Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-12-22 Cont ID  
Sent By RGATHRIG Date 2020-12-22 Time 16:13 Rev Time 0.00
Received By rgathrig Date 2020-12-22 Time 16:12 Sent To  
Notes
2020-12-22 16:13:44PASSED WITH THE FINAL APPROVAL OF THE CONDITIONS IN THE
 FIELD MAY VARY DO TO CONSTRUCTION NEEDS AT THE TIME
  
 RICHARD GATHRIGHT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-10-29 Cont ID  
Sent By RGATHRIG Date 2020-10-29 Time 17:49 Rev Time 0.00
Received By rgathrig Date 2020-10-29 Time 17:46 Sent To  
Notes
2020-10-29 17:49:36THIS PLAN REVIEW FOR PHASED OCCUPANCY IS FAILED BY
 RICHARD GATHRIGHT, ASSISTANT BUILDING OFFICIAL, WITH
 THE FOLLOWING COMMENTS.
  
 1. COMMENTS FROM THE FIRST REVIEW WERE NOT ADDRESSED.
  
 2. A NARRATIVE WAS REQUESTED SO YOUR THOUGHT OF THE
 PHASING COULD BE UNDERSTOOD.
  
 3. IT APPEARS THAT YOU HAVE CREATED A DEAD END IN
 CORRIDOR C102 BY STAIR 4 BY INSTALLING THE TEMPORARY
 DOOR IN CORRIDOR C104. WHEN COMPARING DRAWING PAGE
 LS-0.1 TO YOUR PHASING PLAN FOR THE GROUND FLOOR, YOU
 ARE RESTRICTING THE USE OF CORRIDOR C 103 FOR EXITING
 OUT OF THE BUILDING
  
 4. PLEASE EXPLAIN BY MODIFYING THE LS PLAN SHOWING THE
 TRAVEL DISTANCE FOR THE OCCUPANTS OF PHASE 1
  
 5. END OF COMMENTS
  
 RICHARD GATHRIGHT
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-09-17 Cont ID  
Sent By regathri Date 2020-09-17 Time 11:42 Rev Time 0.00
Received By rgathrig Date 2020-09-17 Time 11:40 Sent To  
Notes
2020-09-17 11:42:11THIS PLAN FOR THE PHASED OCCUPANCY IS FAILED BY RICHARD
 GATHRIGHT, ASSISTANT BUILDING OFFICIAL, WITH THE
 FOLLOWING COMMENTS.
 1. ALL LIFE SAFETY MUST BE IN PLACE, INSPECTED AND
 APPROVED PRIOR TO ANY OCCUPANCY. EXPLAIN HOW YOU WILL
 BE ABLE TO DIVIDE THE PROPOSED OCCUPIED AREA FROM THE
 CONSTRUCTION AREA IN TERMS OF THE SPRINKLER AND ALARM
 SYSTEMS.
 2. IT APPEARS THAT YOU ARE PROPOSING PHASE 1 OCCUPANCY
 TO BE THE SOUTH WING OF THE BUILDING ALL FLOORS AND THE
 PARKING GARAGE. PHASE 2/3 OCCUPANCY WILL BE THE
 APARTMENTS THAT WRAP AROUND THE GARAGE ALL FLOORS.
 3. YOU ARE PROPOSING STAIRS 1 AND 5 WILL BE USED BY THE
 APARTMENTS IN THE SOUTH WING OF THE BUILDING. STAIRS 5
 AND 4 WILL BE USED BY THE PARKING GARAGE
 4. BY STAIR 4 ON GROUND FLOOR IT APPEARS THAT YOU MAY
 HAVE CREATED A DEAD END BY BLOCKING OFF DOOR
 5. PROVIDE A NARRATIVE OF YOUR INTENTIONS TO OCCUPY THE
 BUILDING IN PHASES.
 6. WHERE IS YOUR LEASING OFFICE AND HOW DO YOU PLAN TO
 HAVE THE PUBLIC HAVE ACCESS TO THE LEASING OFFICE?
 WHERE IS THE ACCESSIBLE PARKING FOR THE LEASING OFFICE?
 7. EGRESS OUT OF THE CONSTRUCTION AREA MUST BE
 MAINTAINED FOR CONSTRUCTION AS WELL AS PROVIDING THE
 REQUIRED EXITING FOR THE APARTMENTS
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 5618056679

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2020-12-22 Cont ID  
Sent By pleduc Date 2020-12-22 Time   Rev Time 0.00
Received By pleduc Date 2020-12-22 Time 16:43 Sent To  
Notes
2020-12-22 16:43:31FIRE PROVISO:
  
 APPROVED PENDING SITE INSPECTIONS
 AND FIRE INSPECTOR LIFE SAFETY CONCERNS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-11-06 Cont ID  
Sent By pleduc Date 2020-11-06 Time   Rev Time 0.00
Received By pleduc Date 2020-11-06 Time 15:01 Sent To  
Notes
2020-11-06 15:01:42APPROVED PENDING TCO FIRE INSPECTIONS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-09-29 Cont ID  
Sent By pleduc Date 2020-09-29 Time   Rev Time 0.00
Received By pleduc Date 2020-09-28 Time 10:37 Sent To  
Notes
2020-09-29 10:13:02APPROVED PENDING TCO FIRE INSPECTIONS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By pleduc Date 2020-07-07 Time   Rev Time 0.00
Received By pleduc Date 2020-07-06 Time 13:35 Sent To  
Notes
2020-07-06 14:32:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS THAT ALL LIFE SAFETY WILL BE
 IN PLACE, TESTED AND INSPECTED PRIOR TO ANY OCCUPANCY.
  
 THE FIRE SPRINKLER AND FIRE ALARM SHALL BE FULLY
 FUNCTIONAL, OPERATIONAL, TESTED AND INSPECTED AS IF IT
 WERE A CO.
  
 A FIRE WATCH IS NOT AN ACCEPTABLE OPTION.
  
 PLEASE REVIEW, ENSURE FUNCTIONALITY AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 1A) WHAT/WHERE IS THE PROPOSED LOCATION OF THE FACP
 DURING THE OCCUPANCY OF PHASE 1 AND FUTURE PHASES?
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
  
 1B) THERE ARE NO INDICATIONS A THE RADIO COMMUNICATIONS
 BEING COMPLETED AND TESTED.
  
 EMERGENCY RADIO COMMUNICATIONS IS A REQUIRED LIFE
 SAFETY SYSTEM.
  
 THE RADIO COMMUNICATIONS IS REQUIRED TO BE INSTALLED,
 INSPECTED AND TESTED ACCORDING TO ALL REQUIRED
 STANDARDS INCLUDING PALM BEACH COUNTY RADIO
 COMMUNICATIONS DEPARTMENT.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEGDEMENT.
  
  
 2) SHEET LS 0.1 - EXITING OUT STAIR # 4 THERE IS AN
 EGRESS PATH OUT ALONG A BARRICADES TO AN UNKNOWN AREA.
  
 WHERE DOES THIS EGRESS LEAD TO? IS THIS AREA A PUBLIC
 WAY?
  
 PER NFPA 101 CH 7
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN
 7.7.1.2 THROUGH 7.7.1.4.
 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS
 OF THE EXIT
 DISCHARGE SHALL BE OF THE REQUIRED WIDTH AND SIZE TO
 PROVIDE ALL
 OCCUPANTS WITH A SAFE ACCESS TO A PUBLIC WAY.
  
 PLEASE REVIEW AND PROVIDE DETAILS AND CORRECT IF
 APPLICABLE.
  
  
 2A) SHEET LS 0.1 - WILL THE EXIT FROM THE POOL AREA BY
 THE POOL PAVILION BE ACESSIBLE AND FUNCTIONAL DURING
 ALL PHASES WHEN THE POOL IS OPEN?
  
 WILL THAT EXIT LEAD TO A PUBLIC WAY AT ALL TIMES?
  
 PLEASE REVIEW AND PROVIDE DETAILS AND CORRECT.
  
  
  
  
 2B) SHEET LS 0.1 - EXITING OUT AND DOWN STAIR # 5 THERE
 IS AN EGRESS PATH OUT THAT IS GREYED-OUT AND NOT COLOR
 CODED TO ANY PHASE.
  
 THIS EXIT SERVES THE FLOORS ABOVE AND APPEARS TO BE
 UNPORTECTED AND IN A CONSTRUCTION AREA.
  
 PLEASE REVIEW AND PROVIDE DETAILS AND CORRECT IF
 APPLICABLE.
  
  
  
  
 3) SHEET LS 0.1 - THERE ARE NO INDICATIONS OF ANY
 OVERHEAD PROTECTION IN AREAS THAT MAY HAVING CONTINUING
 CONSTRUCTION OVERHEAD.
  
 PLEASE REVIEW, PROVIDE DETAILS OF NEEDS, ENSURE
 PROTECTION AND CORRECT WHERE APPLICABLE.
  
  
  
 4) SHEET LS 0.1 - THERE ARE INDICATIONS OF CORRIDORS
 BEING BLOCKED OFF WITH TEMPORARY DOORS.
  
 WHAT IS THE CONSTRUCTION MATERIAL TYPE, FIRE RATING AND
 HARDWARE THAT PROVIDES THE APPLICABLE PROTECTION IN
 THESE AREAS?
  
 PLEASE REVIEW AND PROVIDE DETAILS AND CORRECT.
  
  
  
 5) REMAINING LIFE SAFETY SHEETS - THERE ARE INDICATIONS
 ON EACH FLOOR OF A WALL CONSTRUCTED WITHIN THE
 CORRIDOR.
  
 WHAT IS THE CONSTRUCTION MATERIAL TYPE AND FIRE RATING
 THAT PROVIDES THE APPLICABLE PROTECTION IN THESE AREAS?
  
 PLEASE REVIEW AND PROVIDE DETAILS AND CORRECT.
  
  
  
 6) REMAINING LIFE SAFETY SHEETS - THERE ARE INDICATIONS
 ON EACH FLOOR AT STAIR # 5 OF A TEMPORARY EGRESS DOOR
 UNTIL CONSTRUCTION COMPLETE.
  
 WHAT IS THE CONSTRUCTION MATERIAL TYPE AND FIRE RATING
 THAT PROVIDES THE APPLICABLE PROTECTION IN THESE AREAS?
  
 PLEASE REVIEW AND PROVIDE DETAILS AND CORRECT.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-22 Cont ID  
Sent By ccarvaja Date 2020-12-22 Time 16:29 Rev Time 0.00
Received By ccarvaja Date 2020-11-04 Time 10:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-30 Cont ID  
Sent By cpuell Date 2020-10-30 Time 12:57 Rev Time 0.00
Received By cpuell Date 2020-09-26 Time 07:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2020-09-17 Cont ID  
Sent By rgathrig Date 2020-09-17 Time 11:44 Rev Time 0.00
Received By rgathrig Date 2020-06-30 Time 07:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-12-22 Cont ID  
Sent By rgathrig Date 2020-12-22 Time 16:14 Rev Time 0.00
Received By rgathrig Date 2020-12-22 Time 16:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-09-17 Cont ID  
Sent By rgathrig Date 2020-09-17 Time 11:43 Rev Time 0.00
Received By rgathrig Date 2020-09-17 Time 11:42 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved