Plan Review Details - Permit 20061271
Plan Review Stops For Permit 20061271
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-08-04 Cont ID  
Sent By lcrespo Date 2020-08-04 Time 09:38 Rev Time 0.00
Received By lcrespo Date 2020-08-04 Time 09:38 Sent To  
Notes
2020-08-04 09:39:3008/04/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-07-22 Cont ID  
Sent By ccole Date 2020-07-22 Time 09:42 Rev Time 0.00
Received By ccole Date 2020-07-21 Time 16:25 Sent To  
Notes
2020-07-22 09:42:532ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20061271
 7/20/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISED GAS ISOMETRIC DRAWING:
 A) THE DRAWING HAS NOTES INDICATING A 2 PSI DELIVERY
 PRESSURE AT THE METER WITH PIPE SIZING ACCORDING TO
 TABLE 402.4(22) FOR PE AT 2PSI, HOWEVER THE DRAWING
 ALSO HAS NOTES INDICATING 12 " WC REGULATOR AT THE
 METER. FOR CLARIFICATION, PLEASE SHOW THE LOCATION OR
 LOCATIONS OF THE REGULATORS ON THE DRAWINGS. IF THE
 REGULATOR IS AT THE METER THEN PROVIDE THE CORRECT
 SIZING TABLE FOR THE LOW PRESSURE RUNS TO THE
 APPLIANCES- SEE TABLE G2413.4(7) FBC RES OR TABLE
 402.4(21) FBC FUEL GAS. IF THE REGULATORS ARE TO BE
 INSTALLED AT THE APPLIANCES PLEASE SHOW THE LOCATIONS
 ON THE DRAWING.
 B) PROVIDE THE MAKE AND MODEL NUMBERS OF THE REGULATORS
 ON THE DRAWING AND SUBMIT SPECS THAT ARE MARKED UP TO
 INDICATE WHICH MODELS WILL BE INSTALLED AND THEIR
 PRESSURE RANGES.
 C) PLEASE LABEL THE METER AS EITHER NEW OR EXISTING.
 PLEASE NOTE THAT IF THE METER IS EXISTING AND IS
 SUPPLYING OTHER EXISTING GAS FIRED EQUIPMENT AND
 APPLIANCES, IN ORDER TO ENSURE A SAFE OPERATING SYSTEM,
 THE DRAWING MUST BE MODIFIED TO SHOW THE ENTIRE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET AND INCLUDE
 ALL BRANCH PIPE RUNS. EACH NEW AND EXISTING APPLIANCE
 BTUH LOAD SHALL BE INDICATED ON THE DRAWING, AND THE
 TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER TO
 THE MOST REMOTE OUTLET MUST BE PROVIDED- SECTIONS
 G2413.4.1, G2413.4.2 & G2413.4.3. FOR CLARIFICATION
 PLEASE SHOW THE MAIN PIPE AND TEE LOCATION AT THE METER
 ON THE DRAWING.
  
 2) THE MAIN PERMIT PLANS FOR THE NEW OUTDOOR KITCHEN-
 PERMIT-20020841 DID NOT PROVIDE GAS VENTING PLANS FOR
 THE FIREPLACE AND BBQ GRILL. COMPLETE DRAWINGS AND
 DETAILS ARE REQUIRED. THE NEW SUBMITTAL LABELED AS
 "CHIMNEY SPECS" IS TWO PAGES OF THE ISOKERN GAS LOG SET
 THAT SHOW ONLY THE REQUIRED INPUT GAS PRESSURE AND THE
 BTUH LOAD OF THE UNIT. THE SUBMITTAL FOR THE BBQ IS
 MISSING PAGE 4 OF THE INSTALLATION MANUAL WHICH
 PROVIDES THE EXHAUST HOOD AND EXHAUST DUCT INFORMATION.
 BECAUSE THE UNIT IS BEING INSTALLED UNDER OVERHEAD
 CONSTRUCTION, THE MANUFACTURER REQUIRES A 1200 CFM HOOD
 TO BE INSTALLED. VENTING PLANS SHALL BE DRAWN IN
 ACCORDANCE WITH THE MANUFACTURER?S SPECIFICATIONS-
 SECTIONS G2435.1, G2447.1AND G2427 FBC RES.
  
 A) PLEASE CLARIFY IF YOUR COMPANY IS CONTRACTED TO
 INSTALL THE VENTING- SUBMIT A COPY OF A SIGNED CONTRACT
 INDICATING THE ENTIRE SCOPE OF WORK YOU ARE PROVIDING
 TO THE CUSTOMER. IF THE APPLIANCE VENTING IS NOT IN
 YOUR SCOPE THEN IT MUST BE PERFORMED BY A SEPARATE
 SUB-CONTRACT UNDER PERMIT 20020841. PERMIT 20020841 IS
 STILL AN OPEN PERMIT THAT WOULD HAVE TO BE REVISED TO
 SHOW THE VENTING PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By ccole Date 2020-07-07 Time 16:39 Rev Time 0.00
Received By ccole Date 2020-07-07 Time 14:53 Sent To  
Notes
2020-07-07 16:39:301ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20061271
 7/7/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-00: THE CONTRACTOR IS NOT PERMITTED BY FL.
 STATUTES 481 AND 489 TO MARK UP AN ARCHITECT'S PLAN.
 THE ARCHITECT DAVID GENGLER MAY PROVIDE AN
 ELECTRONICALLY SIGNED AND SEALED GAS PIPING LAYOUT
 PLAN, OR THE CONTRACTOR MAY PROVIDE A SEPARATE LAYOUT
 PLAN WITH HIS SIGNATURE ON THE PLAN- SECTION 107.2.1
 WPB.
  
 2) BASED ON THE APPROVED PLANS UNDER PERMIT-20020841, A
 SEPARATE PERMIT WAS REQUIRED FOR GAS. THE APPROVED
 PLANS INDICATED A GAS BBQ WAS BEING INSTALLED IN THE
 OUTDOOR KITCHEN. IT IS MANDATORY THAT THE BBQ AND ANY
 OTHER GAS-FIRED APPLIANCES EITHER NEW OR EXISTING ARE
 INCLUDED IN THE GAS PLANS AND ISOMETRIC DRAWING TO
 ENSURE A SAFE OPERATING SYSTEM WILL BE INSTALLED-
 SECTION G2412.4 FBC RES.
  
 COMMENTS 3-5 BELOW ARE SPECIFIC TO THE CURRENT
 SUBMITTAL WHICH MUST BE MODIFIED PER COMMENT #2.
  
 3) GAS ISOMETRIC: A) PROVIDE THE TOTAL DEVELOPED LENGTH
 OF THE SYSTEM AND THE TOTAL BTUH LOAD- SECTIONS
 G2413.4.1 AND G2413.3 FBC RES. B) PROVIDE THE SIZE AND
 TYPE OF GAS PIPE AT THE METER THAT THE NEW CSST LINES
 ARE CONNECTING TO- SECTION 2413.4.1. C) SHOW THE
 REGULATOR AND GAS DELIVERY PRESSURE AT THE METER-
 SECTION G2413.2 D) ACCORDING TO TABLE 402.4(15) FBC FG
 OR G2413.4(5) FBC RES THE EHD 13 AND 15 CSST PIPES ARE
 UNDERSIZED: 160,000 BTUH = 160 CFH OF GAS. TANKLESS-1
 REQUIRES AT 75 FT. AND TANKLESS-2 AT 60FT. EACH REQUIRE
 EHD 37. D) SIGNATURE OF THE CONTRACTOR SHALL BE ON THE
 REVISED ISOMETRIC DRAWING- SECTION 107.2.1 WPB.
  
 4) UNDERGROUND CSST INSTALLATIONS SHALL BE DONE IN
 ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS. THE
 PIPE SHALL EITHER BE LISTED AND LABELED FOR DIRECT
 BURIAL OR BE INSTALLED IN A PROTECTIVE CONDUIT. PROVIDE
 INSTALLATION DETAILS AS RECOMMENDED BY THE
 MANUFACTURER- SEE SECTIONS G2415.2 AND G2415.11 FBC RES
 (404.2 & 404.11 FBC FG).
  
 5) PROVIDE FRONT ELEVATION VIEWS OF THE TANKLESS WATER
 HEATERS SHOWING: A) INSTALLATION HEIGHTS ABOVE THE
 GRADE. B) VENT TERMINATION CLEARANCES TO OPERABLE
 WINDOWS AND DOORS AND AIR INLETW INTO THE BUILDING-
 G2427.8. C) VENT FLUE INSTALLATIONS: PROVIDE A VENTING
 DIAGRAM SHOWING THE TYPE AND SIZE FLUE VENT, LENGTH OF
 CONNECTOR (IF APPLICABLE), TOTAL LENGTH OF VENT FLUE
 RUN INCLUDING OFFSETS, AND TERMINATION LOCATION-
 SECTIONS G2427.6.1- G2427.6.11 FBC RES. PLEASE INDICATE
 VENT TERMINATION CLEARANCES PER SECTION G2427.6.3.
  
 6) THE SUBMITTED TANKLESS WATER HEATER SPECS ARE
 INCOMPLETE AND DO NOT PROVIDE THE REQUIRED GAS INPUT
 PRESSURES FOR THE WATER HEATERS- SECTION G2448.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-04 Cont ID  
Sent By lcrespo Date 2020-08-04 Time 09:38 Rev Time 0.00
Received By lcrespo Date 2020-08-03 Time 06:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-07-22 Time   Rev Time 0.00
Received By lmarchan Date 2020-07-13 Time 14:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-07-07 Time   Rev Time 0.00
Received By lmarchan Date 2020-06-25 Time 15:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-08-04 Cont ID  
Sent By lcrespo Date 2020-08-04 Time 09:38 Rev Time 0.00
Received By lcrespo Date 2020-08-04 Time 09:38 Sent To  
Notes
2020-08-04 09:40:0008/04/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-07-22 Cont ID  
Sent By ccole Date 2020-07-22 Time 09:45 Rev Time 0.00
Received By ccole Date 2020-07-21 Time 16:25 Sent To  
Notes
2020-07-22 09:46:37PLUMBING APPROVAL STAMPS AND PROVISOS WILL BE PLACED ON
 THE PLANS AT TIME OF FUEL GAS APPROVAL

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By ccole Date 2020-07-07 Time 16:41 Rev Time 0.00
Received By ccole Date 2020-07-07 Time 14:54 Sent To  
Notes
2020-07-07 16:47:531ST REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20061271
 7/7/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A WATER PIPING PLAN AND RISER DRAWING
 SHOWING NEW WATER PIPING RUNS FROM THE WATER HEATERS,
 AND POINTS OF CONNECTIONS TO THE EXISTING SYSTEM-
 SECTION 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-07-22 Cont ID  
Sent By ccole Date 2020-07-22 Time 09:51 Rev Time 0.00
Received By ccole Date 2020-07-22 Time 09:51 Sent To  
Notes
2020-07-22 09:52:32THE UNSIGNED AND SEALED ARCHITECT'S PLAN HAS BEEN
 VOIDED. NEW CONTRACTOR DESIGNED PLANS BEARING
 SIGNATURES HAVE BEEN RESUBMITTED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By ccole Date 2020-07-07 Time 16:52 Rev Time 0.00
Received By ccole Date 2020-07-07 Time 14:54 Sent To  
Notes
2020-07-07 16:56:06THE CONTRACTOR SHALL PROVIDE AN ELECTRONICALLY SIGNED
 AND SEALED PLAN BY THE ARCHITECT OF RECORD, OR REPLACE
 THE MARKED UP ARCHITECT'S PLAN WITH A SEPARATE GAS
 PIPING LAYOUT PLAN-- FL STATUTE 481.221 AND SECTION
 61G1-16.005 FLORIDA ADMINISTRATIVE CODE.
  
  