Plan Review Details - Permit 20061258
Plan Review Stops For Permit 20061258
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-29 Cont ID  
Sent By hmoser Date 2020-07-29 Time 13:40 Rev Time 0.00
Received By hmoser Date 2020-07-29 Time 11:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-09 Cont ID  
Sent By lmarchan Date 2020-07-09 Time 13:11 Rev Time 0.00
Received By lmarchan Date 2020-06-25 Time 11:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-07-29 Cont ID  
Sent By hmoser Date 2020-07-29 Time 13:39 Rev Time 0.00
Received By hmoser Date 2020-07-29 Time 13:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-07-29 Cont ID  
Sent By medwards Date 2020-07-09 Time 11:49 Rev Time 0.00
Received By medwards Date 2020-07-29 Time 08:43 Sent To  
Notes
2020-07-29 08:44:36BASED ON CONVERSATION WITH HAROLD MOSER THIS SYSTEM
 WILL BE A RETURN AIR PLENUM ABOVE THE CEILING. WITH
 THIS INFORMATION I WIL APPROVE THIS PROJECT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2020-07-09 11:49:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE TYPE OF DUCT USED AND THE R-VALUE OF THE NEW
 DUCT, ALSO PLEASE PROVIDE THE MANUAL D CALCULATIONS FOR
 THE SIZING OF THE DUCT SYSTEM. FBC M 603
  
 2) PLEASE PROVIDE THE SPEC SHEETS FOR THE NEW BATH
 EXHAUST FANS. FBC FS 107.2.1
  
 3) PLEASE SHOW RETURN AIR PATH BACK TO EXISTING AHU. IS
 THE CLOSET DOOR TO THE EXISTING AHU A LOUVER DOOR? IS
 THE CEILING A LAY IN CEILING AND THE AREA ABOVE USED AS
 A RETURN AIR PLENUM? FBC M 601.6
  
 4) PLEASE SHOW RETURN AIR PATH WHEN POCKET DOOR IS
 CLOSED AT MASTER BEDROOM AREA. FBC M 601.6
  
 5) PLEASE SHOW RETURN AIR PATH FOR GUEST BEDROOM. FBC M
 601.6
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-29 Cont ID  
Sent By hmoser Date 2020-07-29 Time 13:40 Rev Time 0.00
Received By hmoser Date 2020-07-29 Time 13:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-09 Cont ID  
Sent By medwards Date 2020-07-09 Time 11:50 Rev Time 0.00
Received By medwards Date 2020-07-09 Time 11:50 Sent To  
Notes
2020-07-09 11:53:37DESIGNER MUST SIGN AND DATE THE DRAWING. FS 471.025
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  