Plan Review Details - Permit 20061190
Plan Review Stops For Permit 20061190
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-31 Cont ID  
Sent By shill Date 2020-07-31 Time 11:25 Rev Time 0.00
Received By shill Date 2020-07-31 Time 11:25 Sent To  
Notes
2020-07-31 11:25:48PROVISO - PROVIDE INSTALLATION SCHEDULE AT INSPECTION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-21 Cont ID  
Sent By jbrooks Date 2020-07-21 Time 13:35 Rev Time 0.00
Received By jbrooks Date 2020-07-21 Time 13:35 Sent To  
Notes
2020-07-21 13:35:39JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON
 SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF
 USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON
 W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
 3. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC
 R 310.4; INCLUDE ROOM DESIGNATION
 4. FBC B 107.2.1. ASCE 7-16 HAS NOT BEEN ADOPTED YET.
 WE ARE CURRENTLY USING THE 2017 FBC AND ASCE 7-10 FOR
 WIND LOAD DESIGN INFORMATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-21 Cont ID  
Sent By jbrooks Date 2020-07-21 Time 13:35 Rev Time 0.00
Received By jbrooks Date 2020-06-25 Time 15:50 Sent To  
Notes
2020-06-25 15:50:49ROUTED TO BLDG. MISC 1