOR
 SPACE DIAGRAMS CONFIGURED FOR THE NEW AND REPLACED
 FIXTURES. PLEASE SEE REQUIREMENT 7 CONTAINED IN THE
 GUIDELINES AND FIGURES 3- 7 FOR GUIDANCE. CONCERNING
 THE SHOWER, GRAB BAR AND WALL HUNG BENCH SEAT
 REINFORCEMENTS SHALL BE INSTALLED IN THE SHOWER WALLS
 TO ACCOMMODATE FUTURE INSTALLATIONS. PLEASE PROVIDE
 DIMENSIONED ELEVATION VIEWS SHOWING THE LOCATIONS OF
 THE WALL REINFORCEMENTS.
 1A) AS AN ALTERNATIVE TO MEETING THE GUIDELINES FOR THE
 BATH ALTERATIONS, THE OWNER AND DESIGNER OF RECORD FOR
 THE PROPOSED PROJECT MAY PROVIDE A SIGNED AND NOTARIZED
 AFFIDAVIT WHICH WOULD INDICATE ACKNOWLEDGEMENT THAT THE
 PROPOSED DESIGN DOES NOT MEET THE REQUIREMENTS OF THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES, BUT WILL ALSO
 REQUIRE THE OWNER TO AGREE TO REVERT THE UNIT BACK TO
 COMPLIANCE AT TIME OF SALE IF SO REQUESTED BY THE
 BUYER. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL
 TO [email protected] AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT. IF CHOOSING THIS OPTION IT WOULD BE
 ADVISABLE AT A MINIMUM TO INSTALL THE SHOWER WALL
 REINFORCEMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-07 Cont ID  
Sent By ccole Date 2020-08-07 Time 12:48 Rev Time 0.00
Received By ccole Date 2020-08-07 Time 12:48 Sent To  
Notes
2020-08-07 12:49:08CONTRACTOR OR RECORD HAS PREPARED AND SIGNED THE
 DRAWINGS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-16 Cont ID  
Sent By ccole Date 2020-07-16 Time 16:26 Rev Time 0.00
Received By ccole Date 2020-07-16 Time 16:26 Sent To  
Notes
2020-07-16 16:27:11THE CONTRACTOR HAS PLACED HIS SIGNATURE ON A COPY OF AN
 ARCHITECT'S COPYWRITTEN PLAN.
 THE CONTRACTOR MUST PROVIDE HIS OWN DESIGNED AND SIGNED
 PLAN, OR THE ARCHITECT SHALL PROVIDE AN ELECTRONIC
 SIGNATURE AND SEAL ON THE DRAWING- SECTION 107.2.1 WPB,
 FL STATUTE 481.221 AND SECTION 61G1-16.005 FLORIDA
 ADMINISTRATIVE CODE.