Plan Review Details - Permit 20061156
Plan Review Stops For Permit 20061156
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-19 Cont ID  
Sent By cthroop Date 2020-08-19 Time 13:35 Rev Time 0.00
Received By cthroop Date 2020-08-19 Time 12:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-15 Cont ID  
Sent By cthroop Date 2020-07-15 Time 12:40 Rev Time 0.00
Received By cthroop Date 2020-07-15 Time 10:10 Sent To  
Notes
2020-07-15 12:43:32PLAN REVIEW ? GENERATOR - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE STRUCTURAL DETAIL OF GENERATOR PAD.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2) STRUCTURAL PAD DETAIL SHALL BE SIGNED BY DESIGNER.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-19 Cont ID  
Sent By cthroop Date 2020-08-19 Time 13:22 Rev Time 0.00
Received By cthroop Date 2020-08-19 Time 12:58 Sent To  
Notes
2020-08-19 13:23:05PROVISO: PROVIDE ATS SPECS. TO CITY INSPECTOR. CT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-15 Cont ID  
Sent By cthroop Date 2020-07-15 Time 12:45 Rev Time 0.00
Received By cthroop Date 2020-07-15 Time 10:09 Sent To  
Notes
2020-07-15 12:48:01PLAN REVIEW ? GENERATOR - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER
 SWITCH. ATS
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2) PROVIDE NEW LOAD CALCULATIONS.
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-08-06 Cont ID  
Sent By lcrespo Date 2020-08-06 Time 17:23 Rev Time 0.00
Received By lcrespo Date 2020-08-06 Time 17:17 Sent To  
Notes
2020-08-06 17:24:3508/06/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-15 Cont ID  
Sent By cthroop Date 2020-07-15 Time 12:53 Rev Time 0.00
Received By cthroop Date 2020-07-15 Time 10:10 Sent To  
Notes
2020-07-15 13:08:50PLAN REVIEW ? GENERATOR - ? FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 SOW IS THE INSTALLATION OF A 48KW GENERATOR
  
 REVIEW OF CITY RECORDS INDICATES THERE IS AN EXISTING
 NG SERVICE AT THE RESIDENCE
  
  
  
  
 1) GAS ISOMETRIC DRAWING:
  
 1A) THE DRAWING IS INCOMPLETE AND MUST BE MODIFIED TO
 SHOW THE ENTIRE SYSTEM INCLUDING ALL BRANCH PIPES FROM
 THE METER TO THE MOST REMOTE OUTLET. THE BTUH LOAD OF
 EACH APPLIANCE AND THE LOCATIONS OF REGULATORS SHALL BE
 INDICATED ON THE DRAWING- SECTIONS G2412.3 & G2412.4
 FBC RES.
  
 EXCEPTION PER TIM LARGE CHIEF PLUMBING INSPECTOR - IF
 IT IS NOT POSSIBLE TO GAIN ACCESS TO THE DWELLING UNIT
 YOU MAY ESTIMATE THE TOTAL BTUH OF THE EXISTING
 APPLIANCES.
  
 NOTE: THIS PLUMBING CONTRATOR INSTALLED THE GAS
 APPLIANCES FOR THE NEW RESIDENCE. I CAN PROVIDE A COPY
 OF THE EXISTING GAS RISER IF NEEDED.
  
 1B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH
 LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 &
 G2413.4.3. PROVIDED
  
 1B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE
 OUTLET OF THE REGULATOR- SECTION G2421.1
  
 1C) PROVIDE THE BTUH LOAD OF THE GENERATOR. G2413.2 FBC
 RES.
  
 1D) PROVIDE GENERATOR SPECS. G2413.2 FBC RES.
  
 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH
 MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET
 AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION
 G2421.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-19 Cont ID  
Sent By cthroop Date 2020-08-19 Time 13:35 Rev Time 0.00
Received By cthroop Date 2020-08-05 Time 07:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-15 Cont ID  
Sent By cthroop Date 2020-07-15 Time 13:10 Rev Time 0.00
Received By cthroop Date 2020-06-25 Time 09:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-08-06 Cont ID  
Sent By lcrespo Date 2020-08-06 Time 17:17 Rev Time 0.00
Received By lcrespo Date 2020-08-06 Time 17:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-15 Cont ID  
Sent By cthroop Date 2020-07-15 Time 12:44 Rev Time 0.00
Received By cthroop Date 2020-07-15 Time 10:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-05 Cont ID  
Sent By shill Date 2020-08-05 Time 07:14 Rev Time 0.00
Received By shill Date 2020-08-05 Time 07:14 Sent To  
Notes
2020-08-05 07:15:08ORIGINAL ENGINEERING SUBMITTED
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-15 Cont ID  
Sent By cthroop Date 2020-07-15 Time 12:50 Rev Time 0.00
Received By cthroop Date 2020-07-15 Time 10:10 Sent To  
Notes
2020-07-15 12:51:59PLAN REVIEW ? GENERATOR - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15
  
 2) DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 3) UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
 4) FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By kalexand Date 2020-07-08 Time   Rev Time  
Received By   Date 2020-07-08 Time   Sent To I
Notes
***NONE***