Plan Review Details - Permit 20061298
Plan Review Stops For Permit 20061298
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-07-23 Cont ID  
Sent By cpuell Date 2020-07-23 Time 12:00 Rev Time 0.00
Received By cpuell Date 2020-07-23 Time 12:00 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-07-28 Cont ID  
Sent By jwitmer Date 2020-07-28 Time 08:38 Rev Time 0.00
Received By jwitmer Date 2020-07-28 Time 07:46 Sent To  
Notes
2020-07-28 08:38:16IN 1997 NEW BUILDING, NO ASBESTOS. J. W.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-10-08 Cont ID  
Sent By jwitmer Date 2020-10-08 Time 14:45 Rev Time 0.00
Received By jwitmer Date 2020-10-08 Time 14:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-09-02 Cont ID  
Sent By jwitmer Date 2020-09-02 Time 09:12 Rev Time 0.00
Received By jwitmer Date 2020-09-02 Time 08:17 Sent To  
Notes
2020-09-02 09:12:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061298
 ADD: 700 S. ROSEMARY ST. SUITE: 218
 CONT: RCC ASSOCIATES
 TEL: 954-4293700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. SEPT. 02ND/2020
 ACTION: DENIED
  
 1) COMPLIED. 9/03/2020
  
 2) SEMI-COMPLIED. THE DESIGNER HAS SHOWN WHERE A
 PORTION OF THE ACCESSIBLE SEATING WILL OCCUR, AT THE
 BAR. 46 SEATS X 0.05 = 2.3 OR 3 SEATS YOU ALWAYS ROUND
 UP THERE ARE NEVER PORTIONS OF PATRONS. THE REQUIREMENT
 OF DISPERSION WOULD REQUIRE ACCESSIBLE SEATING AT LEAST
 ONE OF THE TABLES.
  
 SHEET A2.1 SHOWS ON THE FLOOR PLAN 2 AREAS OF DROPPED
 BAR SURFACES. SHEET A601 DETAIL 5 SHOWS ON THE NEW
 PROPOSED DROP BAR COUNTER SURFACE A SUB-SURFACE 3/4
 INCH PLYWOOD AND A 1 1/2 INCH CONCRETE TOP SURFACE. THE
 PLANS ARE SILENT AS TO HOW THE WEIGHT OF THE CONCRETE
 COUNTER TOP WILLBE SUPPORTED. PLEASE REVIEW THE
 REQUIREMENTS FOR KNEE & TOE CLEARANCES SEE SECTION 306
 OF THE 2017 ACCESSIBLITY CODE.
 IT WOULD APPEAR THAT A SUPPORT POST AT THE OUTER CORNER
 OF THE DROPPED BAR WOULD NOT ALLOW FOR THE FORWARD
 APPROACH WITH 30 INCHES CLEAR?CLEAR FLOOR SPACE 30 X 48
 INCHES CLLEAR FLOOR SPACE FIGURE 305.3.
  
 1ST ROUND COMMENTS. SHEET A201 SHOWS 34 SEATS AT THE
 BAR AND 12 SEATS W/ TABLES. THE PLAN DOES NOT SHOW ANY
 ACCESSIBLE SEATING. 2017 FBC-ACC. SECTION 226.1 WHERE
 DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF
 FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES
 AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902.
  
 2A) DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW
 YOU ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS (&55,000.00 X 0.20% =
 $11,000.00 DOLLARS) LISTED FOR EACH ELEMENT WHERE THE
 FUNDS ARE BEING SPENT AND IN THE ORDER LISTED IN
 SECTION 202.4.1 DISPROPORTIONATE COST OF THE 2017
 ACCESSIBILITY CODE.
  
 2B) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
  
 2C)2ND REQUEST. 206.2.5 206.2.5 RESTAURANTS AND
 CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS,
 INCLUDING RAISED OR SUNKEN DINING AREAS, AND OUTDOOR
 DINING AREAS.
  
 2D) 2ND REQUEST. 902.1 .DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY
 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT
 LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS.
 EXAMPLES OF WORK SURFACES INCLUDE WRITING SURFACES,
 STUDY CARRELS, STUDENT LABORATORY STATIONS, BABY
 CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL
 GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ADA
 SCOPING PROVISIONS, EMPLOYEE WORK STATIONS.
  
 2D)(1)2ND REQUEST. 902.2 CLEAR FLOOR OR GROUND SPACE. A
 CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2D)(2) 2ND REQUEST. 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By jwitmer Date 2020-07-28 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2020-07-28 Time 07:46 Sent To  
Notes
2020-07-28 08:35:29WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061298
 ADD: 700 S. ROSEMARY ST. SUITE: 218
 CONT: RCC ASSOCIATES
 TEL: 954-4293700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 28TH/2020
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS ARE COPIES OF STAMPED APPROVED
 PLANS NOT ORIGINALS. THE 2NDDD ISSUE IS THAT THEY ARE
 BEING SUBMITTED DIGITALLY AND REQUIRE THE ARCHITECT AND
 ENGINEERS TO HAVE DIGITALLY SIGNED AND SEALED PLANS.
 ARCHITECTS: FLORIDA ADMINISTRATIVE CODE 61G1-16.005.
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) SHEET A201 SHOWS 34 SEATS AT THE BAR AND 12 SEATS W/
 TABLES. THE PLAN DOES NOT SHOW ANY ACCESSIBLE SEATING.
 2017 FBC-ACC. SECTION 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 2A) DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW
 YOU ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS (&55,000.00 X 0.20% =
 $11,000.00 DOLLARS) LISTED FOR EACH ELEMENT WHERE THE
 FUNDS ARE BEING SPENT AND IN THE ORDER LISTED IN
 SECTION 202.4.1 DISPROPORTIONATE COST OF THE 2017
 ACCESSIBILITY CODE.
  
 2B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 2D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 2D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-08 Cont ID  
Sent By fgiaquin Date 2020-09-08 Time 23:09 Rev Time 0.00
Received By fgiaquin Date 2020-09-08 Time 22:33 Sent To  
Notes
2020-09-08 23:09:43APPROVED FOR LIGHTING ONLY, NO POWER PLAN SUBMITTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-12 Cont ID  
Sent By fgiaquin Date 2020-08-12 Time 20:09 Rev Time 0.00
Received By fgiaquin Date 2020-08-12 Time 19:51 Sent To  
Notes
2020-08-12 20:09:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THIS IS A SIGNED AND APPROVED PLAN FROM 2018
 PREVIOUSLY SIGNED BY ELECTRICAL PLANS EXAMINER JAKE
 LEAHY. PROVIDE NEW PLANS SIGNED AND SEALED DIGITALLY BY
 DESIGN PROFESSIONAL FOR REVIEW.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-08-27 Cont ID  
Sent By pleduc Date 2020-08-27 Time   Rev Time 0.00
Received By pleduc Date 2020-08-27 Time 11:19 Sent To  
Notes
2020-08-27 11:32:40THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 1) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
  
 2) ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 3) THE EXTENT OF THE REMODEL OR REVISION IS UNCLEAR AND
 DOES NOT INDICATE SUFFICIENT DETAIL OF THE FIRE
 SPRINKLER & FIRE ALARM TO ADDRESS LIFE SAFETY CONCERNS
 OF THE PROPOSED PROJECT.
  
  
 4) THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 ANY FIRE SPRINKLER AND FIRE ALARM SYSTEM EQUIPMENT FOR
 CODE COVERAGE AND COMPLIANCE. ANY REMOVAL AND/OR
 CONSTRUCTION OF WALLS REQUIRE AN EVALUATION OF THE
 EXISTING EQUIPMENT.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-07-24 Cont ID  
Sent By pleduc Date 2020-07-24 Time   Rev Time 0.00
Received By pleduc Date 2020-07-24 Time 10:10 Sent To  
Notes
2020-07-24 10:40:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 1) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 2) ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 3) THE EXTENT OF THE REMODEL OR REVISION IS UNCLEAR AND
 DOES NOT INDICATE SUFFICIENT DETAIL TO ADDRESS LIFE
 SAFETY CONCERNS OF THE PROPOSED PROJECT.
  
  
 4) THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 ANY FIRE ALARM SYSTEM EQUIPMENT FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRE AN EVALUATION OF THE EXISTING EQUIPMENT.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-13 Cont ID  
Sent By cpuell Date 2020-10-13 Time 16:00 Rev Time 0.00
Received By cpuell Date 2020-10-06 Time 07:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-21 Cont ID  
Sent By ccarvaja Date 2020-09-21 Time 13:25 Rev Time 0.00
Received By ccarvaja Date 2020-08-26 Time 08:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-25 Cont ID  
Sent By lmarchan Date 2020-08-25 Time 06:53 Rev Time 0.00
Received By lmarchan Date 2020-07-23 Time 09:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-08-05 Cont ID  
Sent By medwards Date 2020-08-05 Time 10:00 Rev Time 0.00
Received By medwards Date 2020-08-05 Time 09:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-08-11 Cont ID  
Sent By tklarge Date 2020-08-11 Time 06:02 Rev Time 0.00
Received By tklarge Date 2020-08-11 Time 05:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-08 Cont ID  
Sent By jwitmer Date 2020-10-08 Time 14:45 Rev Time 0.00
Received By jwitmer Date 2020-10-08 Time 14:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-02 Cont ID  
Sent By jwitmer Date 2020-09-02 Time 09:13 Rev Time 0.00
Received By jwitmer Date 2020-09-02 Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By jwitmer Date 2020-07-28 Time 08:45 Rev Time 0.00
Received By jwitmer Date 2020-07-28 Time   Sent To  
Notes
2020-07-28 08:39:38) THE SUBMITTED PLANS ARE COPIES OF STAMPED APPROVED
 PLANS NOT ORIGINALS. THE 2NDDD ISSUE IS THAT THEY ARE
 BEING SUBMITTED DIGITALLY AND REQUIRE THE ARCHITECT AND
 ENGINEERS TO HAVE DIGITALLY SIGNED AND SEALED PLANS.
 ARCHITECTS: FLORIDA ADMINISTRATIVE CODE 61G1-16.005.
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2020-10-13 Cont ID  
Sent By eschneid Date 2020-10-13 Time 14:05 Rev Time 0.25
Received By eschneid Date 2020-10-13 Time 12:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-09-21 Cont ID  
Sent By eschneid Date 2020-09-21 Time 11:33 Rev Time 0.25
Received By eschneid Date 2020-09-21 Time 11:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-08-24 Cont ID  
Sent By eschneid Date 2020-08-24 Time 17:09 Rev Time 0.25
Received By eschneid Date 2020-08-24 Time 16:10 Sent To  
Notes
2020-08-24 17:10:49SEE STAMPS FROM PREVIOUS APPROVAL (PERMIT 18070895).