Plan Review Details - Permit 20061019
Plan Review Stops For Permit 20061019
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-20 Cont ID  
Sent By cthroop Date 2020-10-20 Time 06:53 Rev Time 0.00
Received By cthroop Date 2020-10-20 Time 06:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-27 Cont ID  
Sent By cthroop Date 2020-07-27 Time 09:17 Rev Time 0.00
Received By cthroop Date 2020-07-27 Time 08:24 Sent To  
Notes
2020-07-27 09:18:42PLAN REVIEW ? GENERATOR - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR PER FBC
 107.3.5.3 AND R301.2 AS REQUIRED FOR THE GENERATOR PAD
 ENGINEERING.
 2) STRUCTURAL DETAIL OF PAD AND DESIGN LOADS SHALL BE
 SIGNED AND SEALED BY A DESIGN PROFESSIONAL.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-07-27 Cont ID  
Sent By cthroop Date 2020-07-27 Time 09:15 Rev Time 0.00
Received By cthroop Date 2020-07-27 Time 08:24 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2020-10-21 Cont ID  
Sent By cthroop Date 2020-10-21 Time 16:34 Rev Time 0.00
Received By cthroop Date 2020-10-21 Time 16:34 Sent To  
Notes
2020-10-21 16:35:03APPLICANT REQUESTS TO REMOVE GAS REVIEW FROM SUBMITTAL.
 A SEPERATE GAS PERMIT IS REQUIRED. CT

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-10-20 Cont ID  
Sent By cthroop Date 2020-10-20 Time 07:03 Rev Time 0.00
Received By cthroop Date 2020-10-20 Time 06:27 Sent To  
Notes
2020-10-20 07:08:41PLAN REVIEW GENERATOR - FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CITY RECORDS INDICATE AN EXISTING GAS SERVICE AT THIS
 RESIDENCE.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 1) GAS ISOMETRIC DRAWING:
 1A) PROVIDE AN ISO DRAWING SHOWING THE ENTIRE SYSTEM
 INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST
 REMOTE OUTLET. THE BTUH LOAD OF EACH EXISTING APPLIANCE
 AND THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON
 THE DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES. (NOT
 ADDRESSED) (PROVIDE TOTAL LOAD OF EXISTING APPLIANCES -
 W/H, DRYER, RANGE AND FUTURE BBQ GRILL)
  
 NOTE: YOU MAY PROVIDE THE EXISTING LOAD AS ONE
 CALCULATION ON THE GAS RISER
  
 1B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH
 LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 &
 G2413.4.3. (NOT ADDRESSED)
  
 1B) CORRECTED
 1C) CORRECTED
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-27 Cont ID  
Sent By cthroop Date 2020-07-27 Time 09:19 Rev Time 0.00
Received By cthroop Date 2020-07-27 Time 08:24 Sent To  
Notes
2020-07-27 09:21:02PLAN REVIEW GENERATOR - FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CITY RECORDS INDICATE AN EXISTING GAS SERVICE AT THIS
 RESIDENCE.
  
 1) GAS ISOMETRIC DRAWING:
 1A) PROVIDE AN ISO DRAWING SHOWING THE ENTIRE SYSTEM
 INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST
 REMOTE OUTLET. THE BTUH LOAD OF EACH EXISTING APPLIANCE
 AND THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON
 THE DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES.
 NOTE: YOU MAY PROVIDE THE EXISTING LOAD AS ONE
 CALCULATION ON THE GAS RISER
 1B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH
 LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 &
 G2413.4.3. PROVIDED
 1B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE
 OUTLET OF THE REGULATOR- SECTION G2421.1
 1C) PROVIDE THE BTUH LOAD OF THE GENERATOR. G2413.2 FBC
 RES.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-20 Cont ID  
Sent By cthroop Date 2020-10-20 Time 07:08 Rev Time 0.00
Received By cthroop Date 2020-10-09 Time 16:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-27 Cont ID  
Sent By cthroop Date 2020-07-27 Time 09:16 Rev Time 0.00
Received By cthroop Date 2020-07-07 Time 15:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-10-20 Cont ID  
Sent By cthroop Date 2020-10-20 Time 06:53 Rev Time 0.00
Received By cthroop Date 2020-10-20 Time 06:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-27 Cont ID  
Sent By cthroop Date 2020-07-27 Time 09:16 Rev Time 0.00
Received By cthroop Date 2020-07-27 Time 08:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-20 Cont ID  
Sent By cthroop Date 2020-10-20 Time 06:52 Rev Time 0.00
Received By cthroop Date 2020-10-20 Time 06:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-27 Cont ID  
Sent By cthroop Date 2020-07-27 Time 09:18 Rev Time 0.00
Received By cthroop Date 2020-07-27 Time 08:24 Sent To  
Notes
2020-07-27 09:19:38PLAN REVIEW GENERATOR - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15
  
 2) DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 3) UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
 4) FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
 NOTE: YOU MAY PROVIDE A PAPER PLAN WITH WET SIGNATURE
 AND SEAL PRIOR TO PERMIT.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By kalexand Date 2020-07-17 Time   Rev Time  
Received By   Date 2020-07-17 Time   Sent To I
Notes
***NONE***