Plan Review Details - Permit 20061050
Plan Review Stops For Permit 20061050
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-07-30 Cont ID  
Sent By rmcdouga Date 2020-07-30 Time 12:52 Rev Time 0.00
Received By rmcdouga Date 2020-07-30 Time 12:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-07-30 Cont ID  
Sent By cthroop Date 2020-07-30 Time 13:32 Rev Time 0.00
Received By cthroop Date 2020-07-30 Time 12:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-12 Cont ID  
Sent By lcrespo Date 2020-08-12 Time 14:57 Rev Time 0.00
Received By lcrespo Date 2020-08-11 Time 10:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-30 Cont ID  
Sent By lcrespo Date 2020-07-30 Time 13:52 Rev Time 0.00
Received By lcrespo Date 2020-06-19 Time 08:50 Sent To  
Notes
2020-07-30 08:54:02CONVERTED TO DIGITAL. JG.
2020-07-17 12:04:53ROUTED TO BLDG. MISC 1
2020-06-25 16:01:53ROUTED TO ZONING BIN

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-08-12 Cont ID  
Sent By lcrespo Date 2020-08-12 Time 14:57 Rev Time 0.00
Received By lcrespo Date 2020-08-12 Time 14:57 Sent To  
Notes
2020-08-12 14:58:4808/12/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-30 Cont ID  
Sent By lcrespo Date 2020-07-30 Time 13:51 Rev Time 0.00
Received By lcrespo Date 2020-07-30 Time 13:51 Sent To  
Notes
2020-07-30 13:51:3907/30/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS
 SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS
 IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE
 TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS.
 4.4.9, 4.4.9.1.
  
 2. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 CARTRIDGE FILTER AND THE PUMP PER THE WPB AMENDMENTS TO
 FBC SEC. 107.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-30 Cont ID  
Sent By jgomez Date 2020-07-30 Time 09:02 Rev Time 0.00
Received By jgomez Date 2020-07-30 Time 09:00 Sent To  
Notes
2020-07-30 09:03:2507/30/2020 CONVERTED TO DIGITAL.
 ENGINEER DRAWINGS WITH ORIGINAL SEAL AND SIGNATURE SENT
 TO STORAGE. JG
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-07-08 Cont ID  
Sent By kalexand Date 2020-07-08 Time   Rev Time  
Received By rthermid Date 2020-07-08 Time   Sent To I
Notes
2020-07-08 11:01:02REVIEWED BY KIZZI ALEXANDRE


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved