2020-07-21 13:35:39 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| 805-6724 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| 1. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION |
| OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL |
| INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL |
| SPREADSHEET): |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS?PAGE=2 |
| 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE |
| NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON |
| SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF |
| USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON |
| W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR). |
| 3. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC |
| R 310.4; INCLUDE ROOM DESIGNATION |
| 4. FBC B 107.2.1. ASCE 7-16 HAS NOT BEEN ADOPTED YET. |
| WE ARE CURRENTLY USING THE 2017 FBC AND ASCE 7-10 FOR |
| WIND LOAD DESIGN INFORMATION. |
| |