Plan Review Details - Permit 20061341
Plan Review Stops For Permit 20061341
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-02 Cont ID  
Sent By jwitmer Date 2020-09-02 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2020-09-02 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By jwitmer Date 2020-07-28 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2020-07-28 Time 08:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-03 Cont ID  
Sent By jleahy Date 2020-08-03 Time 07:23 Rev Time 0.00
Received By jleahy Date 2020-08-03 Time 07:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-08-26 Cont ID  
Sent By pleduc Date 2020-08-26 Time   Rev Time 0.00
Received By pleduc Date 2020-08-26 Time 15:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-07-22 Cont ID  
Sent By pleduc Date 2020-07-22 Time   Rev Time 0.00
Received By pleduc Date 2020-07-22 Time 10:42 Sent To  
Notes
2020-07-22 10:48:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE DOES NOT APPEAR TO BE A SITE PLAN THAT CLEARLY
 LOCATES THE PROPOSED TRAILER.
  
 PLEASE PROVIDE AN ACCURATE SITE PLAN INCLUDING ALL
 APPLICABLE DIMENSIONS TO PROPERTY LINES, BUILDING, OR
 OTHER IMPORTANT SITE FEATURES.
  
  
  
 2) THE APPLICATION STATES INSTALL TEMPORARY TRAILER;
 HOWEVER, THE ATTACHED FOUNDATION PLAN APPEARS TO
 INDICATE 4 TRAILERS ATTACHED TO EACH OTHER.
  
 ADDITIONALLY, THE PREVIOUSLY APPROVED AND ATTACHED FIRE
 SPRINKLER PERMIT AND THE ELECTRICAL SHOP DRAWINGS
 INDICATE ONLY ONE TRALIER.
  
 PLEASE PROVIDE DETAILED CLARIFICATIONS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-09-02 Time 07:15 Rev Time 0.00
Received By lmarchan Date 2020-08-25 Time 16:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-05 Cont ID  
Sent By lmarchan Date 2020-08-05 Time 08:35 Rev Time 0.00
Received By lmarchan Date 2020-07-20 Time 09:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-07-31 Cont ID  
Sent By hmoser Date 2020-07-31 Time 13:22 Rev Time 0.00
Received By hmoser Date 2020-07-31 Time 13:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-08-26 Cont ID  
Sent By lcrespo Date 2020-08-26 Time 16:04 Rev Time 0.00
Received By lcrespo Date 2020-08-26 Time 15:47 Sent To  
Notes
2020-08-26 16:07:30BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST PALM
 BEACH ORD #2853-95. A PERMIT REQUIRED BY A LICENSED
 CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES PRIOR TO
 FINAL INSPECTION. PLEASE CONTACT THE CITY OF WPB
 UTILITIES AT 561-822-2240 FOR FURTHER DIRECTIONS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By ccole Date 2020-07-31 Time 13:40 Rev Time 0.00
Received By ccole Date 2020-07-31 Time 12:55 Sent To  
Notes
2020-07-31 13:45:501ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20061341
 7/31/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REVIEW THE FIRE DEPT. REVIEW NOTES- NO SITE
 PLAN OR UTILITY PLANS HAVE BEEN SUBMITTED. PLEASE NOTE
 THAT SEPARATE PERMITS WILL BE REQUIRED FOR THE
 UNDERGROUND FIRE LINE AND FOR THE FIRE SERVICE BACKFLOW
 PREVENTER- SECTIONS 105.1 & 107.1 WPB.
  
 2) PROVIDE A SITE PLAN AND A PLUMBING PLAN SHOWING THE
 WATER SERVICE AND SANITARY DRAINAGE SYSTEMS FOR THE
 PROPOSED TRAILER. PROVIDE DETAILS INCLUDING:
  
 A) POTABLE WATER SERVICE PIPE RUN FROM POINT OF
 CONNECTION AT THE CITY MAIN TO THE TEMPORARY TRAILER.
  
 B) TYPE, SIZE AND BURIAL DEPTH OF WATER SERVICE PIPE-
 SECTIONS 602.1, 602.2, 603.1 AND TABLE 605.3 FBC P.
  
 C) BACKFLOW PREVENTER LOCATION AND TYPE TO BE
 INSTALLED. PLEASE NOTE THAT THE BACKFLOW PREVENTER
 SHALL BE INSTALLED UNDER A SEPARATE PERMIT- 608.1.
 A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC,
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 D) LOCATION AND TYPE OF MAIN SHUTOFF VALVE- 606.1.
  
 E) SANITARY SEWER LINE RUN FROM THE TRAILER TO THE
 POINT OF CONNECTION TO THE CITY SEWER LINE- 701.3.
  
 F) TYPE, SIZE, BURIAL DEPTH OF THE SANITARY SEWER PIPE
 AND LOCATIONS OF CLEANOUTS- TABLE 702.3. AND SECTIONS
 708.1.2 & 708.1.3.
  
 3) PLEASE NOTE IF HOLDING TANKS ARE TO BE INSTALLED FOR
 SANITY SEWER IN LIEU OF CONNECTING TO THE CITY SEWER,
 PLEASE SHOW THEIR LOCATIONS AND SIZES ON THE PLAN AND
 ALL PIPING RUNS. SUBMIT A COPY OF THE CONTRACT FOR THE
 TANKS THAT INCLUDES THE PUMP-OUT SCHEDULE- SECTION
 108.1 WPB.
  
 PLEASE NOTE ADDITIONAL INFORMATION FOR PERMITTING MAY
 BE REQUIRED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 IF YOU HAVE QUESTIONS OR REQUIRE MORE INFORMATION
 PLEASE CONTACT ME OR CHIEF PLUMBING INSPECTOR TIMOTHY
 LARGE- [email protected] (561)-805-6692.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-02 Cont ID  
Sent By jwitmer Date 2020-09-02 Time 07:16 Rev Time 0.00
Received By jwitmer Date 2020-09-02 Time 07:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-13 Cont ID  
Sent By medwards Date 2020-08-13 Time 13:40 Rev Time 0.00
Received By medwards Date 2020-08-13 Time 13:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-08-27 Cont ID  
Sent By llouie Date 2020-08-27 Time   Rev Time 0.00
Received By llouie Date 2020-08-27 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By llouie Date 2020-08-05 Time   Rev Time  
Received By llouie Date 2020-08-05 Time   Sent To  
Notes
2020-08-05 08:25:05** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY IS
 REQUIRED (NOT PROVIDED).
  
 2.) SITE PLAN SHOWING THE LOCATION OF THE TRAILER AND
 SETBACK DISTANCE FROM THE PROPERTY LINES IS REQUIRED
 (NOT PROVIDED).
  
 3.) PLEASE CLARIFY THE PURPOSE OF INSTALLING THE
 TEMPORARY TRAILER AND HOW LONG IT IS EXPECTED TO REMAIN
 ON THE PROPERTY.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: CS
  