Plan Review Details - Permit 20061307
Plan Review Stops For Permit 20061307 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-07-13 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-07-13 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-07-13 |
Time |
08:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-07-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-07-02 |
Time |
09:44 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-07-02 |
Time |
09:44 |
Sent To |
|
|
Notes |
2020-07-02 09:49:09 | SHUTTERS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) NEED SIGNED AND SEALED WIND DESIGN PRESSURES FROM AN | | ARCHITECT OR ENGINEER FBC 1609 - DRAWINGS/DOCUMENTS | | NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE | | ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC PLAN | | REVIEW. | | | | 2) ROOF MEAN HEIGHT APPEARS TO BE HIGHER THAN 25' AS | | SHOWN ON THE DOCUMENTS PROVIDED. | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-07-13 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-07-13 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-07-06 |
Time |
13:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-07-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-07-02 |
Time |
09:50 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-06-30 |
Time |
07:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2020-07-13 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-07-13 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-07-13 |
Time |
08:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-07-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-07-02 |
Time |
09:49 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-07-02 |
Time |
09:49 |
Sent To |
|
|
Notes |
2020-07-02 09:49:54 | NEED SIGNED AND SEALED WIND DESIGN PRESSURES = | | DRAWINGS/DOCUMENTS NEED TO BE DIGITALLY/ELECTRONICALLY | | SIGNED BY THE ENGINEER OR ARCHITECT TO BE USED IN | | ELECTRONIC PLAN REVIEW. DRAWINGS/DOCUMENTS DO NOT SHOW | | IN "ADOBE READER" AS DIGITALLY/ELECTRONICALLY SIGNED. | | | | FYI = ENGINEER CANNOT SELF-CERTIFY THE DIGITAL | | SIGNATURE | | 668.003(2) AND (3), F.S. | | (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL | | SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING | | PLANS, | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE | | THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION | | AUTHORITY. | | |
|
|
|